Infrared Ceiling Mounted Occupancy Sensor

Cat. No. LIRO H

To be used with 24VDC

 LPCS Series Power Pack Class II Low-Voltage Wiring

INSTALLATION INSTRUCTIONS

Typical Installations:

Listed are 3 typical installation options (A, B, and C). Choose one that best suits

 your needs. Other methods of installation may be possible but they have not been

described here.

A. Drop Ceiling Installation (Mounting Option A):

NOTE: Use the threaded rod included.

1. Select location for mounting of sensor and proper masking for your application

(refer to Mounting Location Diagram).

2. Use the supplied threaded rod or other methods to make a hole (1/2" to 1") in the

ceiling tile just large enough to pass the body of the threaded rod through.

3. Insert the sensor wires through the flared end of the threaded rod. Position the

threaded rod to the base of the sensor.

4. Insert the flared end of the threaded rod into the opening in the bottom of the

sensor and twist to lock into place.

DI-400-OSC15-00A-X1

Tools needed to install your Sensor:

Slotted/Phillips Screwdriver

Electrical Tape

Pliers

Pencil

Cutters

Parts Included List:

)

1

(

 t

u

N

 

x

e

H

 

d

n

a

 

)

1

(

 

d

o

R

 

d

e

d

a

e

r

h

T

)

1

(

 

r

o

s

n

e

S

#8-32 x 1/2" Screw (2)

Half Mask (1)

#8-32 x 1-1/2" Screw (2)

360

°

 Perforated Mask (1)

#8-32 Washer and Nut (2)

Plastic Washer (1)

DESCRIPTION

The Occupancy Sensor is a low-voltage infrared sensor that works with the LPCS Series

power pack to automatically control lighting. The sensor turns the lights on and keeps

them on whenever occupancy is detected and will turn them off after the ‘delayed-off

time’ has expired.
The sensor continually analyzes and adjusts to changing conditions. The sensor uses

the latest microprocessor-based technology which permits it to continually adjust and

optimize its performance.
Infrared motion detection gives higher false triggering immunity that yields a sensor with

excellent performance.

INSTALLING YOUR OCCUPANCY SENSOR

NOTE: Use check boxes       when Steps are completed.

WARNING:

 

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER

at circuit breaker or fuse and test that power is off before wiring!

Preparing and connecting wires:

Step 1

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

WARNINGS AND CAUTIONS:
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult a qualified electrician.
• Sensors must be mounted on a vibration free surface.
• All sensors must be mounted at least 6 feet away from air vents.
• Do not touch the surface of the lens. Clean outer surface with a damp cloth only.

Step 3 cont’d

Mounting Option Diagram A

Occupancy Sensor Mounted to Drop Ceiling Using Threaded Rod

Low-Voltage Wires

NOTE: Wires routed through  

the Threaded Rod 

Drop Ceiling

1" thick maximum

Nut

Washer

Threaded Rod

5. Push the wires into the hole in the ceiling tile and insert the threaded rod until the

sensor is flush with the tile.

6. Insert wires through the hole in the included washer, then place the included

washer over the rod and screw on the included hex nut.

7. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per

WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit

conductors, push firmly into appropriate wire connector. Screw connectors on

clockwise making sure that no bare conductor shows below the wire connectors.

Secure each connector with electrical tape.

8. Rotate the sensor to the desired orientation. Note that the sensor base and back

cover are keyed. To lock the device in place, ensure that the arrows are not aligned.

9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS

COMPLETE.

C. Junction Box or Surface Mount Raceway Installation (refer to

Mounting Diagrams):

NOTE: Listed below are suggested JUNCTION BOX installation applications which

require mounting to conduit in one of the following three ways:

Step 3 cont’d

Mounting Option Diagram B

Occupancy Sensor Mounted to Wallboard

or Drop Ceiling Using Screws

Low-Voltage Wires

Wallboard  

Ceiling

Sensor  

Back Cover

Sensor Base

Keylock Arrow

Mounting Screws

(2 places)

Sensor Front Cover

Low Voltage Wires

Wallboard Ceiling

Back Cover open center to

route Low-Voltage Wires

Mounting Screw

Back Cover internal

surface shown

Back Cover shown mounted 

on ceiling with screws

Nut (2 places)

Washer (2 places)

Step 2

B. Wallboard or Drop Ceiling Installation (Mounting Option B):

NOTE: You may use the mounting screws, nuts and washers included, or screws in

combination with commercially available wall anchors.

1. Select location for mounting of sensor and proper masking for your application

(refer to Mounting Location Diagram).

2. Make a hole in the ceiling tile or wallboard large enough to pass the wire

connections and wire nuts through (approximately 1" diameter).

3. Remove the back cover of the sensor. Hold the back cover and body of the sensor

and rotate until the two arrows line up and pull apart.

4. Install back cover of the ceiling sensor to the wallboard or drop ceiling using the

included screws, nuts and washers, or screws in combination with commercially

available wall anchors.

5. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per

WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit

conductors, push firmly into appropriate wire connector. Screw connectors on

clockwise making sure that no bare conductor shows below the wire connectors.

Secure each connector with electrical tape.

6. Push wire connections through the center hole of the back cover and into the ceiling.
7. Secure the sensor body to the back cover by aligning the arrows. Lock it by

turning the sensor such that the arrows do not line up.

8. Rotate the sensor to the desired orientation.
9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS COMPLETE.

Occupancy Sensor Mounted to Octagon

Box Installed Flush to Wallboard Ceiling

#8-32 Screws 

(2 places)

Octagon Box

4" x 1 1/2" deep 

Low-Voltage  

Wires 

Wallboard or

Drop Ceiling

FCC COMPLIANCE STATEMENT:

T

his device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1)

This device must not cause harmful interference, and (2) This device must accept any interference received,

including interference that may cause undesired operation.

Step 3 cont’d

Occupancy Sensor Mounted to Round Fixture

with Raceway for Wallboard Installation

Wire Mold Back Cover

Back Cover Screws

(4 places)

Wire Mold Round Fixture

Box Cat. No. V5738 

(for raceway mount)

Mounting Screws 

(4 places)

Low-Voltage Wires

Wallboard Ceiling

Wire Mold Raceway

(use applicable fittings)

Hot (Black)

Neutral (White)

Load

Blue

(Control)

Black

Black

Red (24VDC)

Blue

Blue

Red

Blue

White

Black

White

Black

Red

Gray

*

Blue

Black

Line 

120/277/347VAC

 60Hz

Sensor

LPCS Series

Power Pack

NC-Brown

NO-Brown/White

Common-Green

To HVAC

System

(DCO Only)

Gray

*

Wiring Diagram 1: Multiple Sensor, Single Power Pack

Catalog No.

LIRO H

Description

Extended Range

Coverage

1500 sq. ft.

Suggested

Mounting Location

Mount in center

of room/area

Current

Consumption

20mA

CATALOG ITEMS

*

NOTE: When using the

Photocell function, connect

the Gray wire of the sensor

to the Blue wire of the

power pack. 

DO NOT use

the Blue wire of sensor.

NOTE: Cap all unused

wires.

Name

Color

Gauge

Temp/Voltage

Power (+24V)

Red

  24

200

°

 C/ 600V

DC Return

Black

  24

200

°

 C/ 600V

Occupancy

Blue

  24

200

°

 C/ 600V

Occupancy/Photocell

Gray

  24

200

°

 C/ 600V

TABLE 1: WIRE DESIGNATIONS

Step 3

Cut

(if necessary)

1/2"

(1.3 cm)

Strip Gage (measure

bare wire here)

CDCS000281