Installation and Commissioning Guide
Variable Capacity Commercial
PRELIMINARY DATA ONLY Ver. 5.01 210406
THIS LABEL TO BE REMOVED ON SIGN-OFF
19
Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial
Doc. Part No. 0525-067 Ver. 5 210414
10. Condensate and Safety Tray Drainage Instructions
OUTDOOR COIL
COMP
INDOOR
FANS
INDOOR
FANS
ID COIL
NOTES
• PKV Under and Over model shown for illustration
purposes only.
• Ensure that Condenser and Evaporator condensate
drains are connected separately.
SUGGESTED DRAIN TRAP DETAILS
Ensure Drain Pipe slopes down
from the unit at a minimum of
10mm per meter
DETAIL A
The top of the Trap must
be 125mm below the top
of the Evaporator Drain
Connection
50mm
4 x PVC
Elbow
Install a T-Piece
as an Air Vent
for long drain runs
Hose
Clamps
Condensate Tray
The top of the Vent must be
50mm higher than the top of
the Evaporator Condensate
Tray
250mm or high enough
to
maintain positive Air Seal
Condensate Drain
Connection
DN 25mm PN12
Trap
Clear
Plastic
Inspection
Tube
125mm
TOP VIEW
FRONT VIEW
A
Ensure Condensate Drain Connection Drain Pipe slopes
down from the unit at a minimum of 10mm per meter.
Seal with
Silicon Sealant
Ensure Condensate Drain
Connection Drain Pipe slopes
down from the unit at a mini-
mum of 10mm per meter.
Содержание PKV290T-L