Installation and Commissioning Guide
ESP Platinum QUE - Three Phase
11
ActronAir is constantly seeking ways to improve the design of its products, therefore specifications are subject to change without notice.
Copyright © 2019 Actron Engineering Pty. Ltd.
06. Unit Lifting Procedures
WARNING
WH&S regulations must be observed and will take precedence during lifting process.
DANGER
Make sure rigging equipment, accessories and plant are sufficiently and safely capable to lift the unit in order to prevent potential
damage to property, severe personal injury or death. Please check unit weight and weight distribution points on unit drawing
dimensions section.
06.01. Crane Lifting Method
NOTE
• Crane lifting method is recommended for high rise lifting.
• Refer to catalogue for unit weight before selecting shackles and slings.
• Lifting procedure and unit model shown are suggestions and for illustration purposes only.
• It is highly recommended that installer observe current industry safe and sound rigging and lifting procedure.
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Confi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airfl ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Fig. 1
Connect the loop ends of
slings onto shackle
DETAIL A
Slip nylon slings
through the palle
t
INDOOR UNIT
PALLET
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Confi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. airfl ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Specifi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
A
Provide rubber pads
to prevent damage to
the unit
EQUIPMENT REQUIRED FOR CRANE LIFTING: 1 x shackle ; 2 x nylon slings; 4 x rubber pads
Procedure:
1. Slip nylon slings through the pallet as shown in Fig. 1.
2. Use a Bow or Dee shackle to connect the slings.
3. Ensure slings are protected by rubber pads or similar if slings are draped across unit edges, corners, or air grilles . This
will prevent the unit from being damaged during lifting.
4. Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location.