46
PERFORMANCE DATA
Calculation Steps
Interpolation
method can be used to get the total
cooling capacity,
TC
and sensible cooling capacity,
SC
and power input,
PI
at those temperatures which
are not stated out in the table. Extrapolation method
is not allowed to be used.
Example:
Model:
A5DB100H – A5MC100H
Indoor Condition:
25°C DB, 17°C WB
Outdoor Condition:
37°C DB
Fan Speed:
High (3000 CFM)
Solution:
Based on the Performance Table,
1. Refer to the Indoor DB column,
-
25°C
is located between 24°C & 27°C
for 16°C WB.
-
25°C
is located between 24°C & 27°C
for 19°C WB.
-Thus, Interpolation needs to be applied.
2. Refer to the Indoor WB column,
-
17°C
is located between 16°C & 19°C
for 25°C DB.
-Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
-
37°C
is located between 35°C & 40°C.
-Thus, Interpolation needs to be applied.
1
st
Step
Interpolation of Indoor WB
Find TC, SC & PI
(a) Indoor:
25°C DB
, 16°C WB
Outdoor: 35°C DB
(b) Indoor:
25°C DB
, 19°C WB
Outdoor: 35°C DB
(c) Indoor:
25°C DB
, 16°C WB
Outdoor: 40°C DB
(d) Indoor:
25°C DB
, 19°C WB
Outdoor: 40°C DB
2
nd
Step
Interpolation of Indoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB,
17°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB,
17°C WB
Outdoor: 40°C DB
3
rd
Step
Interpolation of Outdoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB, 17°C WB
Outdoor:
37°C DB
Details of Calculation:
1
st
Step:
To obtain the TC, SC & PI for
(a) Indoor Condition:
25°C DB, 16°C WB
Outdoor Condition:
35°C DB
EWB
EDB
Outdoor temperature
35°C
TC
SC
PI
16
24
26.67 23.01
9.83
25
x
1
y
1
z
1
27
27.44 26.09
9.88
By Interpolation Method
25°C – 24°C
=
x
1
– 26.67kW
27°C – 24°C
27.44kW – 26.67kW
x
1
= 26.93kW
Similarly
,
y
1
= 24.04kW
z
1
= 9.85kW