Caution
Please take note of the following important points when installing.
•
Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
•
Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the
furniture.
•
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
•
Ensure that the units panel is closed after service or installation.
Unsecured panels will cause unit to operate noisily.
INSTALLATION LOCATION
•
Installation work should be done by the authorized dealer or qualified contractor. Never install the unit
yourself.
•
Make sure there is sufficient airflow around the unit.
•
Vibration isolator should be provided to reduce the vibration and noise of the unit.
•
There should be sufficient space allocated for servicing and maintenance when installing the unit.
TRANSPORTATION
•
The unit should be lifted using a crane. Ensure that the hanger belts
are not touching the coil, top panel and front panel (use protective panel)
as shown in Figure 1.
•
The bolt of the base and channel support can be removed after
putting the unit on the fixed location.
Figure 1
WATER PIPING AND FITTING
•
All water pipe must be insulated to prevent capacity losses and condensation.
•
Install a 40-60 mesh strainer to ensure water quality is good.
•
Water pipe recommended are black steel pipe and copper pipe.
•
During installation, the piping of the unit should be clamp before rotating the installation pipe to reduce the
moment induce on the unit piping.
•
Users are recommended to install the pipe and accessories as shown in Figure 2 & 3.
•
An air vent must be installed at the highest position, while a drainage plug at the lowest position of
the water circuit. Open the air vent to release any air trap in the water circuit.
•
Run the clean water through the water inlet and operate the pump to drain out the dirty water. Clean
the strainer after running the pump for 30 minutes.
•
Fill up the water circuit after connecting the pipes and equipment. Check water leakage at all
connections and joints. Do not start the unit when the system is leaking.
•
To optimize the capacity of the system, ensure that the system is free of air bubbles. The air trapped
in the system would make the system unbalanced.
!
!
!
Содержание A4AC100C
Страница 1: ...Technical Manual AIR COOLED MINI CHILLER AMAC 20 150 C CR A4AC 20 150 C A4AC 60 150 CR A5AC 20 55 CR...
Страница 19: ...17 5 2 Menu Structures Menu Structure Diagram for Chiller...
Страница 140: ...138 9 WIRING DIAGRAMS MODEL A4AC AMAC20C...
Страница 141: ...139 MODEL A4AC AMAC25 30C...
Страница 143: ...141 MODEL A4AC AMAC80 100C WITH ISOLATED SWITCH...
Страница 144: ...142 MODEL A4AC AMAC 120 150C WITH ISOLATED SWITCH...
Страница 145: ...143 MODEL A4AC AMAC80 100C WITH TERMINAL BLOCK...
Страница 146: ...144 MODEL A4AC AMAC 120 150C WITH TERMINAL BLOCK...
Страница 147: ...145 MODEL AMAC 25 30CR...
Страница 149: ...147 MODEL A4AC AMAC 80 100CR WITH ISOLATED SWITCH...
Страница 150: ...148 MODEL A4AC AMAC 120 150CR WITH ISOLATED SWITCH...
Страница 151: ...149 MODEL A4AC AMAC 80 100CR WITH TERMINAL BLOCK...
Страница 152: ...150 MODEL A4AC AMAC 120 150CR WITH TERMINAL BLOCK...
Страница 153: ...151 MODEL A5AC20 25CR...