Marvair GAA A/C w/Gas Heat I&O Manual

06/2023 Rev.5

1.5  Sequence of Operation - Heating Mode

1.   On a call for heat, two stage thermostat contact( s ) close, providing 24 VAC to “4” terminal on 

the ignition control.

2.   Draft inducer is energized at high speed ( B-W leads ) at line voltage.
3.   Air Pressure Switch ( APS ) closes, initiating 30 second prepurge.
4.   At end of 30 second prepurge period, Spark & Gas Valve are energized for up to 5 second 

ignition trial. Gas valve will open in either low or high fire position, depending upon the heat 

requirements and contact closure in the thermostat.

5.  Burners ignite and carryover.
6.  Flame is detected by flame sensor and control operates in steady state heating position.
7.   The two stage thermostat powers the low fire contact continuously on a call for heat and will 

close the high fire contact if necessary to meet heat requirements. Unit continues in operation 

in either low or high fire until the thermostat set point is reached.

8.   Low fire contact in thermostat opens, interrupting power to “4” terminal on control and closing 

the gas valve.

9.   The Draft inducer continues to run for a 60 second post purge period.
10.   The control system is capable of three retrials if the above sequence is interrupted at any point.

If the above sequence does not occur then:

11.   If ignition is not achieved with in 5 seconds, the gas valve is shut off, the inducer keeps running for 

an inter purge period of 60 seconds and additional trials follow the specified sequence. If all 3 trials 

for ignition have occurred without proper ignition and flame detection, the control is locked out.

12.   Control may be brought out of lock out by a. turning the thermostat to OFF for a minimum of 

5 seconds and then ON, or b. turning the disconnect to OFF for a minimum of 5 seconds and 

then ON. Control will automatically also attempt another ignition sequence one hour after a 

lockout occurrence.

13.   If flame is lost once it has been established, the control will shut off the gas supply within .8 

seconds and enter the interpurge period. Control will initiate up to 3 additional trials per normal 

sequence of operation. ( To restart, refer to item 12 ).

14.   If flame sensor indicates presence of a flame during the purge period when no flame is present, 

the inducer will remain energized, but the gas valve will not be energized until the cause of the 

false flame is removed.

15.   If the air pressure switch ( APS ) is closed when the inducer is energized or does not close after 

the inducer is energized, the control will wait one minute for the air switch to open or close and 

then lock out. ( To restart, refer to item 12 ).

16.   If the control detects power to the gas valve when the it should be off or no power when it 

should be on, the control will go into lockout with all outputs off. ( To restart, refer to item 12 ).

Содержание Marvair GAA1024A

Страница 1: ...th INSTALLER Affix the instructions on the inside of the building adjacent to the thermostat END USER Retain this manual for future reference Air Conditioner Product Manual Vertical Wall Mount Air Con...

Страница 2: ...T the UNIT UPRIGHT Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components 3 TURN ELECTRICAL POWER OFFAT THE breaker or fuse box BEFORE installing o...

Страница 3: ...tion ou entretien peut causer d g ts mat riels et dommages corporels ou m me mort Installation et interventions doivent tre effectu es par un installateur ou une agence de d pannage qualifi s ou par l...

Страница 4: ...r Inlet and Outlet 61 7 11 Venting of the Furnace 61 7 12 Clearances 61 Chapter 8 Parts List 62 Chapter 9 WarrantyPolicy 9 1 Marvair Limited Product Warranty 64 Illustrations Figure 1 Enthalpy Sensor...

Страница 5: ...Hand90 000BTUH ModelsGAA1042A GAA1048AandGAA1060A arefactory set up for natural gas with nominal heating capacities are 75 000 BTUH 100 000 BTUH and 125 000 BTUH The units are easily field convertible...

Страница 6: ...sor None 18 Air Flow 1 Top Supply Bottom Return 19 Compressor Location D Left Hand E Right Hand 20 Filter Option A 2 Pleated MERV 8 AC HP C C 2 Charcoal D MERV 11 High Filtration Package E MERV 13 Hig...

Страница 7: ...nition is not achieved with in 5 seconds the gas valve is shut off the inducer keeps running for an inter purge period of 60 seconds and additional trials follow the specified sequence If all 3 trials...

Страница 8: ...tion Thermostatmustprovide the fan G signal to HVAC to activate the indoor blower Forced Mechanical Cooling When 24VAC is applied to the FC input of the economizer board the economizer damper is force...

Страница 9: ...vice the motorized damper opens to 100 open position and the indoor blower is forced to operate During Emergency Ventilation mode the compressor and heater do not operate The relay has a wire lead ext...

Страница 10: ...ormation to the end user Special features include 2 Stage operation with varying speed control to optimize latent and sensible capacity built in remote communication Modbus for monitoring and or contr...

Страница 11: ...age 23 Control Board Power Indicator LED 2 2 Installation and Replacement ThePCBisfactoryinstalled ToinstallareplacementPCB usethesixmountingholesalongwiththeappropriate screw size to firmly secure th...

Страница 12: ...elay in seconds 4 IBM Y1 Set 80 40 100 G Fan only and Y1 1st Stage Cooling Indoor Blower Speed Setting 5 IBM Y2 Set 100 40 100 Y2 2nd Stage Cooling Indoor Blower Speed Setting 6 OFM Select P P dC P PW...

Страница 13: ...orhigh pressurelockout 6 OFM Select This setting allows the IBM Indoor Blower control signal to be configured for PWM or 0 10vdc control The default control output signal is PWM 7 OFM Set This is an i...

Страница 14: ...default to compressor cooling if any sensor becomes disconnected or faulty ChangingtheECONOSelecttoN no willdisableeconomizeroperationandtheeconomizer function will be ignored 13 SensorType Thissettin...

Страница 15: ...re Version Number The software version of the 92589 control board will be displayed on the seven segment display This is for informational purposes only 2 4 Operation Power The Marvair PCB requires 24...

Страница 16: ...ps 5 0 Dehumidification Operation AC HP 5 1 Hot Gas Reheat 5 2 Electric Reheat 6 0 Refrigeration Protection 6 1 High Pressure lockout 6 2 Low Pressure Lockout Freeze Protection 6 3 Anti Short Cycle 7...

Страница 17: ...ority This means that in any combination involving the G input the speed associated to Fan Only will never take precedence The priority list from Highest to Lowest goes as follows 1 Y2 Request 2 Y1 Re...

Страница 18: ...l the switch reopens at 290 PSIG These outputs function as described until the Cooling setpoint is satisfied This is considered as ON OFF fan cycle control and the PSC motor will not modulate Note Sin...

Страница 19: ...nce Y2 has higher priority These outputs remain energized until the cooling setpoint is satisfied Once the setpoint is satisfied the Compressor and the Outdoor fan outputs are de energized The Indoor...

Страница 20: ...e testing of the air conditioner at the factory the control board has been configured for the sensor type used in the system There should be no need to change the sensor configuration If an enthalpy s...

Страница 21: ...rovides a signal to the economizer controller for modulating the position of the damper The default supply air temperature is 55F in economizer cooling and is not adjustable A disconnected or faulty s...

Страница 22: ...a defrost cycle based on the time selected in the control board configuration menu setting 8 The defrost time intervals selections are 30 60 and 90 minutes and the factory default setting is 30 minut...

Страница 23: ...in off as long as the request for W2 is active Once the request for W2 satisfies the compressor will be allowed to operate The default setting for SCKT is N No the electric heat and compressor will be...

Страница 24: ...re of 80F and 115F Systems with PSC Outdoor Motors utilizes a Fan Cycle Switch which closes at 400 PSIG to energize the OFR outdoor fan relay to start the outdoor fan which runs until the switch reope...

Страница 25: ...ng it from excessive short cycling When the compressor goes off due to any fault emergency or if the cooling heat pump heating setpoint is satisfied a built in 3 minute timer locks the compressor for...

Страница 26: ...and the system will operate in normal cooling mode until the request for FC is satisfied Once satisfied the system will be allowed to return to economizer operation if conditions are favorable 7 4Low...

Страница 27: ...instructions could result in severe personal injury or death due to carbon monoxide poisoning if combustion products infiltrate into the building Check that all openings in the outside wall around the...

Страница 28: ...burned completely or when the flame does not receive sufficient oxygen Therefore to help alert people of potentially dangerous carbon monoxide levels you should have a commercially available carbon m...

Страница 29: ...ring cold weather you should take these precautions 1 Turn off the water supply to the structure and drain the water lines if possible and add an antifreeze for potable water to drain traps and toilet...

Страница 30: ...au du ou des autres appareils Reportez vous la section Ventilation de la chaudi re dans ce manuel d instructions 4 1 Location and Clearances Choose the location or evaluate the existing location based...

Страница 31: ...The furnace ductwork and filters are cleaned as necessary to remove drywall duct and construction debris from all HVAC system components after construction is completed d Verify proper furnace operat...

Страница 32: ...gnations 15 Marvair GAA air conditioners with gas heat may be used for heating and cooling in buildings under construction provided thatALL installation procedures described in this manual are followe...

Страница 33: ...eight BASIC MODEL GAA1024A GAA1030A GAA1036A SHIP WEIGHT LBS 335 415 415 SHIP WEIGHT KG 152 189 189 Filter Size inches BASIC MODEL GAA1024A GAA1030A GAA1036A FILTER SIZE IN 30 x 16 x 2 FILTER SIZE MM...

Страница 34: ...RESSOR ACCESS FROM LEFT SIDE Shipping Weight BASIC MODEL GAA1042A GAA1048A SHIP WEIGHT LBS 555 580 SHIP WEIGHT KG 252 264 Filter Size inches BASIC MODEL GAA1042A GAA1048A FILTER SIZE IN 18 x 24 x 1 FI...

Страница 35: ...GHT LBS 555 580 595 SHIP WEIGHT KG 252 264 270 Filter Size inches BASIC MODEL GAA1042A GAA1048A GAA1060A FILTER SIZE IN 18 x 24 x 1 FILTER SIZE MM 457 x 610 x 25 FILTER PART 2 FILTERS UNIT 81199 502 m...

Страница 36: ...start makes excessive noise or will not operate return the unit to the freight carrier General 1 Inspect unit for completeness Check for missing parts e g hardware Refer to the installation kit inform...

Страница 37: ...t and cool setpoints Manual or automatic changeover System switch Off Cool Heat Emergency Heat Fan Switch Auto On Keypad lockout available Ventilation terminals No batteries required Display indicates...

Страница 38: ...incorrecte de la tuyauterie peut entra ner mort blessure corporelle et ou d g ts mat riels Sur chaque installation le syst me de conduites doit tre bien calcul et install afin d assurer un flux d air...

Страница 39: ...tions to duct work and grilles Use fabric boots to prevent the transmission of vibration through the duct system The fabric must be U L rated UL 181 to a minimum of 197o F Note Followlocalcodesandstan...

Страница 40: ...iping WARNING CARBON MONOXIDE FIRE AND EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death and or property damage Models designated for Natural Gas are to b...

Страница 41: ...mat riels Utilisez une cl pour maintenir la vanne de contr le de gaz de la chaudi re quand vous tournez coudes ou conduite de gaz afin d viter d endommager la vanne et la chaudi re 3 Use black iron o...

Страница 42: ...on of LP gas is recommended WARNING FIRE OR EXPLOSION HAZARD A natural gas or LP gas leak ignited by an open flame or spark could result in death personal injury and or property damage Natural gas is...

Страница 43: ...nne liaison de terre est r alis e avant de brancher la tension d alimentation secteur MarvairGAAairconditionerswithgasfurnaceMUSTbewiredandgroundedinaccordancewithelectrical codes or in the absence of...

Страница 44: ...by monitoring the temperature of the refrigerant lines at the compressor The temperature should rise on the discharge line while the suction line temperature decreases Reverse rotation also results i...

Страница 45: ...C I F I D I M U H E D M U H N A F G T A E H C I R T C E L E 2 W E V L A V G N I S R E V E R O T N E V Y C N E G R E M E V E L O O C D E C R O F C F 3 3 1 0 5 K 4 3 1 0 5 K 3 1 1 0 5 K D R O C E R N O...

Страница 46: ...1 1 K B 811 KB 611 KB 711 KB 14 LB 04 Y 221 RB 121 KB 221 RB 121 KB 04 Y 14 LB 2 1 L B 6 KB 6 K B 31 KB 6 1 K B 61 KB 31 KB 801 R 701 LB 601 KB 211 KB 311 KB 211 KB 311 KB 5 1 1 R 4 1 1 R 411 R 511 R...

Страница 47: ...ed verti cally Use only the vent supplied with the unit Vent connectors shall not be connected into any portion of mechanical draft systems operating under positive pressure WARNING CARBON MONOXIDE PO...

Страница 48: ...MM DIATEMENT le gaz et l alimentation secteur de l unit V rifiez s il y a des erreurs de c blage des fuites de gaz ou des obstructions au soufflage 5 1 Gas Supply Pressure Gas supply pressure should b...

Страница 49: ...d clockwise to increase the manifold pressure Set the manifold pressure to 3 5 w c for Natural Gas and 10 0 w c for LP gas Only adjust the setting marked HI A 3 32 Allen Key is required for adjustment...

Страница 50: ...nace has the correct main burner orifices for the altitudeof the site Refer to the following table for the correct orifice for both natural and propane gas HMG 22 500 BTUH Burner Used with GAA1024 103...

Страница 51: ...personal injury or loss of life The qualified service agency performing this work assumes the responsibility for the proper conversion of the appliance with this kit AVERTISSEMENT DANGER D INCENDIE MO...

Страница 52: ...lly leak check union fitting and connection at gas valve using soap suds or a liquid detergent to each joint Bubbles indicate a leak Correct even the smallest leak immediately Do NOT use a flame to ch...

Страница 53: ...rsion must be done by a qualified service agency in accordance with the following instructions or in the absence of local codes the applicable national code AVERTISSEMENT DANGER D INCENDIE EXPLOSION O...

Страница 54: ...2 80 0 1102 2 40 0 0945 2 90 0 1142 Table 7 Altitude Orifice Sizing NOTE Data for LP gas is based upon a 0 60 specific gravity For fuels with different specific gravity consult the National Fuel Gas C...

Страница 55: ...e caused by one or more of the following 1 Lint or dirt inside the burner or burner ports 2 Lint or dirt at the air inlet between the burner and the manifold pipe or 3 An obstruction over the burner p...

Страница 56: ...switch to Off 2 Move the cooling temperature on the wall thermostat to a point higher than the room temperature Move the heating temperature to a temperature that is lower than the room temperature 3...

Страница 57: ...ntrol will also attempt another ignition sequence after a one hour after a lock out occurrence 13 If flame is lost once it has been established the control will shut off the gas supply within 0 8 seco...

Страница 58: ...58 Marvair GAA A C w Gas Heat I O Manual 06 2023 Rev 5 6 3 Start Up Checklist...

Страница 59: ...ar once prior to the heating seasonandoncepriortothecoolingseason Atthistimethefilters evaporatorcoil condensercoil the cabinet and condensate drains the burner flame the burner and the combustion air...

Страница 60: ...econdary drain has a stand pipe An obstruction will forcewatertodumpintothemiddleoftheunitanddrainoutthesidesofthe air conditioner causing discoloration of the side panels If discoloration is noted se...

Страница 61: ...ged limiting air flow 6 Make sure all service panels are in place 7 11 Venting of the Furnace The MarvairGAAwall mounted air conditioner with gas heat furnace is a Category I furnace i e a cen tral fu...

Страница 62: ...8 DD Outdoor Motor HP RPM 40190 40190 1 2 ECM 1 2 ECM Fan Blade Clockwise Rotation 30236 30236 T2404 20 T2404 20 High Pressure Control 660 Open 450 Close 70656 70656 Low Pressure Control 40 Open 60 Cl...

Страница 63: ...ed Draft Blower 3000 RPM 0 9 A 230 v 30064 Induced Draft Blower 460 v Pressure Switch Low 0 36 WC PR 70377 Pressure Switch High 1 1 WC PF 70373 Flame Rollout Switch L270 Spark Igniter Flame Sensor In...

Страница 64: ...r material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by operating or staging the unit in a corrosive environment 4 Damages caused...

Отзывы: