Model TT339-0700
4-Wire Isolated Frequency Transmitter w/USB
Acromag, Inc. Tel: 248-295-0880
[
13
]
http://www.acromag.com
USB Connections
This transmitter is configured and calibrated via configuration software that runs on
Windows-based PCs connected to the transmitter via USB (Windows XP or later
version required). Refer to the following drawing to connect a PC to the transmitter
for the purpose of configuration
WARNING:
The intent of mating USB with this
transmitter is so that it can be
conveniently configured and
calibrated in a safe area, then
installed in the field which may be
in a hazardous area. Do not
attempt to connect a PC or laptop
to this transmitter while installed
in a hazardous area, as USB energy
levels could ignite explosive gases
or particles in the air.
USB Signal Isolation is recommended and required when connected to a grounded
input.
Input and USB connections are isolated from the output of this transmitter.
USB isolation is recommended for safety and noise suppression reasons, but
required when the input signal is grounded (i.e. when non-insulated or grounded
sensors are used). Acromag model USB-ISOLATOR may be used to isolate the USB
port, or optionally a different USB signal isolator that supports USB Full Speed
operation (12Mbps).
IMPORTANT
: USB logic signals to the transmitter are referenced to the potential of
the transmitter’s input ground. This ground is held in common with USB ground and
USB cable shield ground. Thus, an isolator is required when the input signal is
grounded and the transmitter is connected to the USB port of an earth-grounded
PC. The use of an isolator can be avoided if a battery powered laptop PC is used to
connect to the transmitter, and the laptop has no other earth ground connection,
either directly or via a connected peripheral.
PERSONAL COMPUTER
RUNNING WINDOWS OS
1 METER USB CABLE
USB-A MALE
TO HOST USB PORT
HOST
USB
HOST USB SERIAL
PORT CONNECTOR
AT BACK OF PC
CONFIGURATION
SOFTWARE
ACROMAG
HOST PC RUNNING
USB-B MALE
D
E
V
IC
E
C
O
N
N
E
C
T
P
C
C
O
N
N
E
C
T
POWER
RESET
CONNECTION
USB-A MALE
TT SERIES USB TRANSMITTER CONNECTIONS
(RECOMMENDED)
USED FOR CONFIGURATION AND CALIBRATION OF THE TRANSMITTER IN A SAFE OR ORDINARY LOCATION
C
A
B
L
E
M
o
d
e
l
4
0
0
1
-1
1
3
MODEL NO. - USB-ISOLATOR
Model 4001-112
Refer to Configuration Software Kit, Model TTC-SIP, which includes:
1 ea, Model 4001-113 USB Cable
1 ea, Model 4001-112 USB Cable
1 ea, Model USB-ISOLATOR
1 ea, Configuration Software CDROM 5040-944
USB MiniB MALE
USB MiniB Socket
(Front-Panel of Module)
MODEL TT3XX TRANSMITTER
12 – 32V
DC POWER
SUPPLY
+
–
– TB4-11
+ TB4-12
TB3
(OUTPUT)
TB4
(POWER)
TB1
(INPUT)
TB2
(INPUT)
!