Model TT231-0600
Two-Wire RTD Transmitter w/USB
Acromag, Inc. Tel: 248-295-0880
- 26 - http://www.acromag.com
- 26 -
http://www.acromag.com
Message Bar
The system message bar at the bottom of the screen will display & repeat prompt
instructions as you step through I/O calibration. It also displays diagnostic
messages. For example:
“Error: Input Zero can only accept whole numbers.”
“Error: Input Span can only accept whole numbers.”
“Error: Output Zero accepts positive numbers with up to 4 decimals.”
“Error: Output Zero accepts positive numbers with up to 4 decimals.”
“Error! Input must be less than 850°C!”
“Error! Input must be less than 1562°F!”
“Error! Output Zero must be between 3.5 and 6mA!”
“Error! Output Full-Scale must be between 16 and 24mA!”
“Error during calibration! Please increase range and try again.”
“Error during calibration! Please lower your input zero or increase your full-scale
value!”
“Error during calibration! Please raise your input zero or increase your full-scale
value!”
“Step 1: (Zero calibration) Please set your input resistance to X Ohms. Measure the
corresponding output current and enter the measured value into the 'Measured
Current Output' field.”
“Error Reading Module! Please check your loop power!”
“Measured Output accepts positive numbers with up to 4 decimal numbers.”
“Error! Output Zero must be between 3.0 and 6mA!”
“Step 2: (Full-scale calibration) Please set your input to X Ohms. Measure the
corresponding output current and enter the measured value into the 'Measured
Current Output' field.”
“Measured Output Box accepts positive numbers with up to 4 decimal numbers.”
“Error! Measured Output must be between 15 and 24mA!”
“Step 3: (Linearization Calibration) Please set your input to X. Measure the
corresponding output current and enter the measured value into the 'Measured
Output Current' field.”
“Calibration Complete!”
“Measured Current Output Box accepts positive numbers with up to 4 decimal
numbers.”
“Error connecting to module! Only model TT231-0600 is compatible with this
software!”
“Reset Complete!
Output Span accepts positive numbers with up to 4 decimal numbers.”