Acromag ST132-0600 Скачать руководство пользователя страница 14

              MiniPuck Model ST132-06x0                                         Two-Wire TC/mV Transmitter        

                         

_________________________________________________________________________________ 

 

______________________________________________________________________________________ 
Acromag, Inc.           Tel: 248-295-0880           Email: 

[email protected]

             https://www.acromag.com 

14   

 
This section of the manual will walk you through the reconfiguration process 
step-by-step.  But before you attempt to reconfigure or recalibrate this 
transmitter, please make the following electrical connections: 

 

Calibration Connections: 

 
1.   Connect a precision voltage source or thermocouple calibrator to the 

input as required and observe proper polarity. 

 

An accurate input source adjustable over the range desired for zero and 
full-scale is required.  A thermocouple calibrator may also be used.  The 
input source must be accurate beyond the unit specifications (better 
than ±0.1%).  A good rule of thumb is that your source accuracy should 
be four times better than the rated accuracy you are trying to achieve 
with the transmitter.  For voltage inputs, use a voltage source with an 
output impedance of 100

 or less. 

 

In the absence of a thermocouple calibrator, a convenient method of 
configuring the TC input would be to use a precision mV source with the 
module’s CJC set to OFF.  Using this method allows the mV source to 
be wired directly to the input T/C terminals using copper wires.  The 
module’s cold junction compensation is turned off and the mV values 
applied to the input are the equivalent thermoelectric voltages that 
correspond to the minimum and maximum temperatures of your desired 
input range, and specific to each T/C type.  Refer to the table of the 
following page for a list of thermocouple voltages at specific 
temperatures.  After setting zero and full-scale in this manner, the CJC 
switch should be returned back to the ON position to enable cold 
junction compensation. 

 
2.   Wire an output current loop to the transmitter as shown in the Electrical 

Connections section.  You will need to measure the output current 
accurately in order to calibrate the unit.  You could connect a current 
meter in series in this loop to read the loop current directly.  
Alternatively, you could simply connect a voltmeter across a series 
connected precision load resistor in the loop, then accurately read the 
output current as a function of the voltage IR drop produced in this 
resistor (recommended).  In any case, be sure to power the loop with a 
voltage that minimally must be greater than the 12V required by the 
transmitter, plus the IR drop of the wiring and terminals, plus the IR drop 
in the load.  To compute the IR drop, be sure to use a current level that 
considers the over-scale current (~24mA).  The output load resistance 
and meter must be accurate beyond the unit specifications (better than 
±0.1%).  A good rule of thumb is that your load and meter accuracy 
should be four times better than the rated accuracy that you are trying to 
achieve with the transmitter. 

 

Loop Power Supply:

  Make sure that your power supply voltage level 

is at least 12V plus 0.020*load_resistance.  Ideally, it should be great 
enough to drive the over-range current of ~24mA into your load (i.e. 
greater than or equal to 12V+ 0.024*Rload, assuming the line drop is 
negligible and the maximum possible over-range current. 

 

Apply power to the transmitter output loop and always power the loop 
before connecting to USB.  You will not be able to calibrate the unit 
without loop power applied. 

 

 

 

CONFIGURATION 
STEP-BY-STEP 
 
Calibration 
Connections 
 

IMPORTANT:

 Do not connect 

the transmitter to your PC via 
USB without also booting the 
configuration software.  
Connection to USB is intended 
as a temporary connection for 
the purpose of setup and 
reconfiguration only.  If you 
connect to USB but do not 
boot the configuration, the 
output DAC will hold its last 
programmed value as the 
unit’s microcontroller awaits 
initialization via the host 
running configuration software. 

Содержание ST132-0600

Страница 1: ...2 0610 Two Wire Transmitter TC Input USER S MANUAL ACROMAG INCORPORATED Tel 248 295 0880 30765 South Wixom Road email sales acromag com Wixom MI 48393 2417 U S A Copyright 2011 Acromag Inc Printed in...

Страница 2: ...libration Connections Reconfiguration Zero Full Scale Calibration Other Configuration Controls SPECIFICATIONS 14 14 16 20 22 24 Model Numbers 24 Input 24 Output 26 USB Interface 27 Enclosure and Physi...

Страница 3: ...il Adapter CE Approved Model ST132 0610 is UL Listed USA Canada suitable for use in Class I Division 2 Groups A B C D Hazardous Locations or Nonhazardous Locations only Model ST132 0610 is ATEX Certif...

Страница 4: ...DIN Form B connection and thermowell protection heads similar to the figure at upper left The M4 mounting screws and relief springs used to attach the transmitter to the connection head are ordered se...

Страница 5: ...hock and vibration applications Since common mode voltages can exist on signal wiring adequate wire insulation should be used and proper wiring practices followed Output wires are normally separated f...

Страница 6: ...n see below Always connect the output power wires and apply loop power before connecting the unit to USB The output of this transmitter has a floating connection relative to ground which makes it flex...

Страница 7: ...ection is typically required and you should connect the metal enclosure s ground terminal green screw to earth ground using suitable wire per applicable codes See the Electrical Connections Drawing fo...

Страница 8: ...model USB ISOLATOR to isolate your USB port or you can optionally use another USB signal isolator that supports USB Full Speed operation 12Mbps Configuration Requires USB and Loop Power This transmit...

Страница 9: ...ol Set the level of filtering to be applied to the input signal CJC Control Select if the CJC is used On or Off I O Scaling Select the input range endpoints to scale to the 4 to 20mA output range endp...

Страница 10: ...s used to calibrate the input output and CJC temperature sensor of the unit Instructions on how to calibrate the unit is detailed in the Configuration Step by Step section of the Technical Reference p...

Страница 11: ...has broken Check your sensor connections to restore operation If connections are OK then your sensor value may be out of range or the unit has been mis calibrated Cannot Communicate with Transmitter v...

Страница 12: ...drop in the wire Ideally the voltage should have ample overhead to drive the load at the maximum output current of 25mA Cannot Calibrate Input Channel Is input wired properly Check input wires at ter...

Страница 13: ...the signals digitally filters the signals and performs analog to digital conversion The A D converter also switches the lead pullups pulldowns to facilitate upscale or downscale thermocouple break det...

Страница 14: ...d junction compensation 2 Wire an output current loop to the transmitter as shown in the Electrical Connections section You will need to measure the output current accurately in order to calibrate the...

Страница 15: ...50 2 585 2 023 2 036 3 048 0 296 0 299 1 340 100 5 269 4 096 4 279 6 319 0 647 0 646 2 774 150 8 010 6 138 6 704 9 789 1 041 1 029 4 302 200 10 779 8 138 9 288 13 421 1 469 1 441 5 913 250 13 555 10...

Страница 16: ...are faded out under these conditions Note that without a device already connected via USB the System Status window at the bottom of the screen prompts you to Connect a ST132 to a USB port After you c...

Страница 17: ...plays the Model the Manufacturer field displays Acromag Inc and the Serial field displays this model s serial number Additionally most of the other fields and controls are not faded out and await your...

Страница 18: ...play a message like No error encountered while reading configuration Select the Input Type T C Type or 100mVDC In the Configuration section of this screen select an input type T C Type J K T R S E B N...

Страница 19: ...the T C input using a voltage source that connects to the module via copper wires as opposed to the wire materials of the various thermocouple types Note CJC temperature values are only resolved to 0...

Страница 20: ...an get a feel for how stable CJC temperatures are by doing this You should turn polling off while trying to calibrate the unit or change its configuration Calibration of Input Output and Tref This sec...

Страница 21: ...0 0 52 410mV Type N TC 0 0 0 000mV 1200 0 43 846mV Type T TC 0 0 0 000mV 390 0 20 255mV Type R TC 0 0 0 000mV 1700 0 20 222mV Type S TC 0 0 0 000mV 1700 0 17 947mV Type E TC 0 0 0 000mV 950 0 72 603mV...

Страница 22: ...its power up conditions e g equivalent to a power on reset This might be useful if you ever encounter erratic operation Return to Out of Box Condition You can use this button to restore the transmitte...

Страница 23: ...configuration No error encountered while sending configuration Getting configuration this takes several seconds Error encountered while reading configuration No error encountered while reading config...

Страница 24: ...enclosures to transmit continuous ambient temperature data via the 4 20mA output Recalibration of any model will require use of an ST13C SIP configuration kit ordered separately see Accessories Models...

Страница 25: ...80 C 0 5 C 1 2 C Input Gain PGA gain is internally adjustable for 1 2 4 8 16 32 64 128 256 and 512 mV mV Note Cold Junction Compensation may be switched off to permit the direct connection of an mV so...

Страница 26: ...C 0 000mV 55661 32768 T 390 C 20 255mV 0 C 0 000mV 50464 32768 R 1700 C 20 222mV 0 C 0 000mV 50432 32768 S 1700 C 17 947mV 0 C 0 000mV 48446 32768 E 950 C 72 603mV 0 C 0 000mV 48626 32768 B 1700 C 12...

Страница 27: ...output span effect per volt DC change USB Interface Includes a USB socket for temporary connection to a PC or laptop for the purpose of setup and reconfiguration During reconfiguration and calibration...

Страница 28: ...The unit can be optionally mounted to 35x15mm T type DIN rails using optional ST130 DIN DIN rail mounting adapter kit Refer to the Mounting Dimensions section for more details Shipping Weight 0 5 pou...

Страница 29: ...ting per IEC 1010 1 1990 Operating Shock Vibration Immunity Sinusoidal Vibration 5G 5 500 Hz in 3 axis at 2 hours axis per IEC60068 2 6 Random Vibration 5G rms 5 500 Hz in 3 axis at 2 hours axis per I...

Страница 30: ...s manual for detailed information on available software control of this model Software Interface Package Configuration Kit Order ST130 SIP USB Signal Isolator USB A B Cable 4001 112 USB A mini B Cable...

Страница 31: ...your PC and the USB isolator It is normally included with the ST13C SIP Software Interface Package and also with the isolator model USB ISOLATOR USB A mini B Cable Order 4001 113 USB A mini B Cable 4...

Страница 32: ...g com https www acromag com 32 Revision History The following table shows the revision history for this document Release Date Version EGR DOC Description of Revision 03 DEC 13 J FJM ARP Change the Def...

Отзывы: