Application
This carrier allows a single Bluetooth-enabled microBlox® input module to be
plugged into its housing as shown at left and mounted on a T-type DIN rail. Carriers
can mount side-by-side on 22.5mm centers and can also plug-together for modular
expansion with a shared input power connection along the DIN rail. These alarm
carriers support ten of eleven available uBxx-B input model types with Bluetooth
wireless technology (it does not support the uB45-B frequency model for alarm
functionality, but will accept the uB45 for transmitter operation). The carrier
provides isolated host power to the module, and separate isolated relay contacts
(dual FORM C mechanical or dual FORM A solid-state relay contacts). The carrier
also provides a wired interface for
the module’s
0-5V output and adds a tandem 0-
20mA current output. Independent High/Low alarm levels or a window alarm may
be configured for each relay. Alarm levels are configured in the captive Bluetooth
wireless technology module via a smartphone or tablet and our free mobile app.
Note:
For alarm operation, the plugged-in Bluetooth wireless technology input
module must be configured for the alarm carrier with 0-5V output, and have any
input sub-range scaled to 0-5V output. However, for transmitter-only operation, it
will additionally support any uB input model that has 0-5V output, and will provide
isolated power to the module, and drive separate transmitter outputs of 0-5V/5mA,
or 0-20mA/0-
550Ω.
Mechanical Dimensions
Units may be mounted to 35mm “T” type DIN rail (35mm, type EN50022), and side
-by-
side on 22.5mm (0.9-inch) centers.
WARNING:
IEC Safety Standards may require that this device be mounted within an
approved metal enclosure or sub-system, particularly for applications with exposure to
voltages greater than or equal to 75VDC or 50VAC.