Acromag IntelliPack 811T Series Скачать руководство пользователя страница 7

IntelliPack Series 811T Transmitter/Alarm User's Manual                                                   DC Voltage/Current Input 
__________________________________________________________________________________________ 

 - 7 - 

 

Transmitter/Alarm General Field Programming Procedure 

 

The following procedure uses the corresponding zero/full-

scale (labeled “Z/FS”) and relay (labeled “RLY”) LED’s to indicate 
which parameter is being programmed.  A constant ON zero/full-
scale LED refers to zero configuration (scaling input for 0% 
output), a flashing ON/OFF zero/full-scale LED refers to full-
scale/span configuration (scaling input for 100% output).  A 
constant ON relay LED indicates setpoint adjustment, a flashing 
ON/OFF relay LED indicates dropout/deadband adjustment.  
Refer to Table 4. 

 

CAUTION:

  Do not insert sharp or oversized objects into the 

switch openings as this may damage the unit.  When depressing 
the push-buttons, use a blunt tipped object and apply pressure 
gradually until you feel or hear the tactile response. 

 

1.     Connect a voltage or current source to the input, as required 

(refer to Electrical Connections Drawing 4501-640). 

2.     Apply power and the module’s green “Run” LED will light. 
3.     Press and hold the 

“MODE”

 push button until the green 

“Run” LED turns OFF and the yellow “Zero/Full-Scale” LED 
turns ON.  In this mode, the unit is ready to accept a zero 
input for the transmitter (scaling input for 0% output).  If you 
do not wish to change the zero parameter, skip to step 7. 

4.     Adjust the input source to the zero level according to your 

input range (value must be within input range selected). 

5.     Press the

 

“UP”

 or

 

“DOWN”

 push-button one time to cause 

the module to auto-adjust its output level to the 
corresponding output zero according to the output range 
selected.  If the output is not exactly at the zero level, then 
each successive depression of the “UP” or “DOWN” switch 
will increment or decrement the output signal by a small 
amount.  Holding the switch depressed will increase the 
amount of increment or decrement. 

6.     Press the 

“SET”

 push-button to accept the zero value.  

Note that every time the “SET” button is pressed, the yellow 
“Status” LED will flash once and the zero output will be 
captured. 

7.     Press the

 

“MODE”

 push button one 

time.  The “Zero/Full-

Scale” LED will flash on/off, indicating that the unit is ready 
to accept the full-scale value for setting the span (scaling 
input for 100% output).  If you do not wish to change the full-
scale parameter, skip to step 11. 

8.     Adjust the input source to the full-scale level according to 

your input range (the value must be within the input range 
selected).  The module uses the zero and full-scale levels to 
set the span (span = full-scale - zero). 

9.     Press the

 

“UP”

 or

 

“DOWN”

 push-button one time to cause 

the module to auto-adjust its output level to the 
corresponding full-scale output for the output range 
selected.  If the output is not exactly at the full-scale level, 
t

hen each successive depression of the “UP” or “DOWN” 

switch will increment or decrement the output signal by a 
small amount.  Holding the switch depressed will increase 
the amount of increment or decrement. 

10.   Press the 

“SET”

 push-button to accept the full-scale value.  

Note that every time the “SET” button is pressed, the yellow 
“Status” LED will flash once and the full-scale output will be 
captured. 

11.   If you are configuring a model 811T-0500 which has no 

alarm, then skip steps 12-17 and jump ahead to step 18.

 

 

Transmitter/Alarm Field Programming Procedure…continued 

 
12.   Press the 

“MODE”

 push button one time until the yellow 

zero/full-scale LED goes out and the yellow relay LED turns 
ON (see Table 4).  In this mode, the unit is ready to accept 
an input setpoint level for the alarm.  If you do not wish to 
change the setpoint, skip to step 15. 

13.   Adjust the input source to the High or Low alarm setpoint 

level. 

14.   Press the

 

“SET”

 push button to accept the setpoint.  Note 

that every time the “SET” button is pressed, the yellow 
status LED will flash once and the value at the input will be 
captured. 

15.   Press the

 

“MODE”

 push button one time and the yellow 

relay LED should start flashing (see Table 4).  This means 
that the unit is ready to accept the dropout level for the 
alarm relay.  If you do not wish to change the dropout, skip 
to step 18. 

16.   Adjust the input source to the desired dropout level.  
17.   Press the

 

“SET”

 push button to accept the input dropout 

level.  Note that every time the “SET” button is pressed, the 
yellow status LED will flash once and the value at the input 
will be captured.  The module will use the difference 
between the setpoint and dropout values to calculate relative 
deadband. 

18.   Press the

 

“MODE”

 push button one time to complete the 

program sequence and return to run mode.  The green 
“RUN” LED will turn ON, the yellow “Zero/Full-Scale” LED 
will be OFF, and the yellow alarm LED will be ON or OFF 
according to the alarm status.  The module will now assume 
a transfer function based on the zero and full-scale values 
just set.  The setpoint and dropout of 811T-1500 units is 
used to determine the alarm deadband.  Note that until 
“SET” is pressed, pushing “MODE” will only toggle between 
the zero & full-scale, plus setpoint & dropout adjustment 
modes (811T-1500 units), without affecting their values.  
Further, if no push-buttons are depressed for a period 
greater than 2 minutes, then the module will automatically 
revert to run mode (green “Run” LED will light) and no 
changes will be made to the original zero or full-scale, and 
optional setpoint or dropout settings. 

 

Notes (Field Program Procedure): 

 
1.   In field configuration mode, the yellow zero/full-scale LED 

(Z/FS) and relay LED (RLY) are used to indicate which 
program parameter is being adjusted as illustrated in Table 4: 

 
Table 4:  Field Configuration LED Program Indication 

LED INDICATOR 

Constant ON 

FLASHING 

Yellow Zero/ Full-Scale 

(labeled “Z/FS”) 

 

Zero 

 

Full-Scale 

811T-1500:  

Yellow 

Relay (labeled “RLY”), 

High or Low 

Setpoint 

High or Low 

Dropout 

 
2.   To summarize, the green “Run” LED is turned off in field 

configuration mode.  The yellow zero/full-scale LED is ON or 
FLASHING when the corresponding zero or full-scale value is 
being set in field configuration mode and turned OFF in run 
mode.  The yellow alarm LED is ON or FLASHING when the 
corresponding setpoint or dropout/deadband level is being set 
in field configuration mode. 

Содержание IntelliPack 811T Series

Страница 1: ...rms Process Current Voltage Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA Da...

Страница 2: ...factory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter mod...

Страница 3: ...applications Custom IntelliPack module configurations are also possible please consult the factory Key IntelliPack 811T Features Agency Approvals cULus Listed Easy Windows Configuration Fully reconfig...

Страница 4: ...transparent to the user It receives its power from the IntelliPack module The adapter has a DB9S connector that mates to the common DB9P serial port connector of a host computer The adapter also has a...

Страница 5: ...r NT Configuration Program and Serial Port Adapter Configuration is normally done prior to field installation since field configurability via the module s push buttons is generally limited to zero ful...

Страница 6: ...wing the instrument s deadband and may produce contact chatter The long term effect of this will reduce the life of mechanical relays To reduce this undesired effect you should increase the effective...

Страница 7: ...rease the amount of increment or decrement 10 Press the SET push button to accept the full scale value Note that every time the SET button is pressed the yellow Status LED will flash once and the full...

Страница 8: ...ks and calibrates the performance of each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE...

Страница 9: ...itation current of process current inputs Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Noise Rejection Normal Mode 40dB 60Hz typical wit...

Страница 10: ...rail mountable for flexible high density approximately 1 wide per unit mounting See Enclosure Dimensions Drawing 4501 642 for details Dimensions Width 1 05 inches Height 4 68 inches Depth 4 35 inches...

Страница 11: ...Relay Yellow Constant ON indicates alarm condition for relay During field configuration this LED has a different function see below Field Configuration Mode Run Green Turned OFF in this mode Status Ye...

Страница 12: ...the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To re...

Страница 13: ...L TIPL EXER AND CONDITIONING INPUT SIGNAL 1 6 BIT A D SHL D SHIEL D ISOL ATION RTN INPUT I 2 3 2 4 2 5 V 2 2 MODEL 811T 1500 UNIT ONLY REL AY REL AY ISOL ATION 4 5 COM N O RELAY 4 6 SHL D NC 4 3 4 4 N...

Страница 14: ...ation S oftware or Module P ush B uttons LIMIT A LA RM Transfer Functions Linear P roportional S quare Root Linearizer ON OFF A larm On Off K 1 A nalog OUTP UT type ALARM OUTPUT BLOCK A larm Configura...

Страница 15: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 15...

Страница 16: ...TB2 2 2 V 2 3 I 2 4 RTN I NPUT SHLD 2 5 2 6 EARTH G RO UND TB2 M O D E M O DE SW I TCH Z F S ZERO FUL L SCAL E L ED YEL L O W Acr om ag R U N RUN PW R L ED G REEN STATUS L ED YEL L O W R L Y S T REL...

Страница 17: ...GROUND L OOP TO GROUND AS THIS WOUL D PRODUCE INPUTS GROUND ONL Y ONE INPUT DO NOT CONNECT THE SECOND INPUT P A S S I NG T H ROUGH C E N T E R H OLE S E E I NP U T RA NGE S E LE C T I ON T A B LE A C...

Страница 18: ...TACT 42 34 SPDT CONTACTS PROTECTION AC RELAY POWER DIODE DC RELAY POWER PROTECTION FIGURE A CONTACT SPDT CONTACTS INPUT CONNECTIONS TB1 OUTPUT JUMPER I TO JMP FOR VOLTAGE OUT POWER 8XXT 1500 RELAY OUT...

Страница 19: ...____________________________________ 19 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R A...

Страница 20: ...__________________________________________ 20 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 K CAP...

Страница 21: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 21 Notes...

Отзывы: