Acromag IntelliPack 811T Series Скачать руководство пользователя страница 4

IntelliPack Series 811T Transmitter/Alarm User's Manual                                                   DC Voltage/Current Input 
__________________________________________________________________________________________ 

 - 4 - 

 
Alarm Relay Model Only (811T-1500) 

 

Powerful Alarm Functionality

 - May be programmed for 

limit alarms with deadband, latching/non-latching contacts, 
and failsafe/non-failsafe operation.

 

 

High-Power SPDT Relay Contacts -

 Includes a Single-

Pole-Double-Throw (SPDT) electro-mechanical alarm relay 
for switching up to 230VAC and 5A. 

 

Failsafe or Non-Failsafe Relay Operation

 - May be 

configured for failsafe or non-failsafe relay operation. Upon 
power up, relay may cycle states during diagnostic 
operation. 

 

Configurable Setpoint With Deadband

 - Deadband helps 

to eliminate relay “chatter” and prolong contact life. 

 

Programmable Latching or Momentary Alarms

 - May be 

configured for automatic alarm reset, or a latching alarm 
with manual push-button or software reset. 

 

Programmable Relay Time Delay Filters Transients

 - 

Useful for increased noise immunity and to filter transients. 

 
 

ACCESSORY ITEMS 

 

The following IntelliPack accessories are available from 

Acromag.  Acromag also offers other standard and custom 
transmitter and alarm types to serve a wide range of applications 
(please consult the factory). 

 
IntelliPack Configuration Software (Model 5030-881) 

 
IntelliPack alarms and transmitters are configured with this 

user-friendly Windows 95

 or NT

 

Configuration Program.  This 

software package includes the IntelliPack Alarm Configuration 
Manual (8500-563) and IntelliPack Transmitter Configuration 
Manual (8500-570).  These manuals describe software operation 
and various alarm and transmitter functions in detail.  The 
Configuration Software also includes an on-line help function.  
All transmitter and alarm functions are programmable and 
downloadable to the modules via this software.  Non-volatile 
memory provides program, configuration, and data storage within 
the IntelliPack.

 

 
IntelliPack Serial Port Adapter (Model 5030-913) 
 

This adapter serves as an isolated interface converter 

between the EIA232 serial port of the host computer and the 
Serial Peripheral Interface (SPI) port of the IntelliPack module.  It 
is used in conjunction with the Acromag IntelliPack Configuration 
Software to program and configure the modules.  This adapter 
requires no user adjustment, no external power, and operates 
transparent to the user.  It receives its power from the IntelliPack 
module.  The adapter has a DB9S connector that mates to the 
common DB9P serial port connector of a host computer.  The 
adapter also has a 6-wire

 

RJ11 phone jack to connect to the 

IntelliPack alarm module via a separate interconnecting cable 
(described below).  Refer to Drawing 4501-635 for computer to 
IntelliPack connection details. 

 
IntelliPack Cable (Model 5030-902) 
 

This 6-wire cable is used to connect the SPI port of the 

IntelliPack Serial Port Adapter to the IntelliPack.  This cable 
carries the SPI data and clock signals, reset signal, and +5V 
power and ground signals.  The cable is 7 feet long and has a 6-
wire RJ11 plug at both ends which snap into jacks on the Serial 
Port Adapter and the IntelliPack module. 

 
IntelliPack Software Interface Package (Model 800C-SIP) 
 

The IntelliPack Software Interface Package combines the 

Configuration Software (5030-881), Alarm Configuration Manual 
(8500-563), Transmitter Configuration Manual (8500-570), Serial 
Port Adapter (5030-913), and Cable (5030-902), into a complete 
kit for interfacing with IntelliPack Alarms and Transmitters. 

 

AC Current Sensor (Model 5020-350) 

 
This optional sensor is an accurate toroidal instrument 

transformer used to convert a sinusoidal 50-60Hz AC current 
signal into a low level DC milliampere signal of 0 to 11.17mA.  
The input AC current range is a simple function of the number of 
turns placed through the toroid as shown in Table 2.  This sensor 
is isolated and requires no calibration or adjustment.  A sensor 
used with the IntelliPack provides redundant input isolation. 

 

Table 2:  AC Current Sensor Turns & Range

 

AC Current 

Input Range 

Primary 

Turns 

Sensor Output 

(Red/Black Wires) 

0 to 20A AC 

0 to 11.17mA DC 

0 to 10A AC 

“ 

0 to 5A AC 

“ 

0 to 2A AC 

10 

“ 

0 to 1A AC 

20 

“ 

 

The output wires of this sensor are polarized:  Red is (+) plus 

and Black is (-) minus.  Normally these output wires are attached 
to one end of a user supplied cable, and the other end of the 
cable connects to the IntelliPack Transmitter’s process current 
input terminals. 

 

Input Burden

:  Is a function of the wire gauge resistance 

used for the primary turns (the current carrying wire being 
monitored). 

Input Overload

:  The AC current sensor will withstand 

overload conditions as follows: 

 

20 times full scale for 0.01 seconds. 

 

10 times full scale for 0.1 seconds. 

 

5 times full scale for 1.0 second. 

AC Current Sensor to Transmitter Wiring Distance

:  400 

feet maximum for 18 gauge wire.  Other wire gauges can be 
used as long as the resistance of both wires is less than 5

 

Содержание IntelliPack 811T Series

Страница 1: ...rms Process Current Voltage Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA Da...

Страница 2: ...factory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter mod...

Страница 3: ...applications Custom IntelliPack module configurations are also possible please consult the factory Key IntelliPack 811T Features Agency Approvals cULus Listed Easy Windows Configuration Fully reconfig...

Страница 4: ...transparent to the user It receives its power from the IntelliPack module The adapter has a DB9S connector that mates to the common DB9P serial port connector of a host computer The adapter also has a...

Страница 5: ...r NT Configuration Program and Serial Port Adapter Configuration is normally done prior to field installation since field configurability via the module s push buttons is generally limited to zero ful...

Страница 6: ...wing the instrument s deadband and may produce contact chatter The long term effect of this will reduce the life of mechanical relays To reduce this undesired effect you should increase the effective...

Страница 7: ...rease the amount of increment or decrement 10 Press the SET push button to accept the full scale value Note that every time the SET button is pressed the yellow Status LED will flash once and the full...

Страница 8: ...ks and calibrates the performance of each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE...

Страница 9: ...itation current of process current inputs Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Noise Rejection Normal Mode 40dB 60Hz typical wit...

Страница 10: ...rail mountable for flexible high density approximately 1 wide per unit mounting See Enclosure Dimensions Drawing 4501 642 for details Dimensions Width 1 05 inches Height 4 68 inches Depth 4 35 inches...

Страница 11: ...Relay Yellow Constant ON indicates alarm condition for relay During field configuration this LED has a different function see below Field Configuration Mode Run Green Turned OFF in this mode Status Ye...

Страница 12: ...the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To re...

Страница 13: ...L TIPL EXER AND CONDITIONING INPUT SIGNAL 1 6 BIT A D SHL D SHIEL D ISOL ATION RTN INPUT I 2 3 2 4 2 5 V 2 2 MODEL 811T 1500 UNIT ONLY REL AY REL AY ISOL ATION 4 5 COM N O RELAY 4 6 SHL D NC 4 3 4 4 N...

Страница 14: ...ation S oftware or Module P ush B uttons LIMIT A LA RM Transfer Functions Linear P roportional S quare Root Linearizer ON OFF A larm On Off K 1 A nalog OUTP UT type ALARM OUTPUT BLOCK A larm Configura...

Страница 15: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 15...

Страница 16: ...TB2 2 2 V 2 3 I 2 4 RTN I NPUT SHLD 2 5 2 6 EARTH G RO UND TB2 M O D E M O DE SW I TCH Z F S ZERO FUL L SCAL E L ED YEL L O W Acr om ag R U N RUN PW R L ED G REEN STATUS L ED YEL L O W R L Y S T REL...

Страница 17: ...GROUND L OOP TO GROUND AS THIS WOUL D PRODUCE INPUTS GROUND ONL Y ONE INPUT DO NOT CONNECT THE SECOND INPUT P A S S I NG T H ROUGH C E N T E R H OLE S E E I NP U T RA NGE S E LE C T I ON T A B LE A C...

Страница 18: ...TACT 42 34 SPDT CONTACTS PROTECTION AC RELAY POWER DIODE DC RELAY POWER PROTECTION FIGURE A CONTACT SPDT CONTACTS INPUT CONNECTIONS TB1 OUTPUT JUMPER I TO JMP FOR VOLTAGE OUT POWER 8XXT 1500 RELAY OUT...

Страница 19: ...____________________________________ 19 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R A...

Страница 20: ...__________________________________________ 20 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 K CAP...

Страница 21: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 21 Notes...

Отзывы: