Acromag IntelliPack 811T Series Скачать руководство пользователя страница 12

IntelliPack Series 811T Transmitter/Alarm User's Manual                                                   DC Voltage/Current Input 
__________________________________________________________________________________________ 

 - 12 - 

be scaled to 0% and 100% at the transmitter analog output.  
The scaling may also be adjusted in-field via front panel 
push-

buttons and status LED’s. 

Transmitter - Computation:

  The following gives a brief 

description of current available transmitter computation 
functions: 

 

None (Default):

  Each input sample is converted into a 

directly proportional output update. 

 

Square Root:  

Each input sample is converted into a 

corresponding output update that is the square root of 
the input signal.  The output in percent is computed as 
the square root of the product of the input in percent 
multiplied by 100%. 

 

Linearizer:

  Permits the entry of up to 25 user-defined 

input-to-output break points to facilitate up to 24 
segment linearization of a non-linear sensor signal. 

 

Alarm Configuration (Model 811T-1500) 

Model 811T-1500 units 

may also be configured for simple limit alarms.  You may also 
refer to the IntelliPack 800A alarm family for dedicated alarm 
modules that support other operating functions. 

 

Alarm - Input:

  The input signal range to the alarm is the full 

range for the configured input type.  Example: if 4-20mA input 
was selected using the configuration program, the alarm can 
be programmed to any setpoint from 0 to 20mA.  If input 
averaging is used, an averaged input value will be used by 
the alarm.  

Alarm - Mode:  

Select a High or Low limit for the limit alarm 

function of this model.  The relay will trip on an increasing 
input signal for a high limit, and on a decreasing input signal 
for a low limit. 

Alarm - Setpoint:

  A high or low setpoint (plus deadband) may 

be assigned to the relay and is programmable over the entire 
input range.  The relay will enter the alarm state when either 
the user-defined high or low setpoint is exceeded for the 
specified amount of time (this allows input transients to be 
filtered).  Relay remains in the alarm state until the input 
signal has retreated past the defined setpoint, plus any 
deadband, for the specified amount of time.  Please refer to 
the IntelliPack alarm family for dedicated alarm modules that 
support other operating functions. 

Alarm - Deadband: 

 Deadband is associated with the setpoin t. 

Deadband settings for bipolar input ranges should be limited 
to 50% or less of the range selected. Unipolar input ranges 
support deadband settings up to 100% of the range selected. 
Deadband determines the amount the input signal has to 
return into the “normal” operating range before the relay 
contacts will transfer out of the “alarm” state.  Deadband is 
normally used to eliminate false trips or alarm “chatter” 
caused by fluctuations in the input near the alarm point.  Note 
that deadband may also apply to latched alarms.  If the alarm 
is latching, it is recommended that the deadband be set to a 
minimum. 

 

 

IMPORTANT:

  Noise and/or jitter on the input signal has 

the effect of reducing (nar

rowing) the instrument’s 

deadband and may produce contact chatter.  Another 
long term effect of contact chatter is a reduction in the 
life of the mechanical relay contacts.  To reduce this 
undesired effect, increase the deadband setting. 

 

Relay - Time Delay:

 Programmable from 0 milliseconds to 25.5  

seconds in 100ms increments for this model (used to help 

filter input transients and avoid nuisance alarming).  A 
minimum delay of 100ms is recommended for increased 
noise immunity & conformance to applicable safety 
standards.  This delay does not apply to control of the 
transmitter’s analog output. 

Relay - Operating Mode:

  

User configurable for “failsafe” 

operation (relay deenergized in alarm state), or non-failsafe 
operation (relay energized in alarm state).  Failsafe mode 
provides the same contact closure for alarm states as for 
power loss, while non-failsafe mode uses alarm contact 
closure opposite to power loss conditions. Upon power up, 
relay may cycle states during diagnostic operation. 

Relay - Reset:

  The relay may be configured to automatically 

reset when the input retreats past its setpoint and deadband, 
or the relay may latch into its alarm state.  Use the up or 
down push-buttons on the front of the module to reset a 
latched relay and exit the latched state (this may also be 
accomplished under software control). 

Visual Alarm Indicator:

  

A yellow LED (labeled “RLY”) for the 

relay provides visual status indication of when the relay is in 
alarm (LED is ON in alarm).  This LED is also used in field 
configuration mode to indicate whether setpoint or deadband 
is being adjusted. 

 
Other IntelliPack Configuration Software Capabilities 

In addition to configuring all features of the module described 
above, the IntelliPack Configuration Software includes additional 
capabilities for testing and control of the module (see below).  For 
complete information on the IntelliPack Configuration Software, 
refer to Transmitter Configuration Manual 8500-570.: 
 

 

Monitors the input and output signal values and allows 
polling to be turned on or off. 

 

Provides a “Show Graph” function to view a graphical 
representation of input signal (x) versus output signal (y). 

 

Allows a configuration to be uploaded or downloaded to/from 
the module.  Also provides a means to rewrite a module’s 
firmware 

if the microcontroller is replaced or a module’s 

functionality is updated. 

 

Provides controls to separately calibrate the input and output 
stages and restore the original factory input or output 
calibration in case of error. 

 

Provides separate controls to reset a module and reset a 
latched alarm relay. 

 

Provides a control to adjust a transmitter’s output signal 
independent of the input signal (timed override). 

 

Allows optional user documentation information to be written 
to the module.  Documentation fields are provided for tag 
number, comment, configured by, location, and identification 
information.  This information can also be uploaded from the 
module and printed via this software. 

 

Allows a module’s complete configuration to be printed in an 
easy to read, two-page form, including user documentation. 

 

Includes on-line help and context (field) sensitive help 
functions. 

Содержание IntelliPack 811T Series

Страница 1: ...rms Process Current Voltage Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA Da...

Страница 2: ...factory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter mod...

Страница 3: ...applications Custom IntelliPack module configurations are also possible please consult the factory Key IntelliPack 811T Features Agency Approvals cULus Listed Easy Windows Configuration Fully reconfig...

Страница 4: ...transparent to the user It receives its power from the IntelliPack module The adapter has a DB9S connector that mates to the common DB9P serial port connector of a host computer The adapter also has a...

Страница 5: ...r NT Configuration Program and Serial Port Adapter Configuration is normally done prior to field installation since field configurability via the module s push buttons is generally limited to zero ful...

Страница 6: ...wing the instrument s deadband and may produce contact chatter The long term effect of this will reduce the life of mechanical relays To reduce this undesired effect you should increase the effective...

Страница 7: ...rease the amount of increment or decrement 10 Press the SET push button to accept the full scale value Note that every time the SET button is pressed the yellow Status LED will flash once and the full...

Страница 8: ...ks and calibrates the performance of each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE...

Страница 9: ...itation current of process current inputs Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Noise Rejection Normal Mode 40dB 60Hz typical wit...

Страница 10: ...rail mountable for flexible high density approximately 1 wide per unit mounting See Enclosure Dimensions Drawing 4501 642 for details Dimensions Width 1 05 inches Height 4 68 inches Depth 4 35 inches...

Страница 11: ...Relay Yellow Constant ON indicates alarm condition for relay During field configuration this LED has a different function see below Field Configuration Mode Run Green Turned OFF in this mode Status Ye...

Страница 12: ...the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To re...

Страница 13: ...L TIPL EXER AND CONDITIONING INPUT SIGNAL 1 6 BIT A D SHL D SHIEL D ISOL ATION RTN INPUT I 2 3 2 4 2 5 V 2 2 MODEL 811T 1500 UNIT ONLY REL AY REL AY ISOL ATION 4 5 COM N O RELAY 4 6 SHL D NC 4 3 4 4 N...

Страница 14: ...ation S oftware or Module P ush B uttons LIMIT A LA RM Transfer Functions Linear P roportional S quare Root Linearizer ON OFF A larm On Off K 1 A nalog OUTP UT type ALARM OUTPUT BLOCK A larm Configura...

Страница 15: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 15...

Страница 16: ...TB2 2 2 V 2 3 I 2 4 RTN I NPUT SHLD 2 5 2 6 EARTH G RO UND TB2 M O D E M O DE SW I TCH Z F S ZERO FUL L SCAL E L ED YEL L O W Acr om ag R U N RUN PW R L ED G REEN STATUS L ED YEL L O W R L Y S T REL...

Страница 17: ...GROUND L OOP TO GROUND AS THIS WOUL D PRODUCE INPUTS GROUND ONL Y ONE INPUT DO NOT CONNECT THE SECOND INPUT P A S S I NG T H ROUGH C E N T E R H OLE S E E I NP U T RA NGE S E LE C T I ON T A B LE A C...

Страница 18: ...TACT 42 34 SPDT CONTACTS PROTECTION AC RELAY POWER DIODE DC RELAY POWER PROTECTION FIGURE A CONTACT SPDT CONTACTS INPUT CONNECTIONS TB1 OUTPUT JUMPER I TO JMP FOR VOLTAGE OUT POWER 8XXT 1500 RELAY OUT...

Страница 19: ...____________________________________ 19 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R A...

Страница 20: ...__________________________________________ 20 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 K CAP...

Страница 21: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 21 Notes...

Отзывы: