Model DT23x-0600
Dual Two-Wire DC I/V Input Transmitters
Acromag, Inc. Tel: 248-295-0880
- 24 -
http://www.acromag.com
- 24 -
https://www.acromag.com
Diagnostics
At this point, following Configuration or Calibration, you
could choose the “Diagnostics” tab to display the
Diagnostics page shown at left. From this page, you can
test the transmitter
’s
operation by polling the input
channels.
Click
[Start Polling]
to trigger the software to
periodically read the input channels and display their
values in the fields below the polling button. Note the
simulated lamp next to the polling button flashes slowly
each time it samples the inputs. Click
[Stop Polling]
to
stop polling the inputs before moving onto another
tab/page.
See the second screen at left which is after starting
polling. Note the input values are indicated in range
units (mA for channel
input A of DT236 models) and “No
error” is displayed in the Communication status field.
Note that this page polls the input ADC readings of the
unit’s input channels, which does not include output
DAC error.