Acromag 655T Series Скачать руководство пользователя страница 5

Series 655T/656T Transmitter User's Manual                                                                                          mV/TC Input 
___________________________________________________________________________________________ 
 

 - 5 - 

 

Table 3A:  Input Range/Type Selection - DIP Switch Settings 

INPUT RANGE 

S1 

S2 

S3 

S4 

S5,6,7

2

 

J TC 

NA 

K TC 

NA 

T TC 

NA 

R TC 

NA 

S TC 

NA 

E TC 

NA 

B TC 

NA 

N TC 

NA 

0-1.0V

3

 

NA 

0-500mV

3

 

NA 

0-250mV

3

 

NA 

0-125mV

3

 

NA 

62.5mV 

NA 

31.3mV 

NA 

15.6mV 

NA 

Reserved 

NA 

 

Notes (Table 3A): 

1.   NA = No Application; Don’t Care; 0 = Switch Open/OFF; 

1 = Switch Closed/ON. 

2.   Note that switches SW5, SW6, SW7 have no function and 

are reserved for future use. 

3.   The unit will permit calibration below 0V, down to -65mV 

typical, for these ranges. 

4.   The economy Model 656T-E600 only provides support for the 

three ranges indicated in 

BOLD

 (J, K, 0-125mV). 

 
Table 3B:  Miscellaneous Options - DIP Switch Settings 

MISCELLANEOUS 
OPTIONS 

SW

SW

SW

10 

SW

11 

SW 

12 

Break Detection ON 

 

 

 

 

Break Detection OFF 

 

 

 

 

TC Break Downscale 

 

 

 

 

TC Break Upscale 

 

 

 

 

CJC OFF 

 

 

 

 

CJC ON 

 

 

 

 

Linearization

3

 OFF 

 

 

 

 

Linearization

3

 ON 

 

 

 

 

Configuration Lock OFF 

 

 

 

 

Configuration Lock ON 

 

 

 

 

 
Notes (Table 3B): 

1.    0 = Switch Open/OFF; 1 = Switch Closed/ON. 
2.   The Default Configuration is all switches OFF (0).  This 

corresponds to the factory default configuration of J TC type, 
TC Break OFF, TC Break Upscale, CJC ON, Linearization 
Enabled, and Reconfiguration Locked Out. 

3.   The economy Model 656T-E600 does not support TC 

linearization (set via SW11) and this setting will be ignored. 

 

These units were packaged with one or more plastic covers for 
installation over the DIP switch openings.  Do not install the DIP 
switch cover(s) until you have completed the zero and span 
configuration procedure outlined in the following section.  This is 
done to maintain access to the Configuration Lock switch 
(SW12), which should be locked following zero and span 
reconfiguration to help prevent inadvertent miscalibration or 
tampering in the field. 

 

ZERO AND SPAN CONFIGURATION 

 
IMPORTANT:

  You must set your DIP switches according to your 

application prior to configuring the zero and full-scale input points 
as described below (see above). 
 

UNLOCK RECONFIGURATION:

  Reconfiguration of zero and 

full-scale is locked out by default and must be unlocked before 
making adjustments to zero and full-scale--DIP switch 12 must be 
set ON to unlock the front-panel Z/FS toggle switches. 
 

After setting the DIP switches as required for your 

application, you may optionally re-scale your input range to the 
output 4mA and 20mA endpoints as described here.  
Configuration of the zero & full-scale I/O points (essentially input 
to output scaling) i

s accomplished via the transmitter module’s 

“Z” and “FS” Up/Down toggle switches located on the front panel 
(see Drawing 4501-779). 
 

Equipment Required 

 

An accurate input source adjustable over the range desired 

for zero and full-scale is required.  A thermocouple calibrator may 
also be used.  An accurate current or voltage meter is also 
required to monitor the output level.  For best results, the input 
source and output meter must be accurate beyond the required 
specifications.  For voltage inputs, use a voltage source with an 
output impedance of 100

 or less. 

 
In the absence of a thermocouple calibrator, a convenient 

method of configuring the TC input would be to use a precision 
mV source with the module’s CJC set to OFF.  Using this method 
allows the mV source to be wired directly to the input terminals 
using copper wires.  The module’s cold junction compensation is 
turned off and the mV values applied to the input are the 
equivalent thermoelectric voltages that correspond to the 
minimum and maximum temperatures of your desired input range 
and are specific to each TC type.  Refer to Table 4 of the 
following page for a list of thermocouple voltages at specific 
temperatures.  After setting zero and full-scale in this manner, the 
CJC switch should be returned to the ON position to enable cold 
junction compensation. 
 

Transmitter Zero/Full-Scale Configuration Procedure 

 

CAUTION:

  Input levels outside of the nominal range of the 

selected input will not be accepted for configuration of zero or full-
scale.  Since input levels cannot be validated during field 
programming, entering incorrect signals may produce an 
undesired output response. 
 

Note: 

 

The transmitter’s input range/type, TC break on/off, TC 

break up/down direction, CJC on/off, linearization, and zero/full-
scale reconfiguration lock/unlock is set via the DIP switches.  
Each input range is already factory calibrated and scaled to the 4 
to 20mA output by default.  However, you may use the front panel 
toggle switches to scale virtually any part of the nominal input 
range to the 4-20mA output range.  For example, use the 0 to 
200

C portion of the type J TC input to drive the 4 to 20mA output 

range--this configuration will be used as an example in the 
following procedure. 

Содержание 655T Series

Страница 1: ...itters mV TC Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 2000 Acromag Inc Printed in the USA Data and specific...

Страница 2: ...tions Output Enclosure Approvals1 Factory Configuration2 655T 06003 C 656T 06003 C 656T E600 C Notes Table 1 1 Approvals cULus Listed Hazardous Locations Class I Division 2 Groups A B C D See specific...

Страница 3: ...SE UNPACKING AND INSPECTION Upon receipt of this product inspect the shipping carton for evidence of mishandling during transit If the shipping carton is badly damaged or water stained request that th...

Страница 4: ...nsmitter accuracy Ripple Noise Power supply ripple at 60Hz 120Hz is normally reduced at the load by the transmitter The ripple at the load will generally be less than 0 02 of span per volt peak to pea...

Страница 5: ...switch 12 must be set ON to unlock the front panel Z FS toggle switches After setting the DIP switches as required for your application you may optionally re scale your input range to the output 4mA a...

Страница 6: ...of increment or decrement Reverse Acting Outputs A reverse acting output can be easily obtained by using the Up Down toggle to adjust the output level accordingly For a reverse acting output you woul...

Страница 7: ...20 878 18 504 13 008 1800 13 585 5 0 SERVICE AND REPAIR CAUTION Risk of Electric Shock More than one disconnect switch may be required to de energize the equipment before servicing SERVICE AND REPAIR...

Страница 8: ...pecifications Thermocouple User configured for the eight types of thermocouples shown in Table 5 Model 656T E600 units only support J K TC types plus the 0 125mV input range Linearization separately e...

Страница 9: ...igible line drop At a 24V DC supply Rload 0 600 Note For sensitive applications with high speed acquisition rates high frequency noise may be reduced considerably by simply placing a 0 1uF capacitor d...

Страница 10: ...DN direction to lower the full scale output level NOTE Note that the zero and full scale adjustments take effect immediately and are saved to non volatile memory after 15 seconds of toggle switch inac...

Страница 11: ...OOPS AND MEASUREMENT ERROR NOTE 1 SHIELDED CABLE 4 20mA NOTE 1 WARNING TB2 or TB3 Acromag CHAN 1 DC SUPPLY 12 36V DC SOURCE VOLTAGE DC SUPPLY 4 20mA SHIELDED CABLE 12 36V DC INPUT CHAN 2 TB2 or TB3 MO...

Страница 12: ...tionON Lock ON 8 9 10 11 12 ConfigurationUNLOCKED 1 ConfigurationLOCKED LinearizationOFF LinearizationON 0 0 1 0 0 1 0 0 1 0 0 0 1 1 1 1 1 1 1 0 1 1 0 1 1 0 0 0 0 0 0 1 1 0 0 CJC OFF CJC ON TC Break D...

Страница 13: ...___________________________________________________________ 13 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision...

Страница 14: ...Series 655T 656T Transmitter User s Manual mV TC Input ___________________________________________________________________________________________ 14 Notes...

Отзывы: