Acromag 651T Series Скачать руководство пользователя страница 5

Series 651T/652T/653T Isolator User’s Manual                                           Process Current Two-Wire Transmitters 
___________________________________________________________________________________________ 
 

 - 4 - 

 

IMPORTANT:

  Note that input and output circuits are isolated 

from each other allowing the output circuit to operate with 
common-mode voltages up to 250VAC, or 354VDC off 
ground, on a continuous basis.  Channels are also isolated 
from each other. 

 
2.

   Output/Power Connections (Each Output)

:  Connect a DC 

power supply and the load in a two-wire configuration as 
shown in Electrical Connections Drawing 4501-727.  For 
supply connections, use No. 14-24 AWG wire rated for at 
least 90

°

 Celsius.  Loop current is input to the OUT+ lead and 

returned via the OUT- lead.  Optionally, a DVM may be 
placed between the “SNS+” terminal and the “OUT-“ 
terminals to monitor the loop current via the voltage drop 
measured across a built-in, precision 10

Ω

 resistor connected 

in series with the “OUT-“ lead.  These transmitters operate 
from DC supplies only.  Power supply voltage is not critical 
and should be from 12-36V DC.  The supply voltage must not 
exceed 60V, even momentarily, or damage to the unit may 
result.  Further, the power supply voltage must be adequate 
to supply full-scale current to the load(s), plus 12V to the 
transmitter terminals, plus any transmission line drop.  
Variations in power supply voltage or load resistance within 
rated limits has negligible effect on transmitter accuracy. 

 

Ripple & Noise:

  Power supply ripple at 60Hz/120Hz is 

reduced at the load by the transmitter.  The ripple at the load 
will generally be less than 0.02% of span per volt peak-to-
peak of power supply ripple.  The unit may have up to 0.25% 
of additional internally generated ripple.  In this case, connect 
an external 1uF capacitor across the load to reduce this 
ripple to less than 0.1% if desired. 

 
3.

   Grounding:

  See Electrical Connections Drawing 4501-727. 

The module housing is plastic and does not require an earth 
ground connection.  If the isolator is mounted in a metal 
housing, a ground wire connection is typically required.  
Connect the metal enclosure’s ground terminal (green screw) 
to earth ground using suitable wire and per applicable codes. 

 

WARNING:

  For compliance to applicable safety and 

performance standards, the use of twisted pair wiring is 
recommended as shown in Drawing 4501-727.  Failure to 
adhere to sound wiring and grounding practices as 
instructed may compromise safety and performance.

 

 
 

3.0 CALIBRATION 

 

Units are calibrated at the factory and further adjustment is 

not normally required unless the circuit has aged or periodic 
calibration is needed to meet your company’s maintenance 
requirements.  

 

Calibration is performed as an iterative process of zero and 

span adjustment for each output channel.  The zero and span 
adjustment potentiometers are accessible from the front panel of 
the unit.  The screwdriver blade used to adjust the potentiometers 
should not be more than 0.1 inch (2.54mm) wide. 

 

TRANSMITTER ADJUSTMENT PROCEDURE 

 
Equipment Required 

 

 

An accurate input current source adjustable for 4-20mA DC.  
This source should be accurate beyond the 

±

0.1% module 

specification for best results. 

 

An accurate current or voltage meter is also required to 
monitor the output level.  This meter must be accurate 
beyond the module specifications for best results. 

 

A precision load resistance will be needed if you are 
monitoring output voltage to complete calibration. 

 
Adjustment Procedure 

 

Note:  

Zero and Span pots are turned clockwise to increase the 

output signal, and counter-clockwise to reduce the output signal. 

 

1.   Connect the input signal and output power/load as shown in 

Electrical Connections Drawing 4501-727 for the channel of 
interest.  Two power supplies and loads will be required to 
calibrate 653T units. 

2.   Adjust the input signal to precisely 4.000mA DC.  Adjust the 

zero pot until the output reads 4.000mA 

±

0.016mA DC.  

Repeat this procedure for the second zero pot and output of 
653T units. 

3.   Adjust the input signal to precisely 20.000mA DC.  Adjust the 

span pot until the output reads 20.000mA 

±

0.016mA DC. 

Repeat this procedure for the second span pot and output of 
653T units. 

4.   Repeat steps 2 & 3 until the readings converge. 
5.   As a check of calibration, adjust the input to precisely 

12.000mA and verify the output measurement to within 

±

0.1% of span.  Check both outputs of 653T units.  If the 

measured error is greater than 

±

0.1%, then perform steps 2 

and 3 again until rated accuracy is achieved. 

6.   Repeat the above procedure for the second channel of 652T 

units. 

 
 

4.0  THEORY OF OPERATION 

 

Refer to Simplified Schematic 4501-726 to gain a better 

understanding of the circuit.  These isolators use a center-tapped 
transformer to isolate from output to input.  Half of the output loop 
current is routed to a 2:1 transformer (output current:input 
current) while being driven in an alternating push-pull fashion to 
modulate the input current.  The other half of the output current 
drives an output circuit supply and is pulled through a current 
steering circuit that regulates the input current (via the 
transformer) and an adjustment current (zero and span circuit).  
The input circuit utilizes a unique mosfet to limit the input voltage 
drop to low V

GS

 threshold levels.  The input circuit also includes 

overvoltage transient suppression circuitry, noise filtering, and a 
reverse polarity protection diode.  Transient voltage suppressors 
and other filtering devices are also included at the output for 
effective noise filtering and transient suppression.  The output 
“OUT-“ lead includes a precision series-connected 10

Ω

 resistor to 

facilitate the connection of a DVM across the output “SNS” and 
“OUT-“ terminals for monitoring the output loop current without 
breaking the loop. 

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание 651T Series

Страница 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Страница 2: ...65 South Wixom Road P O BOX 437 Wixom MI 48393 7037 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1999 Acromag Inc Printed in the USA Data and specifications are subject to change without notice 8...

Страница 3: ...t Enclosure Approvals1 651T3 0600 652T3 0600 653T3 0600 Notes Table 1 1 Approvals CE marked UL and cUL listed Hazardous Locations Class 1 Division 2 Groups A B C D See specifications 2 The unit is cal...

Страница 4: ...secure the DIN rail to the mounting surface Units may be mounted side by side on 1 inch centers for limited space applications T Rail 35mm Type EN50022 To attach a module to this style of DIN rail ang...

Страница 5: ...cessible from the front panel of the unit The screwdriver blade used to adjust the potentiometers should not be more than 0 1 inch 2 54mm wide TRANSMITTER ADJUSTMENT PROCEDURE Equipment Required An ac...

Страница 6: ...t acts as a signal splitter with one input driving 2 isolated two wire outputs These isolators are DIN rail mounted with plug in type terminal blocks Units are calibrated via zero and span adjustment...

Страница 7: ...ght 1 pound 0 45 Kg packed APPROVALS xxx0 0 CE marked UL listed UL508 17TH Edition and ANSI ISA 12 12 01 2007 cUL listed Canada Standard C22 2 142 M1987 and 213 M1987 Hazardous Locations Class 1 Divis...

Страница 8: ...1 OUT2 INPUT FILTERING SCREW TERMINAL NUMBER OSCILLATOR ISOLATED CHANNEL 2 652T SINGLE ISOLATED INPUT TWO ISOLATED OUTPUTS 653T 4501 726B ISOLATED CHANNEL 1 651T IS ISOLATED FROM INPUT TO OUTPUT 652T...

Страница 9: ...GREATER THAN OR EQUAL TO 75VDC 50VAC OUTPUT LOOP 1 ZERO SPAN ADJUST I O CONNECTIONS SEE I O CONNECTIONS OF FOLLOWING PAGE 4501 727B FIGURE A ELECTRICAL CONNECTIONS IN TB2 OUT TB2 OUT OUT IN TB1 OUT O...

Страница 10: ...NNECTION W OPTIONAL OUTPUT SENSE CONNECTION ISOLATED CHANNEL 1 TYPICAL CALIBRATION CONNECTIONS CONNECTIONS AT CHANNEL 1 MODEL 651T 652T 653T INPUT OUTPUT R XMTR IN DC SUPPLY SHIELDED CABLE OUTPUT CURR...

Страница 11: ..._ 10 Acromag SPAN PWR CHAN 2 3 75 95 3 SPAN ZERO R ZERO CHAN 1 PWR L C T RAIL DIN MOUNTING DIN EN 50022 35mm 59 4 2 34 SCREWDRIVER SLOT FOR REMOVAL FROM T RAIL 3 90 99 1 4 35 110 5 4501 728A NOTE ALL...

Страница 12: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Отзывы: