AIM-T500L Series Industrial Insulation 

Monitoring and Fault Locating Products 

 

Installation and Operation Manual V1.4 

 

 

 

 

 

 

 

 

 

Acrel Co., Ltd. 

 

 

Содержание AIM-T500L Series

Страница 1: ...375 AIM T500L Series Industrial Insulation Monitoring and Fault Locating Products Installation and Operation Manual V1 4 Acrel Co Ltd...

Страница 2: ...ignoring the instructions in this operation manual The equipment is professional electrical equipment any related operation need to be carried out by special electrical technicians Acrel is not respo...

Страница 3: ...AIL200 12 Modified address table and added fault location records 4 2020 08 10 V1 3 Modified the power supply in the wiring diagram Add dc input Modified the wiring of ASG200 Added AIL200 12 operatio...

Страница 4: ...on 4 5 1 Shape and size 4 5 2 Installation method 5 5 3 Wiring method 6 5 4 Typical application 8 5 5 Matters needing attention 8 6 Program and Usage 9 6 1 AIM T500L insulation monitor 9 6 2 ASG200 te...

Страница 5: ...fault in time The products conform to the requirements of enterprise standard Q VDCL 26 2017 IT System Insulation Monitor Type and Name Picture Introduction AIM T500L insulation monitor AIM T500L ins...

Страница 6: ...Indicate the phase line where the fault is Manual startup positioning is supported CAN bus technology is adopted to facilitate data interaction with other devices in the system 2 3 AIL200 12 insulatio...

Страница 7: ...age AC 220V 3AC 0 690V DC 0 800V Fault locating Response time 5s positing voltage 20V 5Hz positing current 0 10mA Response sensitivity Internal parameters EMC Radiation IEC61326 2 4 Output Relay outpu...

Страница 8: ...Electrical equipment for measurement control and laboratory use EMC requirements Part 2 4 Particular requirements Test configurations operational conditions and performance criteria for insulation mon...

Страница 9: ...dimensions mm Hole size mm Installation dimensions mm product weight g W H D M N L 2 L 45 16 100 75 75 22 46 65 65 4 3 4 200 10 L 80 100 250 120 120 23 81 105 105 4 4 4 380 20 L 100 250 400 140 140 2...

Страница 10: ...connect T1 and T2 and the instrument self test results will be displayed F1 and F2 23 24 are interconnection terminals When two sets of ungrounded systems are interconnected the monitor which F1 and...

Страница 11: ...access to L1 L2 For single phase DC systems L1 is connected to the positive pole and L2 is connected to the negative pole PE 14 is the instrument functional earthing terminal and shall be connected t...

Страница 12: ...sleeve joint then insert the corresponding terminals of the instrument and tighten the screws to avoid abnormal operation of the instrument due to poor contact 2 AIM T500L has two communication inter...

Страница 13: ...resistance value is less than the warning value the warning indicator flashes ALARM When the monitored insulation resistance value is less than the alarm value the warning and alarm indicator light f...

Страница 14: ...1 Loop 1 L1 time 15 07 01 11 30 Press enter Press ESC Parameter setting 1 Enter the menu If the system runs normally press Enter to enter the password input page Use the Up and Down keys to change the...

Страница 15: ...Down to set TimeSet press ESC to save or exit Press Up and Down to set AlarmSet press ESC to save or exit Press Up and Down to select the CommSet and press Enter to confirm Press Up and Down to select...

Страница 16: ...ermined L1 L2 and L3 are all on 6 2 3 keys function The Start button of the ASG200 test signal generator is reserved for manual fault location After manual startup the signal generator interacts with...

Страница 17: ...for 01 ZCT loop fault fault state To modify the settings press OK and enter the password to enter the settings The blinking character indicates that you can modify the settings You can change the def...

Страница 18: ...arameters default If multiple fault locators are connected to the system confirm the transformer circuit connected to each fault locator and manually close the unconnected circuit Set the address of e...

Страница 19: ...ters The function code 10H allows the user to change the contents of multiple registers which can write the time and date in this meter The host can write up to 16 32 bytes data at a time The followin...

Страница 20: ...e R W 60 4999 unit k default 60 word 0007H low Warning value 9 0008H high Alarm value R W 10 4999 unit k default 38 word 0008H low Alarm value 10 0009H high Resistance value R 1 10001 unit k word 0009...

Страница 21: ...and the rules and formats are the same as the first 117 120 0074H 0077 H Reserve 121 0078H high Fault Locate Record 1 Number R The sequence number of incident record 0 19 word 0078H low Locator R Loc...

Страница 22: ...ts D03 and D03 control the warning lights The malfunction fault indicates that the meter itself is out of order Lock Check If the N line is not elicited access any 2 phase in the 3 RS485 communication...

Страница 23: ...19 19 8 2 AIM T500L typical application diagram...

Страница 24: ...6 21 69158303 Web site www acrel electric com mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industrial Park N...