background image

6

Return Duct

1. Assemble the collar by overlapping the two ends.  

NOTE: 

One end of the collar is slotted and the opposite end 

has two small holes. Position the end with small screw holes 

underneath the slotted end.

2. Fasten the collar ends with two self drilling sheet metal screws.

3. Position the collar over the opening. Align the four holes in 

the collar with the four dimples or holes (depending on unit 

model) in the panel.

4. Secure the collar to the rear panel using self tapping screws 

(10-16x.5).

Connecting Return & Supply Air Flexible Ducts

•  Flexible ducts may be cut to the required length and spliced 

with sheet metal sleeves and clamps. 

Keep all ducts as short 

and straight as possible. Avoid sharp bends. 

Please follow 

all instructions packed with duct.

•  Flexible ducts can be secured to the corresponding collars 

with the provided clamps. After the inner duct is connected 

to the collar, pull the insulation and plastic sleeve over the 

connection and clamp. 

NOTE:

 To prevent a loss in cooling 

capacity, make sure all connections are tight.

•  Homes with multiple supply ducts (or special applications), a 

Y fitting is available for dividing the supply air to different areas 

of the home for more efficient cooling. 

NOTE:

 For maximum 

performance, insulate the Y fitting.

Locating & Installing the Return Air Assembly

To simplify installation, locate and install the return air assembly 

first. See 

Figure 4

. If desired, the return opening can be located 

inside a closet with louvered doors that has an open area equal 

to or greater than a 12” x 20” grille. The return air grille can be 

placed in the wall of a closet and the ducted into the filter box 

through a boxed-in area at the closet floor level. 

Make sure the 

filter is readily accessible.
NOTE:

 The return air box with grille and filter should not be 

located in heavy traffic areas like hallways or center of rooms. 

A good spot is in a corner or under a table, if a minimum two 

inch clearance is available.
1. Start the installation from under the home by cutting a small 

hole in the sub-floor. Determine how the floor joist location 

will affect cutting the opening needed for the return air box. 

NOTE:

 Floor joists are generally located on 16” centers, 

leaving 14-3/8” between joists.

2. After measuring the return air box (approximately 12-1/4” x 

20-1/4”), cut the hole through the floor so that the box will fit 

between the floor joists. Care should be taken when cutting 

through carpeting to avoid snags. 

NOTE:

 In most installations it 

will be necessary to cut a similar hole in the fiberboard directly 

under the hole in the floor. However, if the floor is more than 

ten inches deep, it will only be necessary to cut a hole for the 
collar on the return air box or for the insulated duct.

3. Set the box into the opening and fasten with screws or nails.

4. Install the filter and return air grille in place.

Locating & Installing the Supply Damper(s)

 CAUTION:

If installing this air conditioning system in 

conjunction with a furnace, a damper must be 

installed in the furnace base assembly to prevent 

cold air from being discharged around the heat 

exchanger. Damage to the heat exchanger and 

asphyxiation may occur if a damper is not 

installed.
Check with the furnace manufacturer for damper 

requirements. Failure to install the required 

furnace damper may invalidate code agency 

listing and limited warranty on the furnace.

When locating the supply damper(s), carefully check floor joists 

and frame members that could interfere with the installation of the 

damper or flexible duct. Ideally, the damper (

Figure 5

) should be 

located in the bottom of the main duct, forward of center of the 

home, at least three feet from the nearest register. The round 

supply opening in the slanted side of the damper should face 

the side of the home where the heat pump is located.
1. Locate the center of the heat duct by cutting a small hole in 

the fiberboard below the duct at the desired location.

2. Cut a hole approximately 3/4” larger than the damper opening 

in the fiberboard.

3. Cut a 9-1/8” x 13-1/8” hole in the duct and bend over all tabs 

flat on the inside of the heat duct.

4. Insert the damper into the duct and bend over all tabs flat on 

the inside of the heat duct.

5. Seal the opening between the fiberboard and damper or 

flexible duct.

Condensate Drainage

A 3/4” condensate fitting extends out of the side of the unit 

as shown in 

Figure 6

. The drain trap, shipped in the electrical 

compartment, must be installed to prevent water from collecting 

inside the unit.

1. Thread the elbow provided with the unit into the drain 

connection until hand tight.

2. Connect the condensate tubing onto the fitting, forming a trap 

(

Figure 6

) near the drain connection.

3. Route the condensate tube from the trap to a suitable drain. 

NOTE:

 For proper drainage, make sure the trap is level to 

the ground and tubing outlet is below trap level.

Transition

Duct Screws

Supply Air

Return Air

Duct

Dimples

Figure 3. Return & Supply Air Collars

Содержание Q7RE Series

Страница 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Страница 2: ...Air Circulation 10 System Heating 10 System Cooling 10 Short Cycle Protection 10 Emergency Heat 10 Forced Defrost Mode Field Test 10 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 COMP...

Страница 3: ...d any other flammable vapors and liquids in the vicinity of the unit CAUTION This unit uses R 410A refrigerant DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the...

Страница 4: ...rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly desig...

Страница 5: ...insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements HEAT PUMP INSTALLATION Unpacking the Uni...

Страница 6: ...or joists Care should be taken when cutting throughcarpetingtoavoidsnags NOTE Inmostinstallationsit will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor Howev...

Страница 7: ...rical box of the unit The installer should become familiar with the wiring diagram before making any electrical connections to the unit An electrical disconnect must be located within sight of and rea...

Страница 8: ...her location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lightingfixtures andconvectiveheatfromwarmairregistersor electrical appliances Refer to the therm...

Страница 9: ...28 1084 29 1027 31 967 33 Tap T3 1266 25 1332 24 1291 24 1245 25 1192 27 1132 28 1067 30 995 32 Tap T4 1518 21 1481 21 1442 22 1400 23 1355 23 1307 24 1256 25 1202 26 Tap T5 1686 19 1644 19 1601 20 15...

Страница 10: ...ting Set the thermostat system mode to HEAT and the fan mode to AUTO Change the thermostat temperature selector above the existing room temperature and check for the discharge of warm air at the suppl...

Страница 11: ...to the System Heating section on page 10 Anti Short Cycle Timer Test The 5 minute time delay feature can be bypassed by shorting the TEST pins together Heating Mode WhentheTESTpinsareshortedtogetherfo...

Страница 12: ...75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 238 135 137 239 139...

Страница 13: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 26...

Страница 14: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Страница 15: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Страница 16: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Страница 17: ...ctric Heater Power Supply 1 125 Power Supply 0 875 Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NU...

Страница 18: ...connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Emp...

Страница 19: ...servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant...

Страница 20: ...1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105...

Страница 21: ...nd stage outdoor thermostat is field supplied NOTE 2 HUD outdoor thermostat is not factory installed in all models For HUD applications Remove white wire between terminal W2 and W2 IN terminal C G O W...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...essure high side Stage 1 Suction Pressure low side FILTER SYSTEM Filter s secured in place YES NO Filter s clean YES NO 10331420 Replaces 10270500 INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OW...

Отзывы: