Commissioning and operation
7.2.6 Tightness
test
Performance:
£
Close operating seal, as described in
manual (
chapter 7.2.5)
£
Close emergency seal (1)
(
chapter 4.5.3)
£
Remove locking screw from test
connection (2)
£
Insert test funnel (3)
£
Fill in clear water up to upper edge of
test funnel (100 mm)
£
Observe water level for 10 min. If
water level sinks, replenish with clear
water until a water column of 100 mm
is again reached. Note down reple-
nished water quantity.
2
3
1