49
Installation
6.4.5 Connect fault signal contacts (optional)
As standard design, the control is equipped with a potential-free contact for the
connection to annunciators (PCs, telephones, alarm devices).
CAUTION
The contact works as changeover contact and closes if a breakdown is
signalled. When configurating the contacts, pay attention that a max. current of 500mA
is not exceeded.
For further accessories, such as signalling plant, refer to ...
ACO K9 online under www.aco-haustechnik.de.
Connection of fault signal contacts
£
Connect component in the connecting box of the control (
chapter 5.3.1)
6.4.6 Extension
kit
If the pressure hose or motor supply cable, included in scope of supply, are too short
(standard length 5 m), a cable extension kit (10 m) is available as accessory.
CAUTION
A total length of 15 m must not be exceeded, as this could affect the
function.
Further accessories
ACO K9 online under www.aco-haustechnik.de.