ACO Oleopator P N 3/950 Скачать руководство пользователя страница 6

www.ACOEnvironment.us

6

V

2.3 Separator positioning

The purpose of a separator is to collect 
light oils for proper disposal. Timely 
emptying and maintenance is critical for 
effective operation. Alarm systems can help 
ensure light oils and sludge are removed 
in a timely fashion and can alert potential 
maintenance issues. 

Alarm failure (or failure to action alarm 

alerts) and back flow from sewer are 

potential causes of operation error and 
pollution. 

These can be overcome in certain 
applications by adjusting height of separator 

relative to collection vessel/drain.

Super elevated positioning is where the 
cover of the separator is higher by a 
minimum height (V) than the collection 

fixture.

V - Super elevated positioning

Cover 

only

Cover & 

Shaft

Cover & 

Shaft

Size

Pedestrian

in (mm)

Heavy duty

in (mm)

NS3/450

1.78 (45) 2.75 (70) 5.90 (150)

NS3/670

1.78 (45) 2.75 (70) 5.90 (150)

N 3/950

1.78 (45) 2.75 (70) 5.90 (150)

NS6/660

1.57 (40) 2.56 (65) 5.71 (145)

NS6/1210

1.57 (40) 2.56 (65) 5.71 (145)

NS10/1080

1.97 (50)

2.95 (75)

6.10 (155)

Installation situation

 Super elevated

positioning

No

No

Yes

Yes

Alarm system

No

Yes

No

Yes

Operating situation

s

 Ready for

use

Normal operation

Normal operation

Normal operation

Normal operation

 

Max. oil =

 float closure

= blockage

Oil will leak from cover

Alarm will alert and 

oil will leak from cover

Oil will stay in separator,

wastewater will flood from 

collection fixture

Alarm will alert and oil will stay 

in separator, wastewater will 

flood from collection fixture

 Backflow

from sewer

Oil will leak from cover -

unless a backflow prevention 

pump is used downstream 

from separator

A

larm will alert and oil will 

leak from cover - unless a 

backflow prevention pump 

is used downstream from 

separator

Oil will stay in separator,

wastewater will flood from 

collection fixture

Alarm will alert and oil will stay 

in separator, wastewater will 

flood from collection fixture

Содержание Oleopator P N 3/950

Страница 1: ...oil and sediment separator system ACO Construction Building Products Oleopator P Oil Water Separator Operating Guide 1 Installation 2 Initial set up commissioning 3 Operation 4 Maintenance ACO Enviro...

Страница 2: ...m inflow volume GPM at which point additional inflow bypasses the separator and diverts directly to the outlet pipe Typically most pollutants are washed into the separator during the initial flow so e...

Страница 3: ...___________________________________________________________7 3 Initial Set up 3 1 Prior to filling the system________________________________________________________________________________8 3 2 Filli...

Страница 4: ...r complying with the following points Only operate the separator according to regulations and in proper condition Ensure that function of protection devices is not impaired Adhere to a scheduled maint...

Страница 5: ...n Oleopator separators are intended for in ground installation Care must be taken to determine correct installation to take into account site loadings and traffic patterns Details are provided for lig...

Страница 6: ...3 670 1 78 45 2 75 70 5 90 150 N 3 950 1 78 45 2 75 70 5 90 150 NS6 660 1 57 40 2 56 65 5 71 145 NS6 1210 1 57 40 2 56 65 5 71 145 NS10 1080 1 97 50 2 95 75 6 10 155 Installation situation Super eleva...

Страница 7: ...tions 1 Excavate area 60 wider and 12 deeper than the separator this allows for a 12 aggregate base compacted to Proctor density 97 2 Check level of unit and inverts of inlet outlet pipes 3 Backfill a...

Страница 8: ...er of the LGA Test report Volume of separator and sludge trap Maximum storage volume and maximum thickness of light oil layer Maximum permissible sludge thickness 3 2 2 Filling procedure 1 Ensure inle...

Страница 9: ...nding ground When any of these events occur a signal is sent to the building management system which can send out audio visual and SMS alerts to ensure maintenance can be carried out before the separa...

Страница 10: ...y and clean separator as required see disposal requirements Remove any coarse floating material Inspect all components of alarm system if used Immediately rectify any faults identified Report findings...

Страница 11: ...e units for clean back up spare coalescence unit The dirty coalescence unit can be stored in a water filled container until to prevent dirt drying hard onto unit until it can be cleaned 5 3 Oil Sludge...

Страница 12: ...4764 Fax 440 285 7005 Electronic Contact info acousa com www acousa com Southeast Sales Office 4211 Pleasant Road Fort Mill SC 29708 Toll free 800 543 4764 Fax 803 802 1063 ACO DRAIN The world s lead...

Отзывы: