For your safety
8/ 100
Oleolift-C
Protection against backflow:
The required elevation must also be maintained with regard to the local backwater level of the
draining sewer system. In addition to the decisive level of the area to be drained on the inlet
side, the backwater level must also be considered as an additional decisive level for the required
elevation. The higher measure is to be applied for the excess height.
As the plant is equipped with an integrated pump station (double pump station according to DIN
EN 752 or DIN EN 12056-4) and is installed with a backflow loop, the plant does not need to be
installed in an elevated position.
1.2 Improper use
Scope and changes
Applications and uses other than those described in chapter 1.1 and modifications are not
permitted.
Non-approved parts
Installation of unapproved parts impairs safety and excludes any guarantee from ACO. In the
event of replacement, only use original ACO parts or spare parts approved by ACO.
Introduction
■
No substances may be discharged into the plant which could impair the stability of the
materials used, the functional capability of the plant or compliance with the discharge
requirements into the downstream wastewater treatment plant or a water body (refer to
e.g. Series DWA-M 167). This includes in particular:
Faecal wastewater
Wastewater containing organic oils and greases
Wastewater in which a significant proportion of stable emulsions is present
Aggressive substances and cleaning agents containing chlorine
■
Drainage of areas where light liquids do not accumulate, such as roofs and yards,
should not be discharged into separator systems
Entry into the plant
■
The built-in fittings and components (e.g. separator inlet, coalescence insert) are
designed for operation as separators. They are not designed to be a step or foot board
for people and storage e.g. heavy cleaning devices. The bearing force is not designed
for such purposes.
■
The use of an access aid for accessing or entering the plant is anchored in the
requirements of the employers' liability insurance association.