Operation
79/ 100
Oleolift-C
When the water reaches the “OFF” level, Pump
2 switches off.
OFF or
SDP OFF
Î
Fill pump station chamber.
When the water level reaches the “Base load”
(BL) level, pump 1 switches on.
Î
Increase the inlet flow so that the water
level continues to rise.
BL
When the water reaches the “Peak load” (PL)
level, Pump 2 also switches on.
Î
Interrupt the inlet.
PL
When the water level reaches the “OFF” level,
the pumps switch off.
OFF or
SDP OFF
Ending automatic mode:
Î
End pump 1 and 2 automatic mode,
Chapter 4.3.2 "Page
view _ Detailed view".
Pump 1
P1
Manual
OFF
Automatic
Close
Pump 2
P2
Manual
OFF
Automatic
Close
Î
Fill pump station chamber.
If the water reaches the “Flood alarm” (AL)
level, an alarm sounds, a fault message
appears in the display panel and the LED for
“Flood alarm” lights up:
Î
Interrupt the inlet.
AL