Operation
75/ 100
Oleolift-C
Touch panel
page view
Operat-
ing field
Meaning
Recommend-
ed settings
Commissioning
settings
Settings / Pump-Con-
trol / Switch-on and
switch-off points
1
Activate or deactivate
alarm message during
dry running
Deactivate
2
Activate or deactivate
alarm message for Max
- Alarm
Activate
4
Max - Alarm switch-on
point
72 cm (NS 3-6)
93 cm (NS 6-10)
84 cm (NS 15-30)
Max - Alarm switch-off
point
?
Peak load switch-on
point
67 cm (NS 3-6)
88 cm (NS 6-10)
79 cm (NS 15-30)
Peak load switch-off
point
?
Base load switch-on
point
62 cm (NS 3-6)
83 cm (NS 6-10)
74 cm (NS 15-30)
Base load switch-off
point
?
Dry run switch-off point
5 cm
Dry run switch-on point
?
4.4.2 Circuit breaker
DANGER
Danger of electric shock due to dangerous electrical voltage
■
Special care must be taken when making adjustments to the electrical
components.
The following setting values for the maximum
current consumption of the pumps must be set
on the two circuit breakers 2Q1 and 3Q2
Plant 3-10 _ DL 50
2.4 A
Plant 6-10 _ DL 100
3.4 A
15-30 / 4500 _ DL 100
7.3 A
The circuit breaker must then be closed.