Installation
48/ 100
Oleolift-C
Installation of the idOil-OIL / 1 + 2 oil layer sensors
Î
Lift the cover out of the cover frame and
store to the side (1).
Î
Place dowels in the maintenance opening
of the cover plate and screw in the screw
hooks (2).
Î
Lay the connection cable of the sensor
according to the height measurement,
according to the following table
"Adjustment of the switching points", in
a loop around the screw hook and fix it
with cable ties (3).
Î
After mounting all sensors, put the cover
back in place.
2.
1.
3.
Setting switching points to oil layer sensors idOil-OIL / 1 + 2
H
LIQ
H
OIL/1 (80 %)
H
OIL/2 (100 %)
2
B
1
1 = idOil-OIL / 1 oil level sensor
2 = idOil-OIL / 2 oil level sensor
B = Reference point / lowest point of the
internal
container base
Plant/NS
H
OIL / 1
H
OIL / 2
3-6 / 600 _ DL 50
1,070
1,040
3-6 / 900 _ DL 50
1,070
1,040
3-6 / 1200 _ DL 50
1,070
1,040
3-6 / 1800 _ DL 50
1,070
1,040
3-6 / 2500 _ DL 50
1,070
1,040
6-10 / 2500 _ DL 50
1,490
1,440