Product Description
22/ 100
Oleolift-C
Before recommissioning, the separation chamber must be filled with fresh water again.
The sensors mounted in the separator chamber are connected to the idOil-D30 warning system
(mounted on a DIN rail in the control unit) and register the following conditions:
■
Oil layer sensor idOil-OIL / 1 reacts to the separating line oil / water at 80 % of the
maximum oil storage quantity
■
Oil layer sensor idOil-OIL / 2 reacts to the separating line oil / water at 100 % of the
maximum oil storage quantity
■
The idOil-LIQ high liquid level sensor reacts to the maximum permissible liquid level
ATTENTION
The following measures must be taken after the following messages are displayed
on the control unit:
Message
Actions
80 % of the maximum oil storage capacity
Schedule emptying and cleaning of the separator
chamber and perform it immediately. Before emptying,
first empty or pump out the contents of the pump station
chamber!
100 % of the maximum oil storage capacity
Empty and clean the separator chamber immediately.
Before emptying, first empty or pump out the contents of
the pump station chamber!
As the switching on of the submerged pumps in the
pumping station is blocked by this message, the inflow
of wastewater into the plant must be prevented until after
the emptying process. Otherwise there is a risk of light
liquid escaping from the maintenance opening!
maximum liquid level H-AL
As the switching on of the submerged pumps in the
pumping station is blocked by this message, the inflow
of wastewater into the plant must be prevented until after
the emptying process. Otherwise there is a risk of light
liquid escaping from the maintenance opening!
A check of the plant function with a possible intermediate
cleaning of the coalescence insert or complete emptying
and cleaning must be carried out.
2.4.2 Sampling
The wastewater from the separator chamber flows via the inlet pipe, which protrudes over
the partition wall, into the pump station chamber at a free gradient. There is sufficient space
between the pipe bottom of the inlet pipe and the water level PL (peak load) to take a sample
from the draining water of the light liquid separator (e.g. with a 1 litre wide-neck bottle).