6.2 SENSOR SETTING
The illustration below depicts the completely mounted sensors. The detail shows the
extension of the sensor cable; also see hanging instructions in the idOil-30 Installation
and Maintenance Manual. The height of the sensors is relative to the upper edge of the
inlet pipe and must be set per the table and diagram below.
ACO Separators
Alarms Assembly Instructions
1 Fitting position of sensor support
red circles.
CAUTION
Do not mount support above inlet
or outlet.
2 Sensor setting
sensors. The detail shows the extension of the sensor ca-
“idOil-30 Installa-
”. The di
ff
erent sensors
−
H3,
referring to = upper edge of inlet submersible pipe (1).
(For dimensions, see below table).
1
1
Oleopator P Model
H1 Sludge Sensor
Height
in (mm)
H2 Oil Sensor
Height
in (mm)
H3 High Level
Sensor Height
in (mm)
NS3/450
30.32 (770)
11.02 (280)
1.38 (35)
NS3/670
34.25 (870)
11.02 (280)
1.38 (35)
NS3/950
38.19 (970)
11.02 (280)
1.38 (35)
NS6/660
34.65 (880)
12.99 (330)
0.59 (15)
NS6/1210
46.46 (1180)
12.99 (330)
0.59 (15)
NS10/1080
46.46 (1180)
12.99 (330)
0.59 (15)