The further door opening function must be activated in the panel settings by activating the “Further 
door opening impulse", which is sent to subsequent panels, and by setting the wait time for opening 
after receiving this impulse. Optionally, "auto-opening" can also be enabled - after a waiting time the 
panel will open the door without having to press any button. By entering the right times, the entry is 
seamless, even with multiple panels. In default settings the further door opening function is disabled. 

 

Make sure to set the correct ranges of supported physical  addresses in the panels.  These 
ranges must not overlap, as it may cause the entire system to malfunction.

 

 

A system in which multiple FAM-P and FAM-PV panels are installed will operate correctly only 

if the number of physical addresses in the system remains at 150 or below (from the pool of 255). If 
the number of apartments exceeds 150 or if their numbers repeat, use  the  or CDNP series 
panels (which support 255 apartments). Familio series panels are compatible with CDNP and Inspiro 
series panels, and can work together in one door entry system. 

 

1 - INSTALLATION OF THE SLAVE PANEL 

 

Installation  of  multiple  Familio  panels  in  video  version  also  requires  a  bus  made  only  with 

UTPs,  with  the difference  to  the  CDNP/INSPIRO  systems being  that  only  one  UTP  cable  can be 
arranged to the "slave" panel and a special "Intermediate combiner to FAM-PV" (symbol: FAM-PV-
Sp) must be installed at the end of the UTP (max 100m). The UTP is arranged to the combiner from 
the previous (upstream) panel and then from the combiner to the next panel or directly to monitors 
(splitters). The combiner is not used in the first Familio master panel. 

If several Familio  audio panels are installed, two bus  wires are arranged to the first  panel: 

Line+, Line- and Line+ are connected to the ML terminal of the next panel (Line- to Line-). Similarly, 
two wires, Line+ and Line-, are arranged to the next panel entering ML and Line- terminals, etc. 

If  the  first  panel  is  an  audio  panel,  and  further  panels  are  video  panel,  the  bus  wires  are 

arranged to the first video panel: Line+, Line-, and -DC POWER and Line+ are connected to the ML 
terminal of the next panel (Line- to Line-, and -DC POWER to -DC POWER). If the first panel is a 
video panel and the next one is an audio panel, the “Combiner with no camera" (symbol: CDNVSbk) 
must be used at the audio panel; the combiner may be installed at a distance from the audio panel; 
UTP to the combiner must be arranged from the video panel; the UTP bus must be arranged to the 
splitters, and the 4-wire bus to the audio panel (Line+, ML, Line- and -DC POWER). If the last panel 
is an audio panel, the power supply (+DC POWER) should be connected to the combiner with no 
camera. 

When using CDNP/ISNPIRO panels, connect them as per their installation instructions. They 

are fully compatible with the FAM-P and PV series and are combined similarly. 

 

The system must run on one type only of power supply - the recommended power supplies 
are DC power supplies. For audio devices and passive receivers, AC power can be supplied 
from  transformers,  but  each  device  must be  powered  from  a  separate  transformer and  DC 
and AC power supplies (transformers) must not be mixed in one system. The entire system 
needs to be powered from the same phase.

 

 

2 - PROGRAMMING THE SLAVE PANEL 

 

The Familio panel can work both as a slave and master panel. Programming the Familio panels is 
described in chapter X.  Each panel must be programmed individually and each panel may feature 
different settings, for instance: 

Содержание FAM-P

Страница 1: ...1 DOOR ENTRY SYSTEMS EXTENDED USER INSTRUCTION OF FAM P AND FAM PV DOOR ENTRY SYSTEMS 62 002 Suchy Las ul Diamentowa 7 tel fax 61 843 93 71 www aco com pl...

Страница 2: ...ccess code 32 Modification of administrator s initial access code 33 2 SETTING E LOCK OPENING TIME 33 3 SETTING THE NUMBER OF RINGTONES PERMISSION TO CALL APARTMENT 33 4 TURNING ON OFF THE DOOR OPENIN...

Страница 3: ...he opening code resident administrator 2 Setting E lock reset time 3 Setting the number of ringtones permission to call apartment 4 Turning the door opening signal off on 5 Setting one of four rington...

Страница 4: ...c keypad while all settings are available via FAM_P computer program PC Windows Adding deleting archiving transferring between panels proximity fobs can be done using the ACC_v3 software PC Windows In...

Страница 5: ...e customised to individual requirements Adjustable camera position in each direction FAM PV panels Option of image viewing in darkness infrared illumination FAM PV panels Support for proximity key fob...

Страница 6: ...addresses from the bottom address 1 bottom button and successively up to address 6 top button It is also possible after changing the settings via the PC program or directly on the panel numeric keypa...

Страница 7: ...d It is possible to open without having to connect with the apartment In this case on classic uniphones the handset must be picked up and the open button pressed three times on active receivers INS UP...

Страница 8: ...ervice program 9 By default the code table is only added to panels FAM P ZS and FAM PV ZS For other versions of the panel use the code table that is used in the panel master panel or generate it using...

Страница 9: ...sed for opening via an additional module such as an I O module The module is connected to the EXTMOD socket on the panel board and configured via the PC program Automatic opening when calling an addit...

Страница 10: ...XI CDN U signalling module with opening function This module can be used to connect additional devices signalling ringing in the apartment for instance additional bells light bulbs signallers etc for...

Страница 11: ...11 V MOUNTING AND CONNECTING THE PANEL ASSEMBLY The panel should be assembled so as to minimise the impact of adverse weather conditions in particular water Allen key 3 Allen key 3 Allen key 3...

Страница 12: ...s where the camera lens may be exposed to direct perpendicular light from the sun street lamps etc 2 CONNECTING THE PANEL All connections in the installation must be soldered The following wires need...

Страница 13: ...cross section with 1 mm2 wire the distance can be increased to 400 m with 1 5 mm2 wire the distance can be increased to 600 m with 2 5 mm2 wire the distance can be increased to 1000 m Use CDNV RJ45 m...

Страница 14: ...number of receivers in the entire system detailed information can be found in the assembly instructions for the active receivers used In the case of video panels the wiring between the panel and the...

Страница 15: ...stalled in the panel available under the panel terminals When working with reversible E locks voltage appears on ELOCK output depending on transformer or DC power supply used 15VDC use suitable revers...

Страница 16: ...16 3 WIRING DIAGRAMS FOR SINGLE PANEL INSTALLATION Audio panel installation with passive receivers should be connected as per the diagram below Line Line Line Line...

Страница 17: ...17 The installation of audio panels with active receivers should be connected as per the diagram below...

Страница 18: ...18 The installations of audio panel with additional external camera and monitors should be connected as per the diagram below To monitor or splitter...

Страница 19: ...ting the bus cable orange and brown together to DC terminal of the panel in this case the maximum distance between the panel and the monitor is 70m If the additional power supply is connected directly...

Страница 20: ...20 Video Panel with several monitors should be connected as per the diagram below Rozdzielacz Splitter Rozdzielacz Splitter...

Страница 21: ...he panel microphone using the MIC potentiometer adjust the panel speaker volume level using the SPK potentiometer As the MIC and SPK values are set turn the BALANCE potentiometer to determine the posi...

Страница 22: ...of the busy panels Calling and connection topology of Slave panels is shown in the figure below where A is the Master panel B C D E F are Slave panels Only those receivers that are physically connect...

Страница 23: ...he first Familio master panel If several Familio audio panels are installed two bus wires are arranged to the first panel Line Line and Line are connected to the ML terminal of the next panel Line to...

Страница 24: ...or opening codes will be the same for all apartments For proper operation of a system with multiple panels configuration is required for the number and range of apartment addresses that a panel is to...

Страница 25: ...25 Installation of multiple audio panels with active receivers should be connected as per the diagram below...

Страница 26: ...multiple audio panels with additional external camera and multiple monitors should be connected as per the diagram below Rozdzielacz Splitter Kolejne pi tra Next floors Sumator bez kamery Intermediate...

Страница 27: ...27 Installation with multiple video panels and monitors should be connected as per the diagram below Rozdzielacz Splitter Sumator po redni do FAM PV Intermediate combiner for FAM PV...

Страница 28: ...mator po redni do FAM PV Intermediate combiner for FAM PV Rozdzielacz Splitter Rozdzielacz Splitter Rozdzielacz Splitter Sumator po redni do FAM PV Intermediate combiner for FAM PV Sumator bez kamery...

Страница 29: ...er for FAM PV Klatka budynek X Staircase building X Kolejne pietra Next floors Kolejne pietra Next floors Klatka budynek Y Staircase building Y Rozdzielacz Splitter Sumator po redni do FAM PV Intermed...

Страница 30: ...30 Installation with two panels the first of which is an Audio panel should be connected as per the diagram below example 4 Kolejne pietra Next floors Rozdzielacz Splitter...

Страница 31: ...he panel such as individual access codes opening time ringtone etc Service programs are also available to facilitate installation and repairs Basic parameters can be changed using the service menu acc...

Страница 32: ...LE To enter the panel programming function with 0000 installer s code press the key followed by 1507 fixed digits and 0000 1 5 0 7 0 0 0 0 Entering the programming mode is confirmed by an up modulated...

Страница 33: ...ting time from 1s to 10s by entering a digit between 0 and 9 0 means 10 seconds When the panel is reset to factory settings the time is set to 4s 3 SETTING THE NUMBER OF RINGTONES PERMISSION TO CALL A...

Страница 34: ...partment With the receiver s handset lifted press the door opening button three times for passive receivers or press the door opening button once for active receivers The panel will confirm receipt of...

Страница 35: ...dents are set across the whole system For panels with only a numeric keypad the code table number is entered in accordance with the code table supplied Any code table can be generated and name tag pri...

Страница 36: ...code Enabling the restriction of the administrator s code from 6 to 4 digits Doorman s call Enabling the doorman s call by shorting the INPUT Call only button Permitting calls only from direct call b...

Страница 37: ...No 1 or 2 or 3 E lock triggering time as for standard opening Activation of the OUTPUT for a pre set time after pressing the F2 key on the uniphone or after selecting the code preceded by the double p...

Страница 38: ...itional number 1 Address Physical address to which the panel will call after dialling the additional number Tone Ringtone in the apartment after dialling the additional number Number of ringtones Numb...

Страница 39: ...e CDNP INSPIRO i e calls can be made directly from the numeric keypad and the codes must be preceded by the apartment number and the button of the button Once the factory settings are successfully res...

Страница 40: ...surface causing abrasion of its natural protective coating and increasing the risk of corrosion XVI SAFETY RULES FOR INSTALLATION AND USE Installation should be carried out by a qualified installer B...

Страница 41: ...12V between GND and ELOCK terminal Each panel in the system must feature a separate power supply Door opening signalled by the unit but E lock won t work Check E lock or E lock connection to the panel...

Отзывы: