background image

 

Installation and Operation Instructions

ACI/TUCH Room Unit 

GENERAL INFORMATION 

WIRING INSTRUCTIONS 

The ACI/TUCH Room Unit is factory-configured to 
support your specific requirements. 

The number of wires needed to connect the ACI/TUCH 
Room Unit to a controller depends on the application.  
Most applications require five wires to support the 
temperature output, the set point output, the RH output, 
power, and ground (common); although some 
applications will require additional wires.  All signals 
are common ground referenced.  

ACI recommends 16-

22 AWG twisted pair wires or shielded cable for all 
sensor installations.  Be sure to connect the cable 
shield to the ground at the controller ONLY. 

 

CAUTION 

• 

CHECK THAT THE ACI/TUCH ROOM UNIT IS 
CORRECTLY CONFIGURED FOR THE 
APPLICATION; CONTACT ACI IF YOU ARE 
UNSURE. 

 

• 

THE ACI/TUCH ROOM UNIT IS A PRECISION 
INSTRUMENT; PLEASE HANDLE IT WITH 
CARE! 

 
WIRING DIAGRAM 

RH/FAN
RH signal to controller.

OFB
Occupied feedback signal from controller.

COM (-)
Ground or signal common, 20-28Vac (-).

POWER (+)
+15 to +30VDC, or 20-28Vac (+).  See notes.

SEN
Temperature sensor signal to controller.

SET
Set point temperature signal to controller.

OR
Override signal to controller.  See notes.

AUX
Auxiliary signal to/from controller.  See notes.

 

 

MOUNTING INSTRUCTIONS 

Separate the cover from the base.  Attach the base 
directly to drywall, or to a standard 2” x 4” junction box 
using the mounting hardware provided.  Refer to the 
wiring instructions to make the necessary connections.  
After wiring, attach the cover to the base and turn the 
(2) hex-screws at the bottom of the base until the cover 
cannot be removed. 
 

WARNING 

• 

REMOVE POWER BEFORE WIRING!  NEVER 
CONNECT OR DISCONNECT WIRING WITH 
POWER APPLIED.  DO NOT ALLOW LIVE 
WIRES TO TOUCH THE CIRCUIT BOARD! 

 

CAUTION 

• 

WIRING MUST COMPLY WITH APPLICABLE 
LOCAL AND NATIONAL ELECTRICAL 
REGULATIONS. 

NOTES: 
1.  The OR signal can be factory configured to short the SEN or SET terminals 
to COM(-) to eliminate the need for a wire jumper between terminals OR and 
SEN or SET outputs. 

 

 

• 

DO NOT RUN THE ACI/TUCH ROOM UNIT 
WIRING IN ANY CONDUIT WITH MAINS 
POWER SYSTEM WIRING. 

2.  If the ACI/TUCH Room Unit has any output configured as 0-10V or 2-10V, 
the voltage at the POWER(+) terminal must be at least +18VDC. 
 
3.  The AUX output/input is normally not used.  For special applications, the 
AUX output/input can be factory configured to support various functions. 

 

 

• 

ACI RECOMMENDS USING A SEPARATE UL-
LISTED CLASS 2 TRANSFORMER WHEN 
POWERING THE ACI/TUCH ROOM UNIT 
WITH 24VAC!  FAILURE TO WIRE DEVICES 
WITH THE CORRECT POLARITY WHEN 
USING A SHARED TRANSFORMER MAY 
RESULT IN DAMAGE TO ANY DEVICE 
POWERED BY THE SHARED TRANSFORMER. 

 
 
 

 

2305 Pleasant View Rd. 

 Middleton Industrial Park 

 Middleton, WI 53562 

PHONE (608) 831-2585 

 FAX (608) 831-7407 

I0000493 REV 1  06/09/2008 

 

Page 1 of 2 