Installation and Operation Instructions

ACI/TUC Room Unit 

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION! 

 
 

GENERAL INFORMATION 

• 

FAILURE TO WIRE DEVICES WITH THE 
CORRECT POLARITY WHEN USING A 
SHARED TRANSFORMER MAY RESULT IN 
DAMAGE TO ANY DEVICE POWERED BY 
THE SHARED TRANSFORMER. 

The ACI/TUC Room Unit is factory-configured to 
support your specific requirements. 
 

CAUTION 

 

• 

CHECK THAT THE ACI/TUC ROOM UNIT IS 
CORRECTLY CONFIGURED FOR YOUR 
APPLICATION; CONTACT ACI IF YOU ARE 
UNSURE. 

WIRING INSTRUCTIONS 

The number of wires needed depends on the application, 
with 4 wires minimum and 8 wires maximum required 
to support the functions of the ACI/TUC Room Unit.  
Generally, one wire is required for each function, one 
wire for power, and one wire for ground.  All functions 
are common ground referenced.  

ACI recommends 16-

22 AWG twisted pair wires or shielded cable for all 
sensor installations.  Be sure to connect the cable 
shield to the ground at the controller ONLY. 

 

• 

THE ACI/TUC ROOM UNIT IS A PRECISION 
INSTRUMENT; PLEASE HANDLE IT WITH 
CARE! 

 

MOUNTING INSTRUCTIONS 

Separate the cover from the base.  If your application 
includes a communications jack, please refer to the 
communications wiring instructions document before 
mounting the base.  Attach the base directly to drywall, 
or to a standard 2” x 4” junction box using the mounting 
hardware provided.  Refer to the wiring instructions to 
make the necessary connections.  After wiring, attach 
the cover to the base and turn the (2) hex-screws at the 
bottom of the base until the cover cannot be removed. 

 
WIRING DIAGRAM 

FAN
Fan speed signal to controller.

OR
Override signal to controller.  See notes.

SET
Setpoint temperature signal to controller.

SEN
Temperature sensor signal to controller.

COM (-)
Ground or signal common, 24Vac (-).

OFB
Occupied feedback signal from controller.

AUX
Auxiliary signal to controller.

POWER (+)
+15 to +30VDC, or 24Vac (+).  See notes.

 

 

WARNING 

• 

REMOVE POWER BEFORE WIRING!  
NEVER CONNECT OR DISCONNECT 
WIRING WITH POWER APPLIED.  DO NOT 
ALLOW LIVE WIRES TO TOUCH THE 
CIRCUIT BOARD! 

 

CAUTION 

• 

DO NOT RUN THE ACI/TUC ROOM UNIT 
WIRING IN ANY CONDUIT WITH LINE 
POWERED WIRING. 

 

NOTES: 

• 

IF THE ACI/TUC ROOM UNIT IS POWERED 
BY 24VAC, THE 24VAC POWER AND 
GROUND WIRES SHOULD BE RUN IN A 
SEPARATE CABLE FROM SIGNAL WIRES.  
SEPARATE THE POWER CABLE FROM THE 
SIGNAL CABLE BY AT LEAST 6 INCHES 
ALONG THE ENTIRE WIRING RUN. 

1. 

Override may be factory configured to function on the SEN or SET terminals to 
eliminate the need for a wire jumper between terminals OR and the SEN or the 
SET outputs. 

 
2. 

If your ACI/TUC Room Unit has any output configured as 0-10V, 2-10V,            
0-20mA, or 4-20mA, the voltage at the POWER (+) terminal must be at least 
+18VDC. 

 
3. 

If your ACI/TUC Room Unit is configured for +5VDC operation, apply a DC 
voltage within the range of +4.75VDC to +5.25VDC to the POWER (+) terminal; 
any voltage outside this range may damage the ACI/TUC Room Unit or cause 
improper operation. 

 

 

• 

ACI RECOMMENDS USING AN ISOLATION 
TRANSFORMER WHEN POWERING THE 
ACI/TUC ROOM UNIT WITH 24VAC! 

4. 

Units configured with the fan speed option will have terminals for the FAN and 
AUX signals.  Units without the fan speed option will not have terminals loaded at 
these locations. 

 