BACnet OUTSIDE SERIES

Installation & Operation Instructions

Version 1.0

I0000806

GENERAL INFORMATION

The BACnet Outside Series sensor is designed for use with 
electronic controllers in commercial heating and cooling 
building management systems. The ACI BACnet Immersion 
Series sensor can be ordered to monitor temperature, RH, 
or temp/RH of outside environments. It uses BACnet MS/TP 
for physical connection to a BAS or controller, has dip switch-
es to set addresses and baud rate, and has on board 
end-of-line termination. There is no analog output.

WIRING INSTRUCTIONS

The BACnet Outside Series temperature sensor has a 
depluggable terminal block located on the front of the 
PCB. For ease of wiring, we recommend removing the 
block, wiring, and reattaching before before 
mounting. 16 to 22 AWG two conductor shielded 
cable is recommended for powering the sensors. 

ACI recommends using Belden 3105 or compatible 
cable for RS-485 communication wiring. This wire has 
120 ohm input impendence. The terminal blocks allow 
for (1) or (2) wires to be connected in each position for 
daisy chaining. Daisy chain the RS-485 wiring and do 
not use “Star” or “T” wiring.

Avoid running communication wires next to AC line 
voltage wires. These can be sources of noise that can 
affect signal quality.

PRECAUTIONS

DO NOT RUN THE WIRING IN ANY CONDUIT WITH 

LINE VOLTAGE (24/120/230 VAC).

Remove power before wiring. Never connect or 

disconnect wiring with power applied.

It is recommended you use an isolated UL-listed 

class 2 transformer when powering the unit with 
24 VAC. Failure to wire the devices with the correct 
polarity when sharing transformers may result in 
damage to any device powered by the shared 
transformer.

FIGURE 1: 

ENCLOSURE DIMENSIONS

EURO (-EH) ENCLOSURE

PROBE 4.70”: TEMP. ONLY

PROBE 3.00”: RH and RH/TEMP.

1.90"

(48.28 mm)

4.30"

(109.22 mm)

3.80"

(96.56 mm)

2.12"

(53.72 mm)

4.70"

(119.46 mm)

2.12"

(53.72 mm)

3.00"

(76.20 mm)