background image

AUTOMATION COMPONENTS, INC                                                                                                                                                                            Version : 4.0 

2305 Pleasant View Road                                                                                       Page 1 of 3                                                                                  I0000598     

Middleton, Wisconsin 53562 (888) 967-5224 

                                                                                                                                    

www.workaci.com

                                                                                                                                                  

 

 

Installation and Operation Instructions

 

                                                           

AUD 

Floating Point or Tri-State Input to Analog Current or Voltage Output 

Versions 1, 2, 3, 4 and 5 

(+)

(-)

(+)

(-)

Analog Signal Output

See E1, E2,

E3 and E4

24 VDC Accessory Output

See Diagram E2

(+)

Power

   

 Set Dip Switch for

Type of Analog Output

Current Out

Voltage Out

Fig. B

Set Dip Switch for

 Offset of Output

Offset of

1 volt or 4mA

Offset adjustable

from 0 to 5 volts

or 0 to 20mA

Fig. C

CAUTION - Don't set both DIP Switches

in ON or OFF position or it will damage AUD

MAKE DIP SWITCH SETTINGS WITH POWER OFF

    

Set Dip Switch for Signal

Output Span (maximum output)

1 Volt (no mA)

10 Volts (no mA)

4 Volts or 16mA

13 Volts (no mA)

Adjustable 1 to 9.5

volts and 4 to 20mA

Adjustable 10 to 20

volts (no mA)

Adjustable 4 to 14

volts (no mA)

Fig. D

Triac Jumper

    Positon

E5

Small box

indicates

switch position

Switch

Legend

Fig. A

Timing

Program #

1 OFF, 2 OFF

1 ON, 2 OFF

1 OFF, 2 ON

1 ON, 2 ON

Version 1 0008Y0A.HEX

5 sec.

15 sec.

30 sec.

90 sec.

Version 2 0244Y0A.HEX

45 sec.

60 sec.

120 sec.

240 sec.

Version 3 0256Y0A.HEX

45 sec.

60 sec.

120 sec.

240 sec.

Note: Version 3 differs in that it will reset to maximum on

startup, or if both inputs pulse 3.5 seconds

Version 4 0537Y0A.HEX

5 sec.

N/A

N/A

360 sec.

Version 5 S-AUD V5.HEX

60 sec.

75 sec.

120 sec.

150 sec.

Pulsed relay contacts

 (optically Isolated)

24 VAC

Power

Supply

    (+) (-)

or VDC

Controller/Triac Output

           (Isolated)

+     -

PWR

+     -

UP

+     -

DWN 24VSIG

24

VAC

+     -

PWR

+     -

UP

+     -

DWN 24VSIG

Separate power

    (+)        (-)

SEE

NOTE

#1

 Supply 24VAC/VDC

E3

E1

Controller

Controller

"UP" Output "DOWN" Output

Pulsed relay contacts

 (not Isolated)

+     -

PWR

+     -

UP

+     -

DWN 24VSIG

E2

Wiring diagram for TEC

(controller mfg. by Siemens

Building Technologies, Inc.

Landis Division)

+     -

PWR

+     -

UP

+     -

DWN 24VSIG

E4

Triac (24 VAC) from Controller

Can share

same power

supply as

TEC

Controller

N.O.

N.O.

C

C

 

INSTALLATION

 

READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION. 

 

Ground yourself before touching board.  Some components are static sensitive. 

 

Mounting: 

Circuit board may be mounted in any position.  If circuit board slides out of snap track, a non-conductive “stop” may be required.  

Use only fingers to remove board from snap track.  Slide out of snap track or push against side of snap track and lift that side of the 

circuit board to remove.  Do not flex board or use tools. 

 

POWER CONNECTIONS – THIS PRODUCT ACCEPTS 24 VDC OR 24 VAC, 50/60 Hz POWER. 

 

Be sure to follow all local electrical codes.  Refer to wiring diagram for connection information.  Make all connections with the power 

off. 

1. 

DC Power

 – Refer to wiring diagram for connection information. 

If the 24VDC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must 

have an MOV, DC Tranzorb, or diode placed across the coil or inductor.  The cathode, or banded side of the DC Tranzorb 

or diode, connects to the positive side of the power supply. 

2. 

AC Power

 – Refer to wiring diagram for connection information. 

Check the wiring configuration of any other loads that may be connected to this transformer.  If required by BAS or 

controller specification, the 24 VAC neutral can be earth grounded at the transformer.  Analog input, digital input, and 

analog output circuits should not be earth grounded at two points.  Any field device connected to this transformer must 

use the same common.  If you are not sure of other field device configuration, use separate transformers for isolation. 

If the 24VAC power is shared with devices that have coils such as relays, solenoids, or other inductors, each coil must 

have an MOV, AC Tranzorb, or other spike snubbing device across each of the shared coils.  Without these snubbers, 

coils produce very large voltage spikes when de-energizing that can cause malfunction or destruction of electronic 

circuits.  Refer to wiring diagram for connection information. 

3.  You should measure the actual voltage output of the secondary.  If the output is not fully loaded you may read a higher 

voltage than the circuit board can handle. 

  

NOTE

    #1

Отзывы: