background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 6.0

I0000602

FIGURE 1: 

DIMENSIONS

ANALOG SIGNAL AMPLIFIER 

SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The ASA is an analog signal amplifier which 
accepts an analog (voltage or current) signal and 
outputs a voltage signal. Several preset input 
ranges are jumper selectable. It is designed to give 
a Building Automation System signal output the 
power (wattage) to control Maxitrol™ Gas Valves 
normally installed in rooftop units. The top-adjust 
trimmer potentiometers can be used to make fine 
adjustments of gain and offset. The output gain 
can be adjusted anywhere from 1 to 20 times the 
input on the ASA (gain will vary depending on 
type of input). By using voltage divider 
applications, the ASA can also accept a resistance 
input. The offset of the output can be +/- 0 to 20 
VDC. If above 30 watts, derate load current and 
calculate again (P out = [(V out/Load) (V out)] 
and/or (P out = (Load Current)(V out)). The ASA is 
field calibratable, however, factory calibration is 
available upon request for an additional charge. 
This will speed up installation time for the end 
user. 

MOUNTING INSTRUCTIONS

Circuit board may be mounted in any position. If 
circuit board slides out of snap track, a 
non-conductive “stop” may be required.  Use only fingers to remove board from snap track. Slide out of 
snap track or push against side of snap track and lift that side of the circuit board to remove. 

Do not flex 

board or use tools.

WIRING INSTRUCTIONS

PRECAUTIONS

•     Remove power before wiring. Never connect or disconnect wiring with power applied.

•    When using a shielded cable, ground the shield only at the controller end. Grounding both 

ends can cause a ground loop. 

•   It is recommended you use an isolated UL-listed class 2 transformer when powering the unit 

with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may 

result in damage to any device powered by the shared transformer.

•    If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or 

other inductors,  each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI 

Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC 

Transorb or diode, connects to the positive side of the power supply. Without these snubbers, 

coils produce very large voltage spikes when de-energizing that can cause malfunction or 

destruction of electronic circuits.
•    All wiring must comply with all local and National Electric Codes.

2.90” (73.78mm)

3.25”

(82.55mm)

3.25”

(82.55mm)

2.70” (68.58mm)

0.70” 

(17.78mm)

FACTORY CALIBRATION

The ASA is set as follows:

Voltage Input Signal
No Offset to the Output Signal
Input to Output Signal Gain (1:1)
The ASA can be ordered calibrated to your specifications or you may follow the procedure below to set 
your own calibration.
Be sure to check the input, output, GAIN and OFFSET specifications of the ASA. It is possible that the ASA 
cannot re-scale to your requirements.

CHECKOUT

Complete the following steps to change the calibration of the ASA. You will need a digital volt/current 
meter, a 24 to 30 VDC or VAC power supply and a voltage input signal simulator.

EQUIVALENT CALIBRATION VOLTAGE

Use a voltage signal for your input signal during calibration: this makes both the procedure and the 
explanation easier. If you will require a current input when you are finished, use the equation below to find 
the equivalent calibration voltage to use during the calibration procedure:
Equivalent Calibration Voltage = Required Input Signal Amps x 250

Example:

 1 VDC is the equivalent calibration voltage for a 4 mA input signal (1= .004 x 250) or 5VDC is the 

equivalent calibration voltage for a 20 mA input signal (5=.020 x 250).

Step 1)

 Trim Pot Presets

Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight 
clicking sound at either end of their range):
Turn the GAIN pot Full Counterclockwise: = Gain of 1
Turn the OFFSET pots Fully Clockwise: = 0 volts offset

Step 2) 

Jumper Shunt Presets

J1 IN - INCOMING SIGNAL: 

Set in “E” position for voltage input.  

 

 

 

If you require a current input, you will set this shunt in the “I” position    

 

 

                    AFTER you are finished with the calibration procedure.

J2 - OFFSET: 

 

Set in the ‘O’ position for no offset to the output. If you will require a (+)  

 

 

 

or (-) offset, you will set this shunt in the appropriate position in Step 6

Step 3)

 Wiring Connections 

Make the following connections with the power OFF : 
Connect  a  24  to  30  VDC  or  VAC  power  supply  (see  power  supply  information  on  specifications  or                                                               
detail at bottom of page 3 instructions ) to the ASA terminals (+) and COM.
Connect the (-) input signal to the IN (-) terminal.
Connect the (-) meter lead to the OUT (-) terminal. 
Connect (+) input signal lead to the IN (+) terminal.
Connect (+) meter lead to the OUT (+) terminal.

Step 4)

 Power Up

Turn on the power supply: the POWER indicator will light

Step 5)

 Set-Up- Input / Output Signal Adjustments

In this step you will figure the desired voltage/current input signal span and the desired voltage output 
signal span and calibrate the ASA to these input and output signal spans.

To calculate the voltage/current input signal span, subtract the minimum voltage/current input signal from 
the maximum input signal (i.e. a 0 to 5 volt input signal will give you a 5 volt input signal span: 5-0=5).

To calculate the voltage output signal span, subtract the minimum voltage output signal from the 
maximum voltage output signal (i.e. a 3 to 15 volt output signal will give you a 12 volt output signal span: 
15-3=12).

Take the number for the voltage input signal span and apply this voltage to the “IN” (+) and (-) terminals.
Compare the output voltage reading on your meter with the voltage output signal span you calculated 
about. If the meter is higher or lower, adjust the “GAIN” potentiometer until the meter reads the calculated 
output signal span.

Step 6)

 Offset Adjustments

The offset adjustments simply shift the output signal range up or down from a “no offset” setting. For 
example, an output signal range with “no offset” is 3 to 15 volts. The maximum offset range is +/- 0 to 20 
VDC.

Adding an offset of 2 volts would make the output signal range 5 to 17 volts. Subtracting an offset of 2 volts 
would make the output signal range 1 to 13 volts.

Apply the minimum voltage input signal and read the minimum output signal on the meter. With the 
“OFFSET” jumper shunt “J2” in the “0” position, no offset will be added or subtracted from the output signal 
range.

If you need to shift the output signal range up, set the “OFFSET” jumper shunt “J2” in the “+” position and 
adjust the “OFFSET” potentiometer until you increase the voltage reading on the meter to match the 
desired minimum output voltage.

(Remember, this also increases the maximum output by the same amount.)

If you need to shift the output signal range down, set the “OFFSET” jumper shunt “J2” in the “-” position and 
adjust the “OFFSET” potentiometer until you decrease the voltage reading on the meter to match the 
desired minimum output voltage.

(Remember, this also decreases the maximum output by the same amount.)

Step 7)

 Final Adjustments

If you require a current input, set the “J1” IN jumper shunt in the “I” position. Check operation of the ASA for 
desired signal rescaling and operation.

Содержание ASA Series

Страница 1: ...INSTRUCTIONS Circuit board may be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to remove board from snap track Slide out of snap track or push against side of snap track and lift that side of the circuit board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect ...

Страница 2: ... you will require a current input when you are finished use the equation below to find the equivalent calibration voltage to use during the calibration procedure Equivalent Calibration Voltage Required Input Signal Amps x 250 Example 1 VDC is the equivalent calibration voltage for a 4 mA input signal 1 004 x 250 or 5VDC is the equivalent calibration voltage for a 20 mA input signal 5 020 x 250 Ste...

Страница 3: ... signal i e a 3 to 15 volt output signal will give you a 12 volt output signal span 15 3 12 Take the number for the voltage input signal span and apply this voltage to the IN and terminals Compare the output voltage reading on your meter with the voltage output signal span you calculated about If the meter is higher or lower adjust the GAIN potentiometer until the meter reads the calculated output...

Страница 4: ...VDC 10Ω minimum Zero Offset Positive Offset Negative Offset 2 Full Scale Output 2A or 30 Watts maximum 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 40 to 150 F 40 to 65 C 5 to 95 non condensing 40 to 150 F 28 9 to 65 5 C NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Range Impedance Input Current Signal Range Impedance I...

Отзывы: