aci A/PS24 Скачать руководство пользователя страница 1

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

A/PS24 (POWER SUPPLY)

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The A/PS24 adjustable power supply is a low 
cost, dependable external power supply. This 
unit will accept an input of up to 26 VAC or 36 
VDC, and provides an adjustable 1.5 to 26 VDC 
output. Field voltage adjustment is done by 
adjusting a potentiometer using a flat-head 
screwdriver.  The A/PS24 is setup for Half-wave 
rectification from factory, but can be set to 
Full-wave rectification via jumpers. 

MOUNTING

PS24 is supplied with a snap track for 
mounting. The circuit board may be mounted 
in any position. In equipment / electrical 
compartments, mounting upside down at top 
of the enclosure is not recommended as heat 
build-up could be a problem when running 
higher current loads.

Use only fingers to remove board from snap 
track.  Slide out of snap track or push against 
side of snap track and lift that side of the 
circuit board to remove.  Do not flex board or 
use tools. 

WIRING INSTRUCTIONS

PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.

• All wiring must comply with local and National Electric Codes.

• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit 
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may 
result in damage to any device powered by the shared transformer.

• In applications where a Pilot Duty or remote relay is required, the A/DO008 transorb can be 
placed across the coil of the relay to snub electrical spikes when the relays are de-energized. An 
external transorb may not be required if the relay and PS24 power supply is mounted within the 
same control panel.

FIGURE 1:

 

DIMENSIONS

PCB Board

Snap 

Track

2.88”(73.2mm)

0.70”

(17.78mm)

2.05”

(52.07mm)

3.10”(78.74mm)

Fuse

24 VAC

VDC

Output Selection Jumpers

V-OUT

Adjustment

Power

Indicator

(LED)

+

-

+

-

Version 4.0

I0000824

Содержание A/PS24

Страница 1: ...se only fingers to remove board from snap track Slide out of snap track or push against side of snap track and lift that side of the circuit board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with power applied All wiring must comply with local and National Electric Codes It is recommended you use an isolated...

Страница 2: ...tput x current draw from load VA load Example 24 VDC 0 2A 4 8 VA load Determine transformer power from the equation output VA efficiency VA transformer or similar Example 4 8 VA 0 65 7 4 VA transformer 2 Output Connections Connect your load to VDC Terminal Blocks Be mindful of polarity OUTPUT SELECTION JUMPERS HALF WAVE FULL WAVE RECTIFICATION The A PS24 comes with the option of selecting either a...

Страница 3: ... Warranty which is located in the front of ACI S SENSORS TRANSMITTERS CATALOG or can be found on ACI s website www workaci com W E E E DIRECTIVE At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with household waste Do not burn 22 VAC to 26 VAC 50 60Hz or 30 VDC to 36 VDC 24 VDC 1 5 VDC to 26 VDC Jumper Selectable Buil...

Страница 4: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 4 Version 4 0 I0000824 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...

Отзывы: