Fig. 2

XRUD Models 060-161

Installation

Move fan to desired location and fasten securely through mounting holes in base. Shims may be necessary depending upon 

roofing material thickness. The diagram below shows dimensions for Model XRUD.

Access to the motor compartment is accomplished by removing the screws designated “R” in the drawing below. The cover 

can then be removed and placed on a flat surface in an area protected from strong winds that could blow it off the roof.

The voltage rating of the motor must be checked for compatibility to supply voltage prior to final electrical connection.  For 

NFPA - restaurant applications, the electrical supply must enter the motor compartment through the breather tube.  For other 

non-flammable applications, the electrical supply can be routed through the conduit chase between the curb cap and the 

bottom of the motor compartment.  

Consult local code authorities for your specific requirements.

IMPORTANT:  UL/cUL 762 Installations are for Restaurant Applications.

A, B, and C motor RPMs are only approved for this installation.  All must include the suffix “G”.

A drain trough is provided on all XRUD fans for one point drainage of residue. Some means of collection of this residue must 

be provided by either placing a container directly under the trough or by utilizing an adapter to direct the residue to another 

location.  

B

C*

D

A

1

3

/

4

"

R

Dimension “A” is the inside dimension of the curb cap.

The roof curb should be 1-1/2” less than the curb cap to allow for 

roofing and flashing.

*May vary depending on motor size.

Dimensional Data

 

 

 

 

 

 

 

Roof 

Approx. 

 

Model 

D   Damper

 

 

 

 

 

 

 

Opening  Unit Wt.

 

  XRUD-060,065,070,075  17  18

3

/

13

1

/

11

3

/

8x8 

10

1

/

2

x10

1

/

26

  XRUD-080,085,090 

19 

21

 

13

3

/

11

1

/

10x10  12

1

/

2

x12

1

/

33

  XRUD-095

 

19 

21

 

15

1

/

13

7

/

16 

10x10  12

1

/

2

x12

1

/

36 

  XRUD-098,101,121,131  19  24

7

/

23

3

/

17

3

/

12x12  14

1

/

2

x14

1

/

2

 

67

  XRUD-141,161

 

22

 

28

7

/

24

3

/

4

  19

3

/

16x16  18

1

/

2

x18

1

/

2

 

85 

PN 470307

Pre-Starting Checks

Check all fasteners for 
tightness. The wheel 
should rotate freely and 
be aligned as shown at 
right. Wheel position 
is preset and the unit 
tested at the factory. 
However, movement may 
occur during shipment, 
and realignment 
may be necessary. Centering (height alignment) may be 
accomplished by loosening the 
set screws in the wheel and 
moving the wheel to desired 
position.

G

H

MODEL

G

  060-095 

3/32 in.

  098-161 

1/4 in. 

-

H

Wheel Rotation

Direction of rotation is very critical. Improper 
rotation will result in loss of performance,  
excessive horsepower and possible motor 
burnout. Check rotation by energizing the 
unit only momentarily. The rotation should 
be as shown in the 
diagram at right and 
should be in the 
same direction as 
the rotation decals 
affixed to the unit.

Belt Span

Deflection = Belt Span

64

Clockwise

CORRECT

WRONG

WRONG

WRONG

Installation, Operation, and Maintenance Manual

Model XRUD Direct Drive

Upblast Centrifugal Roof Exhaust Fans

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate 
or maintain the unit. Failure to comply with instruction could result in personal injury and/or property damage!
Upon receiving unit, check for any damage that may have occurred during transit and report it immediately to the shipper. 
Also check to see that all accessory items are accounted for. 