40
Parameter
Editable value
Default values
Notes
P47
Selects ΔT for pump modulation (°C)
10 ÷ 40
20
P48
Selects the pump operation
0 … 1
0
0 = intermittent
1 = continuous
P49
Enables OEM
0 ÷ 99
0
49 = allows reading / writing the following parameters
P50
Not used
P51
Not used
P52
Selects the water automatic filling
0 … 1
0
0 = not envisaged
1 = envisaged
DO NOT MODIFY THIS VALUE
P53
Not used
P54
Selects the ACS minimum flow for activation
request
10 ÷ 40 (lx10)/min
15 (1.5l/min)
P55
Selects the ACS post-ventilation time
1 ÷ 30 sec x 10
3
P56
Selects the ACS post-circulation time
0 ÷ 100 sec
30
P57
Increase the fan revolutions number
0 ÷ 10%
0
DO NOT CHANGE
P58
Not used
P59
Not used
P60
Offset additional to the shut-down temperature
after burner ignition
0 ÷ 20
0
DO NOT CHANGE
P61
Selects the fumes exhaust temperature alarm
20 ÷ 150
105
P62
Not used
P63
Not used
P64
Not used
P65
Selects the anti-Legionella function duration
5 ÷ 30 min
15 min
Only for boilers with thermostat
P66
Not used
P67
Not used
P68
DO NOT CHANGE -
Not Used
P69
DO NOT CHANGE -
Not Used
P80
Selects the heating ΔT for circulation blocking
detection
0 ÷ 20
5
0 = disabled
P81
Maximum heating temperature
0 ÷ 150
90
0 = disabled
P82
Selects the Δt maximum permitted on delivery/
return
0 ÷ 50
30
0 = disabled -
DO NOT CHANGE
P83
Selects the countdown in months until
maintenance
0 ÷ 255
0
0 = disabled
P98
Reset TSP to default values
0 … 1
0
P99
Reset OEM to default values
0 … 1
0
Table 10: TSP Parameters General Table