46
13.1
MENU
The following are the main features for navigating the menus, especially describing functions which are not obvious. The main
menu has the following items:
MENU
LABEL
PASSWORD LEVEL
OTHER CONDITIONS
Setpoint
Set
User
Not accessible if connected to Hi-t2
Probes
tP
Installer
---
Alarms
Err
User
Only if active alarms
Digital inputs
Id
Installer
---
Parameters
Par
Installer
---
Password
PSS
User
---
Hours of operation
oHr
Installer
---
USB
USb
Installer
Only with pen drive with relevant update
files
Firmware Version
Fir
Installer
Version, Revision and Sub
Alarm log
Hist
Installer
Only if the log contains data
The PSS menu is accessed to enter the service password and to enable access with a higher user permission. When you have
exited the menus, the password must be entered once again to re-enter.
13.2
SETPOINT MENU
The various setpoints can be viewed and edited.
SETPOINT
DESCRIPTION
UNIT
DEFAULT
RANGE
Coo
First Summer setpoint
°C
7.0
5
-
Co2
Hea
First Winter setpoint
°C
45.0
25
-
60
*San
Sanitary setpoint
°C
48.0
25 - 60
Coo2
Second Summer setpoint
°C
18.0
Coo
-
25
Hea2
Second Winter setpoint
°C
35.0
25- Hea
**rCoo
Mixing valve summer setpoint
°C
15.0
0.0
÷
80
**rHEA
Mixing valve winter setpoint
°C
30.0
0.0
÷
80
(*) If the DHW function is enabled
(**)If Gi module is included, access is only possible with installer password.
13.3
ALARMS MENU [Err]
This menu is only displayed if there are triggered alarms. All of the active alarms can be seen. This is a multi-circuit machine.
Therefore all the alarms are divided by circuit (label ALCx grants access to the alarms of circuit number x).