The motherboard has two relays:
OUT1/relay 1
OUT2/relay 2
The relay settings can be configured in this tab.
Relay 1 is mostly used for transmission errors. If the AZWG10200-PSTN/IP
CONVERTER has still not received any acknowledgement after the third
transmission attempt, this relay is enabled. As soon as an acknowledgement is
received, the relay is reset.
Relay 2 must be set for EN 54-21 applications in accordance with VdS
regulations. This relay is enabled if an error occurs with the supply, the
transmission paths, during programming or with the processor. Once the error
is reset, the relay is also reset. Select the 'Standby current for EN 54-21/VdS
applications' option.
Attention: Once the AZWG10200-PSTN/IP CONVERTER has received new
data via the 'Send' key, the converter is automatically restarted and the
current status of all active notifications is sent. During startup the green
LED flashes for approx. one minute and the left of the two yellow LEDs
flashes approx. two minutes, until all connection paths are active and the
server receives the correct time.
Diagnosis
There are four sub-tabs in the 'Diagnosis' tab:
Modules: status of GSM, Ethernet, supply, converter and time
Alarm lines: status of all inputs
Outputs: status of all relays
System: event log (log book)