Absolute Process Instruments IsoSplitter APD 3393 Скачать руководство пользователя страница 1

IsoSplitter

®

 Potentiometer to DC Signal Splitter/Isolator/Transmitter, Factory Ranged 

APD 3393

1 Input:

 100 

 to 1 M

 Potentiometer

2 Outputs:

  0-1 V to 0-10 V, ±1 V to ±10 V, 0-1 mA to 20 mA, 4-20 mA

 

O

One Input to Two Outputs with Full Isolation

 

O

Zero and Span for Each Output

 

O

Full 1200 V Input/Output /Power Isolation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Output Test Button for Each Channel

 

O

Built-In Loop Power Supplies for Sink/Source I/O

 

Q

Split, Convert, Boost, and Rescale Process Signals

 

Q

Split Process Signals for Control and Validation

 

Q

Interface a Process Signal with Multiple Panel Meters, 
PLCs, Recorders, Data Acq., DCS, & SCADA Systems

Applications

Options—add to end of model number
R1

  Channel 1 I/O reversal (ie. 4-20 mA in to 20-4 mA out) 

R2 

Channel 2 I/O reversal (ie. 4-20 mA in to 20-4 mA out) 

R3 

Channel 1 and channel 2 I/O reversal 

M19

  Channel 1 high voltage output >10 V up to 20 V  

M29 

Channel 2  high voltage output >10 V up to 20 V 

M39 

Channel 1 and channel 2  high voltage output

DF

  Fast response time, consult factory. 

U

 

Conformal coating for moisture resistance

Accessory—order as separate line item
API BP4

  Spare removable 4 terminal plug, black

Description

The APD 3393 IsoSplitter accepts a potentiometer input and 
provides two optically isolated DC voltage or current outputs 
that are linearly related to the input. The input range and each 
output range are independent and can be specified as required. 
This provides an economical solution when one signal must be 
sent to two different devices. 
Typical applications include isolation, output splitting, output 
device separation and redundancy (i.e. to prevent failure of 
the entire loop if one device fails), or a combination of these.
The voltage drop across a stable 1 VDC excitation source is mea-
sured allowing any full-range 3-wire potentiometer to be used. 
The input signal is filtered, amplified, split, and then passed 
through an opto-coupler to the output stages. Full 4-way isola-
tion (input, output 1, output 2, power) make this module useful 
for ground loop elimination, common mode signal rejection, 
and noise pickup reduction.

I/O Sink/Source Versatility

Standard on the APD 3393 are 20 VDC loop excitation sup-
plies for each output channel. These power supplies can be 
selectively wired for sinking or sourcing allowing use with any 
combination of powered or unpowered milliamp I/O devices.

LoopTracker 

API exclusive features include three LoopTracker LEDs (green 
for input, red for each output) that vary in intensity with 
changes in the process input and output signals. 
These provide a quick visual picture of your process loop at all 
times and can greatly aid in saving time during initial startup 
and troubleshooting. 

Output Test 

An API exclusive feature includes output test buttons for each 
channel to provide a fixed output (independent of the input) 
when held depressed. A test button is provide for each output 
channel. The output test greatly aids in saving time during 
initial startup and/or troubleshooting. 
The test output level for each channel is potentiometer adjust-
able from 0 to 100% of the output span. 
Terminals are provided to operate the test functions remotely 
for each channel. This also allows use as a remote manual 
override to provide a temporary fixed output if desired.

Potentiometer Input Ranges

3 wire connection and full potentiometer travel is required  
Consult factory for other ranges and configurations 
1 VDC excitation provided to potentiometer
Minimum range: 

0-100 

 

Maximum range: 

0-1 M

Input Impedance

100 

 to 1 M

Ω 

minimum

Input Protection, Common Mode

100 dB minimum

LoopTracker

Variable brightness LEDs indicate I/O loop level and status 
One for input, one for each output

Channel 1 and Channel 2 DC Output Ranges

Factory configured, please specify for each output channel
Voltage: 

0-1 VDC to 0-10 VDC, 10 mA max

 

up to 20 VDC with M19, M29, M39 

Bipolar voltage:  ±1 VDC to ±10 VDC 
Current: 

0-1 mADC to 0-20 mADC, 4-20 mADC 

 

20 V compliance, 1000 

 at 20 mA

Output Calibration

Multi-turn zero and span potentiometers for each output channel  
±15% of span adjustment range typical

Output Loop Power Supplies

20 VDC nominal, regulated, 25 mADC for each output channel 
May be selectively wired for sinking or sourcing mA output

Output Test/Override

Front momentary buttons or external contact closures for 
each channel to set output test levels.  
Each output test level potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mV

RMS

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.04% of span per °C stability

Response Time

Standard: 70 milliseconds nominal 
DF option: Output noise levels will be greater than standard 
specifications. Consult factory.

Isolation

Full 4-way, 1200 V

RMS

 minimum

Installation Environment

IP 40, requires installation in panel or enclosure with ade-
quate ventilation 
For use in Pollution Degree 2 Environment 
Mount vertically (as shown in picture) to a 35 mm DIN rail 
allowing minimum 1" (25 mm) above and below housing 
vents for air circulation.

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 6 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 6 W maximum

Dimensions and Connectors

1.78" W x 4.62" H x 4.81" D   
45 mm W x 117 mm H x 122 mm D  
Eight 4-terminal removable connectors, 14 AWG max wire size

How to Order

Models are factory ranged. See I/O ranges above left. 
Please specify ranges and options on order

Input range 
Channel 1 output range 
Channel 2 output range

See options at right

Model

Description

Power

APD 3393

IsoSplitter  

1 input to  
2 outputs

85-265 VAC, 50/60 Hz or 

60-300 VDC

APD 3393 D

9-30 VDC or 10-32 VAC

Options and Accessories

© 11-19

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Quick Link: 

api-usa.com/3393

Removable Plugs

Sink or Source  

mA Output for  

Each Channel

Output LoopTracker 

LED for Each 

Channel

Input LoopTracker 

LED

Zero and Span for 

Each Channel

Connect Sink or 

Source mA Input

Custom I/O Ranges

Adjustable Output 

Test Function for  

Each Channel

1     2     3     4

5     6     7    8

9   10   11   12

13   14   15   16

25   26   27   28

29   30   31   32

17   18   19   20

21   22   23   24

See Wiring 

Diagrams on 

Next Page

Universal Power

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

Applications Link 

api-usa.com/apps

Pb

Lead 

Free