High/Low Select Transmitters, 2 to 4 DC Inputs to 1 DC Output, Factory Configured APD 44Hx, APD 44Lx
© 11-19
Input:
0-50 mV to 0-10 VDC, ±25mV to ±10VDC, 0-1 mA to 0-20 mADC, ±0.5 to ±20 mA
Output:
0-1 V to ±10 VDC or 0-2 mA to 0-20 mA, 4-20 mA
O
Versions to Follow the Highest or the Lowest Input
O
1200 V Input/Output/Power Isolation
O
Input LoopTracker
®
LED
O
Zero and Span Output Calibration Potentiometers
O
Functional Test Button
O
Built-In Loop Power Supply for Output
Q
Track Highest or Lowest of Multiple Input Signals
Q
Monitor Maximum Flow From Multiple Pumps
Q
Sensor Redundancy
Applications
Options—add to end of model number
M01
Input/output reversal, such as 4-20 mA input to
20-4 mA output
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare 4-terminal plug, black
Model
Inputs: Factory Configured Output: Factory Configured
Power
APD 44H2
High select from 2 inputs
Specify 2 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44H2 D
9-30 VDC or 10-32 VAC
APD 44H3
High select from 3 inputs
Specify 3 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44H3 D
9-30 VDC or 10-32 VAC
APD 44H4
High select from 4 inputs
Specify 4 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44H4 D
9-30 VDC or 10-32 VAC
APD 44L2
Low select from 2 inputs
Specify 2 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44L2 D
9-30 VDC or 10-32 VAC
APD 44L3
Low select from 3 inputs
Specify 3 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44L3 D
9-30 VDC or 10-32 VAC
APD 44L4
Low select from 4 inputs
Specify 4 input ranges
Specify VDC or mADC range
85-265 VAC or 60-300 VDC
APD 44L4 D
9-30 VDC or 10-32 VAC
All models are factory ranged
The APD 44Lx or APD 44Hx series is configured to your
specifications
Each input can have different ranges and/or units
How to Order
With the model number, please specify
2, 3, or 4 input ranges depending on the model
Output range
Options as required
Description
The APD 44xx series accepts 2, 3 or, 4 DC voltage or current
inputs, depending on the model. They provide an optically
isolated DC voltage or current output that is linearly related to
the highest or lowest of the inputs, depending on the model.
They are used where the highest or lowest of multiple inputs
are required to drive the output, or where sensor redundancy
is needed. Full 3-way isolation (input, output, power) makes
this module useful for ground loop elimination, common mode
signal rejection or noise pickup reduction. The inputs are not
isolated from each other.
The APD 44xx series can be wired to allow a mA output to be
either sinking (passive) or sourcing (active).
LoopTracker
API exclusive features include a green LoopTracker LED that
varies in intensity with changes in the process input signal. It
provides a quick indication of your process input at all times
and can greatly aid in saving time during initial startup and/or
troubleshooting.
Functional Test
An API exclusive feature includes the Functional Test Button to
provide a fixed output (independent of the input) when enabled.
The test output level is potentiometer adjustable from 0 to 100%
of output span. The functional test button greatly aids in saving
time during initial startup and/or troubleshooting.
DC Input Range
Factory configured, please specify each input range or con-
sult factory for special ranges. Each input can have different
ranges and/or units. mA inputs are sinking.
Voltage:
0-50 mVDC to
0-10 VDC
Bipolar voltage:
±25 mVDC to
±10 VDC
Current:
0-1 mADC to 0-20 mADC
Bipolar current:
±0.5 mADC to ±20 mADC
Input Impedance
Voltage:
50 k
Ω
minimum
Current: 50
Ω
nominal
Balance Between Inputs
Better than ±0.5% of span
LoopTracker
Variable brightness LED indicates input loop level and status
DC Output Range
Factory configured, please specify output range
Voltage, 10 mA max.: 0-1 VDC to
0-10 VDC
Bipolar voltage:
±1 VDC to
±10 VDC
Current:
0-2 mADC to 0-20 mADC
20 V compliance, 1000
Ω
at 20 mA
Milliamp output can be field wired for sink or source.
Output Calibration
Multi-turn zero and span potentiometers
±15% of output span typical
Output Loop Power Supply
20 VDC nominal, regulated, 25 mADC, <10 mV
RMS
max. ripple
May be selectively wired for sinking or sourcing mA output
Output Test
Front button sets output to test level. Enabled via pushbutton.
Default setting approximately 50% of span
Potentiometer adjustable 0-100% of span
Output Ripple and Noise
Less than ±0.2% of span
Linearity
Better than ±0.25% of span
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Response Time
50 milliseconds, nominal per channel used
Isolation
1200 V
RMS
minimum
Full isolation: power to each input, power to output, each
input to output.
Non-isolated: input to input
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60HZ or 60-300 VDC, 4W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 4 W maximum
Dimensions
0.89" W x 4.62" H x 4.81" D
22.5 mm W x 117 mm H x 122 mm D
Height includes connectors
api-usa.com
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
Removable Plugs
Sink or Source mA Output
Input LoopTracker
LED
Zero and Span for
Output
Custom I/O Ranges
Adjustable Output
Test/Override
Function
Mixed Voltage or mA Inputs
Universal Power
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Next Page
Quick Link:
api-usa.com/math
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
File E145968
85-265 VAC, 60-300 VDC
model only
Pb
Lead
Free