Dimensions

0.89" W x 4.62" H x 4.81" D   
22.5 mm W x 117 mm H x 122 mm D  
Height includes connectors

DC to DC Transmitters, Isolated, Factory Configured 

APD 4300

Input:

 

0-100 mV to 0-300 VDC, Bipolar Voltages, 0-1 mA to 0-1000 mADC

Output:

 

0-1 V to ±10 VDC or 0-1 mA to 4-20 mA

 

O

Removable Plugs for Faster Installation

 

O

Full 1200 V Input/Output/Power Isolation

 

O

Zero and Span Output Calibration Potentiometers

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Functional Test Button with Remote Capability

 

O

Built-In Loop Power Supplies for Input and Output

 

Q

Convert, Boost, Rescale Process Signals

 

Q

Isolate Single-Ended (Common Ground) PLC Inputs

 

Q

Interface Process Signals with Panel Meters, PLCs, 
Recorders, Data Acquisition, DCS, and SCADA Systems

Applications

Options—add to end of model number
M01

 

Input/output reversal, such as 4-20 mA input to  

 

20-4 mA output

M09

 

High voltage output up to 20 V (specify range)

DF

 

Fast response time, consult factory.

U

 

Conformal coating for moisture resistance

Accessory—order as separate line item
API BP4

  Spare 4-terminal plug, black

Model

Input

Output

Power

APD 4300

Factory configured—specify 

input range

Factory configured—specify 

output range

85-265 VAC or 60-300 VDC

APD 4300 D

9-30 VDC or 10-32 VAC

All models are factory ranged 

The APD 4300 is configured to your specifications.  
Milliamp inputs and outputs can be field wired for sink or 
source.

How to Order

Please specify 

Model 
Input range 
Output range 
Options as required

Description 

The APD 4300 accepts a DC voltage or current input and pro-
vides an optically isolated DC voltage or current output that is 
linearly related to the input. 
Typical applications include signal isolation, conversion, boost-
ing or a combination of the three. Full 3-way isolation (input, 
output, power) makes this module useful for ground loop 
elimination, common mode signal rejection or noise pickup 
reduction.
The APD 4300 can be factory configured for 4-20 mA input and 
4-20 mA output to solve signal isolation, ground loop, common 
mode, or noise pickup problems for non-isolated PLC inputs.
For maximum versatility loop excitation power supplies are 
included for the input and output. A mA input and a mA output 
can be selectively wired for sinking or sourcing. This allows the 
APD 4300 to work with any combination of sinking or sourcing 
mA transmitters and sinking or sourcing mA receiving devices.  

LoopTracker 

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Functional Test 

An API exclusive feature includes the Functional Test Button 
to provide a fixed output (independent of the input) when held 
depressed. The test output level is potentiometer adjustable 
from 0 to 100% of output span. The functional test button 
greatly aids in saving time during initial startup and/or trouble-
shooting.
The functional test can also be enabled with a customer-
supplied external contact closure across terminals 5 and 6. 
This allows remote testing of the output or, for example, a 
PLC-controlled manual override setting. 

DC Input Range

Factory configured, please specify input range or consult fac-
tory for special ranges.  
See table on other side for common ranges.
Voltage: 

0-100 mVDC 

to 

0-300 VDC 

Bipolar voltage: 

±100 mVDC 

to 

±10 VDC 

Current: 

0-1 mADC 

to  0-1000 mADC

Input Impedance (Voltage)

200 k

 minimum

Input Voltage Burden (Current)

1.25 VDC maximum

Common Mode Rejection

120 dB minimum

Input Loop Power Supply

15 VDC nominal, regulated, 25 mADC 
Max. ripple, less than 10 mV

RMS

May be selectively wired for sinking or sourcing mA input

LoopTracker

Variable brightness LEDs indicate I/O loop level and status

DC Output Range

Factory configured, specify output range
Voltage, 10 mA max.:  0-1 VDC  to 

0-10 VDC 

Voltage, M09 option:  0-10 VDC  to 

0-20 VDC 

Bipolar voltage: 

±1 VDC  to 

±10 VDC 

Current: 

0-1 mADC  to  0-20 mADC

 

20 V compliance, 1000 

 at 20 mA

Output Calibration

Multi-turn zero and span potentiometers 
±15% of span adjustment range typical

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC, <10 mV

RMS

 

max. ripple

May be selectively wired for sinking or sourcing mA output

Output Test/Override

Front button sets output to test level when pressed or via 
external contact closure 
Potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mV

RMS

 ripple and noise

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 
Better than ±0.04% of span per °C stability

Response Time

Standard: 70 milliseconds nominal 
DF option: Fast response time. Output noise levels will be 
greater than standard specifications. Consult factory. 

Isolation

1200 V

RMS

 minimum 

Full isolation: power to input, power to output, input to output

Housing and Connectors

IP 40, requires installation in panel or enclosure 
For use in Pollution Degree 2 Environment 
Mount vertically to a 35 mm DIN rail 
Four 4-terminal removable connectors, 14 AWG max wire size

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum

Removable Plugs

Sink or Source  

mA Output

Output LoopTracker 

LED

Input LoopTracker 

LED

Zero and Span for 

Output

Custom I/O Ranges

Adjustable Output 

Test/Override 

Function

Terminals for 

Remote Output 

Test/Override 

Sink or Source  

mA Input

Universal Power

1  2  3  4

5  6  7  8

9 10 11 12

13 14 15 16

See Wiring 

Diagrams on 

Next Page

© 11-19

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Quick Link: 

api-usa.com/4300

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

Applications Link 

api-usa.com/apps

Pb

Lead 

Free

Отзывы: