Strain Gauge/Bridge/Load Cell/Pressure Transducer to DC Transmitters, Field Rangeable 

APD 4058

Input: 

100 

 to 10,000 

 Bridge, 0.5 mV/V to 120 mV/V, 1-10 VDC Excitation

Output: 

0-1 V to ±10 V or 0-2 mA to 4-20 mA (Sink or Source), Non-Isolated

 

O

Adjustable Excitation Power Supply 

 

O

One Minute Setup for Hundreds of I/O Ranges

 

O

Removable Plugs for Faster Installation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Output Test or Calibration Resistor Options

Applications

Options

add to end of model number

M01

 

Switch with built-in calibration resistor. Specify  

 

resistor value. 

M02

 

Switch for external calibration resistor. 

R

 

Input/output reversal, such as 20-4 mA output 

DF10

  10 millisecond response time. 

Option—add to end of model number
U

 

Conformal coating for moisture resistance

Accessory—order as separate line item
API BP4

  Spare removable 4 terminal plug, black

Model

Input

Output

Power

APD 4058

Field configurable. Specify the following if 

factory is to set switches 

Bridge mV/V or mV range 

Excitation voltage

Field configurable. Specify follow-

ing if factory is to set switches 

Output range 

Output type (V or mA)

85-265 VAC or 60-300 VDC

APD 4058 D

9-30 VDC or 10-32 VAC

Description

The APD 4058 accepts an input from a strain gauge, bridge 
type sensor, load cell, or pressure transducer. 
It filters, amplifies, and converts the resulting millivolt signal 
into the selected DC voltage or current output that is linearly 
related to the input. The output is not electrically isolated.
The adjustable excitation power supply generates a stable 
source of voltage to drive your sensor. 
Input, output, excitation and zero offset are field configurable, 
via external rotary and slide switches. 
Offsets up to ±100% of span can be used to cancel sensor 
offsets or non-zero deadweights (taring). 

Sink/Source Versatility

For maximum versatility the APD 4058 milliamp output can be 
selectively wired for sinking or sourcing. This allows connec-
tion to any type of mA input receiving device.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Output Test

An API exclusive feature includes the test button to provide a 
fixed output (independent of the input) when held depressed. 
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting. The test output level is potenti-
ometer adjustable from 0 to 100% of output span.
The output test is not available with the M01 or M02 options. A 
calibration resistor switch replaces the test button.

Dimensions

0.89" W x 4.62" H x 4.81" D  
22.5 mm W x 117 mm H x 122 mm D  
Height includes connectors

Strain Gauge Input Ranges

Minimum range: 

0 to 5 mV 

Maximum range: 

0 to 1200 mV

Minimum sensitivity:  0.5 mV/V 
Maximum sensitivity:  120 mV/V
Millivolt output range is determined by the sensitivity of the 
sensor (mV/V) and the excitation voltage applied. 

mV/V sensitivity  X  excitation voltage  =  total mV range

Input Impedance

1 M

 typical

Common Mode Rejection

100 dB minimum

Calibration Resistor Options

M01 option:  Switch with calibration resistor inside module.  
 

Specify resistor value. 

M02 option:  Switch for external (load cell) calibration resistor.

Excitation Voltage

Maximum output:  10 VDC maximum at 30 mA
Drive capability:  One 100 

Ω 

to 10,000 

 bridge at 10 VDC

Switch selectable: 0-10 VDC in 1 V increments
Fine adjustment:  ±2.5% via multiturn potentiometer
Stability: 

±0.01% per °C

LoopTracker

Variable brightness LEDs for input/output loop level and status

DC Output Ranges

 

Minimum Maximum 

Voltage: 

0-1 VDC 

0-10 VDC (10 mA max) 

Bipolar Voltage: 

±1 VDC 

±10 VDC (±10 mA max) 

Current: 

0-2 mADC 

4-20 mADC 

 

20 V compliance, 1000 

 at 20 mA

Output Calibration

Multi-turn zero and span potentiometers 
±15% of span adjustment range typical
Zero offset switch:  ±100% of span in 15% increments

Output Test

Sets output to test level when pressed 
Potentiometer adjustable 0-100% of span 
Not available with M01 or M02 options

Output Ripple and Noise

Less than 10 mV

RMS

 ripple and noise

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 
Better than ±0.02% of span per °C stability

Response Time

Nominal time at 63.2% of step change 
Standard: 70 milliseconds (14.3 Hz)
DF10 option: Fast response time, 10 milliseconds (100 Hz) 
nominal.  DF option will cause output noise levels to be 
greater than standard specifications. See APD 4059 for custom 
response times.

Housing and Connectors

IP 40, requires installation in panel or enclosure 
For use in Pollution Degree 2 Environment 
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size

Power

Standard:  85-265 VAC, 50/60 Hz or 60-300 VDC 
D option: 

9-30 VDC (either polarity) or 10-32 VAC

Power:  

2 to 5 Watts depending on number of load cells

 

Q

Load Cell Weighing Systems and Scales

 

Q

Strain Gauge Pressure Sensors and Transducers

 

Q

Tanks, Scales, Extruder Melt Pressure, Crane Loads

Connect One 100 

 to 

10,000 

 Load Cell

Output LoopTracker 

LED

Input LoopTracker 

LED

Adjustable Output 

Test Function

Connect mA Output 

for Sink or Source

Hundreds of Range 

Selections

External or Internal 

Calibration Resistor 

Options

Universal 

Power

Zero and Span for 

Output

Removable Plugs

1  2  3  4

5  6  7  8

9 10 11 12

13 14 15 16

See Wiring 

Diagrams on 

Page 3

© 11-19

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Quick Link: 

api-usa.com/4058

Minute 

Setup!

1

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

Applications Link 

api-usa.com/apps

Pb

Lead 

Free

Содержание APD 4058 Series

Страница 1: ...ges Minimum range 0 to 5 mV Maximum range 0 to 1200 mV Minimum sensitivity 0 5 mV V Maximum sensitivity 120 mV V Millivolt output range is determined by the sensitivity of the sensor mV V and the excitation voltage applied mV V sensitivity X excitation voltage total mV range Input Impedance 1 MΩ typical Common Mode Rejection 100 dB minimum Calibration Resistor Options M01 option Switch with calibr...

Страница 2: ...an be set for your application 4 If switch positions are changed repeat the calibration procedure on the last page Precautions Range Setup APD 4058 Output 0 1 V 0 2 V 0 4 V 1 5 V 0 5 V 0 8 V 2 10 V 0 10 V 5 V 10 V 0 2 mA 0 4 mA 0 8 mA 2 10 mA 0 10 mA 0 16 mA 4 20 mA 0 20 mA Switches BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE BCDE Input 2 5 mV 1B0V 1B1V 1B2...

Страница 3: ...ls Typical voltage may be 9 24 VDC Module Power Check model serial number label for module operating voltage to make sure it matches available power Connect power last When using DC power either polarity is acceptable but for consistency with similar API products positive can be wired to terminal 13 and negative can be wired to terminal 16 CAUTION To maintain full isolation avoid wiring DC power s...

Страница 4: ...adjustable from 0 to 100 of the output span Press and hold the Test button and adjust the Test Cal potentiometer for the desired output level Calibration with Resistor Options M01 or M02 Use this calibration procedure if your APD 4058 was ordered with a calibration resistor or if your sensor has its own internal calibration resistor Note Perform the following calibration procedure any time switch ...

Отзывы: