EN - 22
BAL.0713.0 • 2019-02-11
6 Commissioning
TCS-FP
6.6.8 TCS-FP microcontroller PCB
If safety devices (e.g., emergency stop switch)
are not used
, a jumper between terminal clamps A and B as well as
between C and D must be integrated; or sliding switches E and F must be switched to the ON position.
If safety devices (e.g., emergency stop switch)
are used
, sliding switches E and F must be switched to the OFF position.
The safety device must connect clamps A and B (24-V operating voltage) and clamps C and D (GND) in operating mode.
Fig. 15
TCS-FP microcontroller PCB
1
2
3
5
6
7
8
9
10
11
A
B
C
D
E
F
4
12
13 14 15 16
LED Color
Status Description
1
Green
On
“Start+” signal is active
Off
“Start+” signal is not active
2
Green
On
“Start+” signal is active
Off
“Start+” signal is not active
3
Orange
On
“Ready” output is active
Off
“Ready” output is not active
4
Green
On
“S3 collet is closed” end switch was tripped
Off
“S3 collet is closed” end switch was not tripped
5
Green
On
“S4 stroke cylinder is up” end switch was tripped
Off
“S4 stroke cylinder is up” end switch was not tripped
6
Green
On
“S1 stroke cylinder is down” end switch was tripped
Off
“S1 stroke cylinder is down” end switch was not tripped
7
Green
On
“S2 collet is open” end switch was tripped
Off
“S2 collet is open” end switch was not tripped
8
Orange
On
“Y2 close clamping cylinder and motor on” output is active
Off
“Y2 close clamping cylinder and motor on” output is not active
Tab. 14
LED status module
Содержание TCS-FP
Страница 4: ...DE 4 BAL 0713 0 2019 02 11 1 Identifikation TCS FP ...
Страница 5: ...TCS FP 1 Identifikation BAL 0713 0 2019 02 11 DE 5 ...
Страница 34: ...EN 4 BAL 0713 0 2019 02 11 1 Identification TCS FP ...
Страница 35: ...TCS FP 1 Identification BAL 0713 0 2019 02 11 EN 5 ...
Страница 64: ...ES 4 BAL 0713 0 2019 02 11 1 Identificación TCS FP ...
Страница 65: ...TCS FP 1 Identificación BAL 0713 0 2019 02 11 ES 5 ...