2 Technical data
—
2.1 Panel type ZX1.5-R
1) Other values on request basic on insulation situation.
2) Rated frequency 60 Hz on request.
3) Other operating sequence on request.
4) Insulating gas: Sulphur hexafluoride SF
6.
5) 100 kPa=1 bar.
6) Other voltage on request.
Electrical Data
Rated voltage
Rated power frequency withstand voltage
Rated lightning impulse withstand voltage
Minimum operating pressure, 20
℃
Rated frequency
2)
Main busbar rated current
Tee-off rated current
Rated peak withstand current
Rated short-time withstand current, 4 s
Rated short-circuit breaking current for CB
Rated short-circuit making current for CB
Rated operating sequence
Total opening time
Closing time
Insulating gas system
Insulating gas
Minimum functional level for insulation (Pme)
Alarm level for insulation (Pae)
Rated filling level for insulation (Pre)
Motor and release data
Charging motor
Closing coil
Opening coil
Rated supply voltage
DC
Degree of protection (IEC 60529, DIN VDE 0470-1)
High voltage live part
Control cabinet
Ambient temperature
Maximum temperature
Maximum temperature of 24-hours-mean
Minimum value
Opearting Altitude
Dimensions
Height (for transport)
Depth
9) 10) 11)
Width
Height of cable fixing
line to earth
line to line
line to earth
line to line
Absolute
kV
kV
kV
kV
kV
kPa
Hz
A
A
kA
kA
kA
kA
ms
ms
kPa
5)
kPa
kPa
W
W
W
V
℃
℃
℃
m
mm
mm
mm
mm
27.5/2x27.5
95
140
200
325
1201)
50
...2500
...2500
...80
...31.5
...31.5
...80
O-0.3-CO-3 min-CO
3)
30-45
55-70
SF
6
4)
120
1)
120
130
240
250
250
110, 220
6)
IP65
IP4X
7)
+40
+35
-15
...1000
8)
2100
960...1800
500/800
1250
7) Other specification on request.
8) Higher altitude for erection on request.
9) Dependent on the number of cables per line.
10) As an option, with conventional control systems, the panel
depth can be extended by 100 mm.
11) Low voltage compartment depth 400 mm.