background image

Montage 

 

Die Abisolierlänge der Kabelisolation beträgt 21 mm. 
Die Kabelisolation darf nicht unterklemmt werden. 
Fig. 1

Demontage

Fig. 2

Einspeisebeispiele SMISSLINE 125 A System

Fig. 3–5

Einspeisebeispiele SMISSLINE 250 A 
Power Bar System

Fig. 6–8

Montage sur les socles  

F

La longueur de dénudage de l’isolant du câble est 
de 21 mm. L’isolation du câble ne doit pas être coincée. 
Fig. 1

Démontage

Fig. 2

Exemples d’alimentation 
SMISSLINE 125 A Système

Fig. 3–5

Exemples d’alimentation 
SMISSLINE 250 A Power Bar Système

Fig. 6–8

Assembly 

G

The stripping length of the cable insulation is 21 mm. 
The insulation must not be trapped into the terminal. 
Fig. 1

Disconnection

Fig. 2

Supply variants SMISSLINE 125 A System

Fig. 3–5

Supply variants SMISSLINE 250 A  
Power Bar System

Fig. 6–8

Montaggio 

I

La lunghezza di spelatura dell’isolamento del cavo  
è di 21 mm. L’isolamento non deve essere compresso 
nel morsetto. 
Fig.1

Smontaggio

Fig.2

Esempi di alimentazione  
SMISSLINE 125 A Sistema

Fig. 3–5

Esempi di alimentazione 
SMISSLINE 250 A Power Bar Sistema

Fig. 6–8

ABB Switzerland Ltd

Low Voltage Products

Fulachstrasse 150

CH-8200 Schaffhausen

Phone:  +41 58 586 41 11

Fax: 

+41 58 586 42 22

www.abb.com

ABB Ltd

Tower Court,

Coutaulds Way

Foleshill Enterprise Park,

Conventry

CV6 5NX

United Kingdom

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 200 A IEC

max. 150 A UL

max. 125 A

(IEC/UL)

max. 125 A

(IEC/UL)

max. 200 A (IEC)

max. 200 A (IEC)

max. 400 A

(IEC)

max. 200 A

(IEC)

max. 200 A

(IEC)

> 30°

1

2

4

3

1

4

3

2

1

> 30°

1

2

4

3

1

4

3

2

1

U L   d a t a

For all types: 
Feeder Blocks cat. nos. ZLS250 – ZLS253,   ZLS954UL, ZLS959UL are suitable for use in feeder circuits up to 600 V

Wire required to be fixed 2 inches (50.0 mm) below entry point of component housing by suitable cable ties
Rated Voltage:

600 V AC

Short Circuit Rating:

50 kA, max. 480 VAC and 480 Y/277 V and 240 VAC

Short Circuit Protection:

150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating of 250 A,  
located at Line Side

Torque: 

2.0 Nm

Stripping length:

21 mm

Wire size:

2 AWG - 1/0 AWG

Wire rated min. 600 V and 75 °C (AVLV2/8)

1

2

max. 125 A (IEC/UL)

max. 125 A (IEC/UL)

max. 200 A

 (IEC/UL)

max. 125 A

 (IEC/UL)

max. 125 A

(IEC/UL)

max. 200 A (IEC)

max. 200 A (IEC)

max. 200 A (IEC)

max. 200 A (IEC)

max. 200 A (IEC)

max. 200 A (IEC)

max. 400 A

(IEC)

max. 200 A

(IEC)

max. 200 A

(IEC)

4

6

8

3

5

7

Отзывы: