ABB | SACE Tmax XT
64 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 11 - Power protections
D Protection
I7
t
t7fw
I
D
t7bw
Function
D protection is very similar to S protection, with the additional capability of recognizing the direction of the
current during a fault.
The current direction allows the user to find out whether the fault is on the supply side or load side of the
device controlled by Ekip Touch.
In ring type distribution systems, D protection allows the distribution section in which the fault has occurred
to be identified and disconnected without affecting the rest of the installation (using zone selectivity).
Depending on the direction of the fault, if the current of one or more phases exceeds threshold I7 (I7fw or
I7bw) for longer than time t7 (t7fw or t7bw), the protection activates and sends a TRIP command.
The
fault direction
is established by comparing the
detected fault current
with the
reference direction
.
NOTE:
the reference direction is calculated considering the set value of the power flow
direction and the phase sequence (cyclic direction of the phases):
Phase sequence (set) Power flow (set)
Phase sequence
(detected)
Reference direction
(forward direction)
123
High-->Low
123
High-->Low
123
Bottom --> Top
123
Bottom --> Top
123
High-->Low
321
Bottom --> Top
123
Bottom --> Top
321
High-->Low
321
High-->Low
123
Bottom --> Top
321
Bottom --> Top
123
High-->Low
321
High-->Low
321
High-->Low
321
Bottom --> Top
321
Bottom --> Top
To check and simulate the trip times in relation to all the parameters, please consult:
• the summary table of the protections with the calculation formulas (page 88)
• the graph with trip curve (page 103)
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
ON
Threshold I7 Fw
Establishes the value that activates the protection with forward direction.
The value is given as both absolute value (Amperes) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
4 In
Threshold i7 Bw
Establishes the value that activates the protection with backward direction.
The value is given as both absolute value (Amperes) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
4 In
Time t7 Fw
This is the trip time in the case of forward direction.
The value is given in seconds and can be set within the range: 0.1 s to 0.8
s, in 0.01 s steps
0,2 s
Time t7 Bw
This is the trip time in the case of backward direction.
The value is given in seconds and can be set within the range: 0.1 s to 0.8
s, in 0.01 s steps
0,2 s
ZoneSelectivity
(1)
Activates/deactivates the function and selectivity time availability on the
display.
NOTE
: configure selectivities S, S2, I, 2I, MCR, G, Gext and MDGF
OFF to ensure that selectivity D functions correctly
OFF
Selectivity t
ime Fw
(1)
This is the trip time of the protection with the zone selectivity function
activated, forward direction and selectivity input Fw not present.
The value is given in seconds and can be set within the range: 0.1 s to 0.8
s, in 0.01 s steps
0,13 s
Selectivity
time Bw
(1)
This is the trip time of the protection with the zone selectivity function
activated, backward direction and selectivity input Bw not present.
The value is given in seconds and can be set within the range: 0.1 s to 0.8
s, in 0.01 s steps
0,13 s
Continued on the next page
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...