ABB | SACE Tmax XT
Protections | 9 - Voltage Advanced protections
59 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
RV Protection
U22
t
t22
V
RV
Function
The protection trips if loss of insulation occurs (verification of residual voltage U0); the protection sends a
TRIP command if voltage U0 exceeds threshold U22 for longer than t2.
The protection is always available in the 4P configuration; if presence of neutral voltage is activated in
Measurement
module (page 137). protection is also available for 3P and 3P + N configurations.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 101)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold U22
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un)
and can be set within the range: 0.05 Un to 0.5 Un in 0.001 Un steps
0,15 Un
Time t22
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.05 s to 120 s, in 0.01 s steps
15 s
Reset Time
This is the time the alarm is retained after the protection has quit the
alarm condition; it can be useful for keeping the timing activated when
the protection is temporarily deactivated.
The value is given in seconds and can be set within the range: 0 s to
0.2 s, in 0.02 s steps
0 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...