2104349 rev. AD
Page 4
–29
Figure 4
–13 RTD calibration screen
The Current Value parameter will display the current value of the selected RTD by
placing a check mark in the Update field.
4.16.1 Step-by-step instructions
1) Connect the variable resistor or RTD calibration equipment to J7 on the G4
EX board.
Terminal
J7
1
SHLD
2
Out
3
Plus (+)
4
Minus (-)
5
In
If the user elects to calibrate using an 100 OHM RTD probe,
refer to the PCCU32 Help Files to view resistance and
corresponding temperature readings.
2) Select the RTD tab within the Analog Inputs tab sub-menu under Onboard
I/O in the Calibration window.
3) Select whether to perform a 3 Point, 5 Point or Bias calibration. Note that if
a 3 Point is selected, there will be 3 Target values and 3 Cal Point buttons.
If 5 Point is selected, there will be 5 Target values and 5 Cal Point buttons.