Page 4
–4
2104349 rev. AD
There is a chance that the user will see a PCCU32 dialog
box display that informs them that the Target Device Loader
is not working. The user will need to follow the dialog box
instructions to warm boot the system.
4.4.2.2
Method 2
The user must be in Expert view.
1) Move into Entry mode within PCCU32.
2) Upon completion, click on the Meter ID in the PCCU32 tree-view. By
default, this will take the user to the Station Setup tab.
3) Locate the System Shutdown/then Reset parameter field. Once located, set
the parameter value to Yes.
4) Click the Send button. This will initiate a warm boot.
4.4.2.3
Method 3
1) Move into Entry mode within PCCU32.
2) Once this has been completed, click the Terminal icon on the PCCU32
window toolbar. This will bring up the Terminal window.
3) Once in the Terminal window, move to the terminal prompt (->), and type in
the following: BOOT=WARM. Press Enter on the keyboard to initiate the
warm boot.
4.5
Performing a Cold Boot
A cold boot occurs when the user cuts power to the board, including the lithium
battery backup. This causes a loss of all historical data. A cold boot can be
initiated from a hardware or software standpoint. The following will take the user
through both methods.
4.5.1 Hardware Cold Boot
1) Open the door to the unit. Locate the lithium battery connector.
2) Upon location, disconnect the battery.
3) Press the Reset button for approximately five seconds. The unit will cold
boot.