A standard kit with orifices of different diameter, including the retainer and gasket is
available, Article number:
TU_KIT01
.
To choose the best size of the orifice, assure the maximum level of intensity do not
exceed 85% with associated burner in operation at maximum load and remain at decent
level, preferably above 40% when the associated burner is operating at the minimum
rate.
Detecting Flicker-Frequency Noise
SF910i has a precision A/D converter that can measure very small Flicker-Frequency
levels in the flame scanner input signal.
If electrical noise exists in the Flame Scanner wiring, the SF910i may detect the electrical
noise if the Flicker-Frequency sensitivity is set too low.
During initial Flame Scanner tuning, the system must be checked to ensure that no
electrical noise is present.
Check for Electrical Noise
–
Darken the Flame Scanner by making sure that it is not exposed to any flame or
ambient light.
–
Set the Flicker-Frequency sensitivity to the minimum value expected for the
application.
–
Select frequency as the value to be shown on the display.
Flicker-Frequency displayed must be 0 Hz. If it is not 0 Hz, the minimum Flicker-Frequency
sensitivity must be raised or the electrical wiring inspected for proper shielding and
installation.
Smoothing
Smoothing filters are algorithms to smooth variations in the Measured-Value values.
Smoothing provides more consistent signals for analysis. This allows for more sensitive
trip points without causing unnecessary Flame-Off conditions.
There are 11 stages of smoothing available for Measured-Values.
Smoothing function values can be set from NONE to 10.
–
A value of NONE disables smoothing filters.
–
Disabling smoothing will maximize the speed of flame detection.
–
A value of 1 provides the minimum amount of smoothing.
–
A value of 10 provides the maximum amount of smoothing.
8VZZ005286 B
88
11 Configuration Parameters in Flame Explorer
Содержание Uvisor SF910i
Страница 1: ...Combustion Instrumentation User Manual Uvisor SF910i Integrated SafeFlame Scanner PROCESS AUTOMATION...
Страница 2: ......
Страница 6: ......
Страница 20: ...8VZZ005286 B 20...
Страница 30: ...8VZZ005286 B 30...
Страница 67: ...Figure 7 5 Version Display in Normal Mode 8VZZ005286 B 67 7 Operating Display 7 5 Version Display...
Страница 68: ...8VZZ005286 B 68...
Страница 78: ...8VZZ005286 B 78...
Страница 90: ...8VZZ005286 B 90...
Страница 92: ...8VZZ005286 B 92...
Страница 97: ...Figure 14 2 Flame Temperature Parameters Screen 8VZZ005286 B 97 14 Flame Temperature Measurement...
Страница 98: ...8VZZ005286 B 98...
Страница 108: ...8VZZ005286 B 108...
Страница 114: ...8VZZ005286 B 114...
Страница 118: ...8VZZ005286 B 118...
Страница 125: ...8 Fit in place the SF910i Flame Scanner 8VZZ005286 B 125 19 Repair and Replacement 19 2 Fiber Optic Replacement...
Страница 126: ...8VZZ005286 B 126...
Страница 128: ...8VZZ005286 B 128...
Страница 130: ...8VZZ005286 B 130...
Страница 150: ...8VZZ005286 B 150...
Страница 151: ...Appendix E Drawings 8VZZ005286 B 151 E Drawings...
Страница 152: ...Figure E 1 Enclosure Quick Release Connector and Version LOS 8VZZ005286 B 152 E Drawings...
Страница 153: ...Figure E 2 Enclosure NPT Cable Inlet and Version LOS 8VZZ005286 B 153 E Drawings...
Страница 154: ...Figure E 3 Enclosure Quick Release Connector and Version FOC 8VZZ005286 B 154 E Drawings...
Страница 155: ...Figure E 4 Enclosure NPT Cable Inlet and Version FOC 8VZZ005286 B 155 E Drawings...
Страница 156: ...Figure E 5 FOC Flexible Assembly 8VZZ005286 B 156 E Drawings...
Страница 157: ...Figure E 6 FOC Rigid Assembly 8VZZ005286 B 157 E Drawings...
Страница 160: ...Figure E 9 Bailey Flame ON Standard Replacement 8VZZ005286 B 160 E Drawings...
Страница 161: ...Figure E 10 Typical Bailey Flame ON Installation 8VZZ005286 B 161 E Drawings...
Страница 162: ...8VZZ005286 B 162...
Страница 164: ...F 1 Earth Connection Cable Figure F 1 Earth Connections 8VZZ005286 B 164 F Cables F 1 Earth Connection Cable...
Страница 170: ...8VZZ005286 B 170...
Страница 172: ...Figure G 1 Diaphragm for SF910i FOC Scanner 8VZZ005286 B 172 G Fittings G 1 TU_KIT03 Set of Diaphragms for SF910i FOC...
Страница 178: ...G 7 Counter Flange 8VZZ005286 B 178 G Fittings G 7 Counter Flange...
Страница 179: ...Figure G 7 Boiler Mounting Counter Flange for FOC Installation 8VZZ005286 B 179 G Fittings G 7 Counter Flange...
Страница 189: ......